Local heat transfer distribution and effect of instabilities during flow boiling in a silicon microchannel heat sink

被引:50
|
作者
Chen, Tailian [3 ]
Garimella, Suresh V. [1 ,2 ]
机构
[1] Purdue Univ, Sch Mech Engn, NSF IUCRC, Cooling Technol Res Ctr, W Lafayette, IN 47907 USA
[2] Purdue Univ, Birck Nanotechnol Ctr, W Lafayette, IN 47907 USA
[3] Gonzaga Univ, Dept Mech Engn, Spokane, WA 99258 USA
关键词
Flow boiling; Microchannels; Boiling regimes; Flow instability; Electronics cooling; DIELECTRIC COOLANT; FLUID; EVAPORATION; MASS;
D O I
10.1016/j.ijheatmasstransfer.2011.04.012
中图分类号
O414.1 [热力学];
学科分类号
摘要
Flow boiling of the perfluorinated dielectric fluid FC-77 in a silicon microchannel heat sink is investigated. The heat sink contains 60 parallel microchannels each of 100 mu m width and 389 mu m depth. Twenty-five evenly distributed temperature sensors in the substrate yield local heat transfer coefficients. The pressure drop across the channels is also measured. Experiments are conducted at five flow rates through the heat sink in the range of 20-80 ml/min with the inlet subcooling held at 26 K in all the tests. At each flow rate, the uniform heat input to the substrate is increased in steps so that the fluid experiences flow regimes from single-phase liquid flow to the occurrence of critical heat flux (CHF). In the upstream region of the channels, the flow develops from single-phase liquid flow at low heat fluxes to pulsating two-phase flow at high heat fluxes during flow instability that commences at a threshold heat flux in the range of 30.5-62.3 W/cm(2) depending on the flow rate. In the downstream region, progressive flow patterns from bubbly flow, slug flow, elongated bubbles or annular flow, alternating wispy-annular and churn flow, and wall dryout at highest heat fluxes are observed. As a result, the heat transfer coefficients in the downstream region experience substantial variations over the entire heat flux range, based on which five distinct boiling regimes are identified. In contrast, the heat transfer coefficient midway along the channels remains relatively constant over the heat flux range tested. Due to changes in flow patterns during flow instability, the heat transfer is enhanced both in the downstream region (prior to extended wall dryout) and in the upstream region. A previous study by the authors found no effect of instabilities during flow boiling in a heat sink with larger microchannels (each 300 mu m wide and 389 mu m deep); it appears therefore that the effect of instabilities on heat transfer is amplified in smaller-sized channels. While CHF increases with increasing flow rate, the pressure drop across the channels has only a minimal dependence on flow rate once boiling is initiated in the microchannels, and varies almost linearly with increasing heat flux. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3179 / 3190
页数:12
相关论文
共 50 条
  • [31] Optimizing microchannel heat sink performance: Effect of step-gap design and contraction on flow boiling stability and heat transfer
    Sulaiman, Mohammed W.
    Wang, Chi-Chuan
    APPLIED THERMAL ENGINEERING, 2024, 257
  • [32] Simulation of subcooled flow boiling in manifold microchannel heat sink
    Luo, Yang
    Li, Wei
    NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2020, 77 (11) : 951 - 965
  • [33] SIMULATION OF SUBCOOLED FLOW BOILING IN MANIFOLD MICROCHANNEL HEAT SINK
    Luo, Yang
    Zhang, Jingzhi
    Li, Wei
    PROCEEDINGS OF THE ASME 2020 18TH INTERNATIONAL CONFERENCE ON NANOCHANNELS, MICROCHANNELS, AND MINICHANNELS (ICNMM2020), 2020,
  • [34] Experimental investigation of non-uniform heating effect on flow boiling instabilities in a microchannel-based heat sink
    Bogojevic, D.
    Sefiane, K.
    Walton, A. J.
    Lin, H.
    Cummins, G.
    Kenning, D. B. R.
    Karayiannis, T. G.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (03) : 309 - 324
  • [35] Effect of flow pulsation on heat transfer performance of biomimetic bark microchannel heat sink
    Daba, Robera
    Xu, Shanglong
    Wang, Weijie
    Huang, Yi
    Luo, Xinkai
    Fang, Kuang
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 56
  • [36] Comparative experimental procedures for measuring the local heat transfer coefficient during flow boiling in a microchannel
    Bortolin, Stefano
    Bortolato, Matteo
    Azzolin, Marco
    Del Col, Davide
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2018, 90 : 231 - 245
  • [37] Flow boiling heat transfer and pressure drop characteristics in expanding silicon microgap heat sink
    Tamanna, Alam
    Lee, Poh Seng
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 82 : 1 - 15
  • [38] Effect of outlet plenum design on flow boiling heat transfer in microchannel heat sinks
    Hedau, Gaurav
    Raj, Rishi
    Saha, Sandip K.
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2021, 23
  • [39] Single-phase and flow boiling heat transfer characteristics in staggered finned manifold microchannel heat sink
    Zhang, Jingzhi
    Xu, Jinjin
    Han, Hao
    Lei, Li
    Xin, Gongming
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 60
  • [40] An experimental study on flow boiling heat transfer of R134a in a microchannel-based heat sink
    do Nascimento, Francisco Julio
    Souza Lara Leao, Hugo Leonardo
    Ribatski, Gherhardt
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2013, 45 : 117 - 127