Flexible Fault Current Adaptation Features of a Novel DC Circuit Breaker Assisted by Superconducting Fault Current Limiters

被引:3
|
作者
Li, Hongxu [1 ]
Xiang, Bin [1 ]
Wang, Xuedong [1 ]
Li, Siyi [1 ]
Liu, Siyuan [1 ]
Geng, Yingsan [1 ]
Liu, Zhiyuan [1 ]
Wang, Jianhua [1 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Capacitors; Fault currents; Resistance; Circuit breakers; Integrated circuits; Voltage; Yttrium barium copper oxide; HVDC; DC circuit breaker; superconducting fault current limiter; quenching voltage of superconducting coils; MODEL;
D O I
10.1109/TPWRD.2021.3125498
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The high di/dt before zero-crossings easily leads to delayed or failed operations for the active current injection mechanical DC circuit breaker, especially for small direct current interruptions. The pre-charging process also makes this type of circuit breaker hard to realize repeat operations economically in the high voltage DC system. This paper proposes a novel DC circuit breaker and its design method that deeply coordinating a superconducting fault current limiter with the active current injection DC circuit breaker. This method significantly reduces di/dt before current zero-crossings and enables repeat operations economically. Besides limiting fault currents, the superconducting fault current limiter also charges the resonance capacitor flexibly in the circuit breaker, realizing the injected reverse current keep a constant proportion to the arbitrary fault current. Validations of the flexible capacitor charge and repeat operations are made by simulation and low voltage experiments. The charging times are within 2.5 ms and the reverse current keeps 1.2 to 1.7 times over the fault current under arbitrary conditions. Di/dt at current zero is reduced by 80% under 30% of rated interruption capacity. Flexible capacitor charge experiments are consistent with the simulation design. The superconducting tapes can recover within 300 ms to support repeat operations.
引用
收藏
页码:2348 / 2358
页数:11
相关论文
共 50 条
  • [21] Superconducting Fault Current Limiters Saving Rate
    Manusov, V. Z.
    Mikheyev, P. A.
    IFOST 2008: PROCEEDING OF THE THIRD INTERNATIONAL FORUM ON STRATEGIC TECHNOLOGIES, 2008, : 538 - 539
  • [22] Fault Current Limitation Coordination in Electric Power Grid With Superconducting Fault Current Limiters
    Hayakawa, Naoki
    Maeno, Yuya
    Kojima, Hiroki
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2018, 28 (04)
  • [23] Comparison between Resistive and Inductive Superconducting Fault Current Limiters for Fault Current Limiting
    Aly, Mohamed M.
    Mohamed, Emad A.
    2012 SEVENTH INTERNATIONAL CONFERENCE ON COMPUTER ENGINEERING & SYSTEMS (ICCES'2012), 2012, : 227 - 232
  • [24] Full-range Currents Interruption Methods by Coupling Current Injection DC Circuit Breakers with Superconducting Fault Current Limiters
    Li H.
    Xiang B.
    Yu S.
    Geng Y.
    Liu Z.
    Wang J.
    Gaodianya Jishu/High Voltage Engineering, 2022, 48 (11): : 4497 - 4505
  • [25] Utility Perspective on Fault Current Limiters and Expected Synergies from Integrating Fault Current Limiters with Superconducting Cables
    Duggan, P. M.
    2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11, 2008, : 2636 - 2637
  • [26] Resistive Superconducting Fault Current Limiter - Integrated Bidirectional Hybrid DC Circuit Breaker for HVDC Systems
    Reddy, Siddavatam Ravi Prakash
    Rajashekara, Kaushik
    Krishnamoorthy, Harish Sarma
    2022 INTERNATIONAL POWER ELECTRONICS CONFERENCE (IPEC-HIMEJI 2022- ECCE ASIA), 2022, : 2004 - 2008
  • [27] SF6passive resonance DC circuit breaker combined with a superconducting fault current limiter
    Xiang, Bin
    Cheng, Nuo
    Yang, Kun
    Liu, Zhiyuan
    Geng, Yingsan
    Wang, Jianhua
    Yanabu, Satoru
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (14) : 2869 - 2878
  • [28] Superconducting Fault Current Limiters for Multi-terminal DC Grid Applications
    Bahirat, H. J.
    Khaparde, S. A.
    Kodle, S.
    Tekletsadik, K.
    Dabeer, V.
    2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), 2016,
  • [29] Design and experiments of novel hybrid type superconducting fault current limiters
    Lee, B. W.
    Park, K. B.
    Sim, J.
    Oh, I. S.
    Lee, H. G.
    Kim, H. R.
    Hyun, O. B.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) : 624 - 627
  • [30] Cascaded commutation circuit for a hybrid DC breaker with dynamic control on fault current and DC breaker voltage
    Shan, Yunhai
    Lim, Tee C.
    Finney, Stephen J.
    Guang, Weixiao
    Williams, Barry W.
    Holliday, Derrick
    Ding, Xiao
    IET POWER ELECTRONICS, 2017, 10 (06) : 676 - 686