Graphic general solutions for desiccant coated heat exchangers based on dimensional analysis

被引:16
|
作者
Hua, L. J. [1 ]
Sun, X. Y. [1 ]
Jiang, Y. [1 ]
Ge, T. S. [1 ]
Wang, R. Z. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, 800 Dongchuan Rd, Shanghai 200240, Peoples R China
基金
中国国家自然科学基金;
关键词
Dimensional analysis; Desiccant coated heat exchangers; Mass transfer; Graphic general solutions; Stepwise elongation; ENERGY WHEEL EFFECTIVENESS; METAL-ORGANIC FRAMEWORK; MASS-TRANSFER; PERFORMANCE; ADSORPTION; PUMP; DYNAMICS; MODEL; AIR;
D O I
10.1016/j.ijheatmasstransfer.2020.119654
中图分类号
O414.1 [热力学];
学科分类号
摘要
Solid desiccant, featuring thermally-driven mass transfer, is nowadays a hotspot in the field of mass adsorption/separation, energy allocation and water harvesting. Former studies indicate that the efficiency in such systems is dominated by the adsorption dynamics of the desiccant-based components. Accordingly, enormous efforts have been attempted on it to derive comprehensive parametric analysis or even theoretical solutions. Given the complexity in adsorption nature and the diversity in sorbent-sorbate interaction, however, the results obtained are either biased for incomplete research or lack of precision due to oversimplification. Here, we propose that dimensional analysis can fill this niche by its potential in freedom reduction and feature generalization. Specifically, desiccant coated heat exchangers (DCHEs) are chosen to demonstrate the method. Our work reveals, 4 dimensionless indexes (Psi(a), K-0, K-1, K-2), extracting from 13 original parameters, are sufficient to identify the adsorption performance in DCHEs, hence making the derivation of graphic general solutions possible. Meanwhile, stepwise elongation method is outlined to overcome the common difficulties aroused by nonlinear isotherms. It is for the first time that the dehumidification performance of DCHEs can be universally represented in a concise form, regardless of the disparities in operating temperature, inlet flow conditions, device configuration and desiccant properties. Afterwards, the application range of the proposed graphic solutions is specified. In view of the compatible nature of dimensional analysis, this method can be expediently extended to other sorption-related devices, and thus propels the theoretical development and technological innovation in the corresponding field. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:10
相关论文
共 50 条
  • [41] Parametric analysis of a liquid desiccant air conditioner using corrugated plate heat exchangers
    Khoshkhoo, Haghighi R.
    Shayegan, P.
    Mohammadi, Seif S.
    CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 535 - 540
  • [42] A novel curdlan based desiccant coated heat exchanger for efficient dehumidification
    Lei, Xiaoping
    Ying, Wenjun
    Xue, Zhaoran
    Zhang, Hua
    Wang, Jiayun
    SCIENTIFIC REPORTS, 2025, 15 (01):
  • [43] Experimental performance evaluation of desiccant coated heat exchangers from a combined first and second law of thermodynamics perspective
    Vivekh, P.
    Bui, D. T.
    Islam, M. R.
    Zaw, K.
    Chua, K. J.
    ENERGY CONVERSION AND MANAGEMENT, 2020, 207
  • [44] A general solution for one-dimensional multistream heat exchangers and their networks
    Luo, X
    Li, ML
    Roetzel, W
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2002, 45 (13) : 2695 - 2705
  • [45] Design and experimental study on a hybrid adsorption refrigeration system using desiccant coated heat exchangers for efficient energy utilization
    Xu, Jing
    Pan, Qaunwen
    Zhang, Wei
    Liu, Zhiliang
    Wang, Ruzhu
    Ge, Tianshu
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2022, 169
  • [46] Feasible study of a self-cooled solid desiccant cooling system based on desiccant coated heat exchanger
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    Li, Y.
    APPLIED THERMAL ENGINEERING, 2013, 58 (1-2) : 281 - 290
  • [47] Multi-mode integrated system of adsorption refrigeration using desiccant coated heat exchangers for ultra-low grade heat utilization
    Pan, Q. W.
    Xu, J.
    Ge, T. S.
    Wang, R. Z.
    ENERGY, 2022, 238
  • [48] GENERAL METHOD FOR ANALYSIS OF COMPACT MULTIFLUID HEAT-EXCHANGERS
    DEMETRI, EP
    PLATT, M
    MECHANICAL ENGINEERING, 1972, 94 (09) : 53 - &
  • [49] Experimental study and analysis of solar based winter air conditioning system using desiccant coated heat exchanger
    Nain, Sunil
    Parinam, Anuradha
    Kajal, Sanjay
    MATERIALS TODAY-PROCEEDINGS, 2021, 46 : 9938 - 9943
  • [50] Preparation and Application of UiO-66 in Desiccant-Coated Heat Exchanger-Based Desiccant Cooling Systems
    Zheng, Xu
    Ma, QanLing
    Tan, Jianming
    Yu, Bo
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2021, 60 (12) : 4727 - 4734