Research on Leakage Current Waveform Spectrum Characteristics of Artificial Pollution Porcelain Insulator

被引:27
|
作者
Fang, Chunhua [1 ]
Tao, Yuning [1 ]
Wang, Jianguo [2 ]
You, Haixin [1 ]
Cui, Yan [1 ]
Zhou, Mi [2 ]
机构
[1] China Three Gorges Univ, Coll Elect Engn & New Energy, Yichang, Peoples R China
[2] Wuhan Univ, Sch Elect Engn, Wuhan, Peoples R China
基金
中国国家自然科学基金;
关键词
leakage current; insulator; pollution flashover; flashover voltage; transmission line; FREQUENCY-CHARACTERISTICS; CLASSIFICATION; HARMONICS; RATIOS; TIME;
D O I
10.3389/fenrg.2021.798048
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The surface discharge development processes of polluted porcelain insulators for power transmission lines are tightly related with the development of leakage current (LC), the characteristics of LC, the insulating condition, and discharge intensity of the insulator surface have an important significance for revealing the contamination discharge state of insulators. In order to analyze the LC characteristics of porcelain insulators in the process of pollution flashover, artificial pollution flashover tests on porcelain insulators were conducted in the artificial fog cabinet, and the characteristics of LC waveforms in time-domain and frequency-domain were simultaneously measured and analyzed during the tests. The results indicated that the amplitude of LC, fundamental harmonic, the third harmonic, and fifth harmonic had a strong correlation, the maximum of LC(I-m), the rate of total harmonics (THD), and the phase difference of fundamental harmonic (theta) were used for the representation of the characteristics of the LC waveform. The LC has the characteristics of high amplitude, low proportion harmonic, and small phase difference between the fundamental harmonic and voltage before the flashover occurrence. The test results provide effective reference for porcelain insulators in pollution flashover forecasting.
引用
收藏
页数:8
相关论文
共 50 条
  • [31] Leakage current characteristics of long insulator string during DC pollution flashover test under varIOUS air pressures
    Yu Xinzhe
    Zhang Qiaogen
    Yang Hao
    Yu Xinzhe
    Zhou Jun
    Liu Bo
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 481 - 484
  • [32] Condition Monitoring of 11kV Porcelain Pin Insulator extracting Surface Current from Total Leakage Current
    Deb, Suhas
    Ghosh, Riddhi
    Dutta, Santu
    Dalai, Sovan
    Chatterjee, Biswendu
    2017 3RD INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2017, : 403 - 406
  • [33] Insulator Leakage Current Studies in Artificial Climatic Chambers Using Dimensional Analysis
    Bashir, N.
    Ahmad, H.
    INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE, 2009, 4 (06): : 1433 - 1439
  • [34] Letter to the editor: Variation of leakage current with SDD on an artificially polluted porcelain pin insulator - An experimental study
    Dixit, Pradimumar
    Gopal, H. G.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2007, 35 (03) : 359 - 365
  • [35] Study of Composite Insulator Leakage Current Characteristics in Contamination and Humidity Conditions
    Wang, Cong
    Lii, Tianfu
    Peng, Qingjun
    Tul, Youping
    Zou, Lifeng
    Zhang, Shaoquan
    2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 353 - 356
  • [36] Frequency characteristics of leakage current waveforms of an artificially polluted suspension insulator
    Suda, T
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (04) : 705 - 709
  • [37] Leakage current characteristics in estimating insulator reliability: experimental investigation and analysis
    Ali Ahmed Salem
    Kwan Yiew Lau
    Wan Rahiman
    Zulkurnain Abdul-Malek
    Samir A. Al-Gailani
    R. Abd Rahman
    Salem Al-Ameri
    Scientific Reports, 12
  • [38] Leakage current characteristics in estimating insulator reliability: experimental investigation and analysis
    Salem, Ali Ahmed
    Lau, Kwan Yiew
    Rahiman, Wan
    Abdul-Malek, Zulkurnain
    Al-Gailani, Samir A.
    Abd Rahman, R.
    Al-Ameri, Salem
    SCIENTIFIC REPORTS, 2022, 12 (01)
  • [39] Study on Leakage Current Characteristics and Electrical Equivalent Circuit Properties of Aged Polymer Insulator under Artificial Environmental Condition
    Rachmawati
    Wakhidin, Mohamad
    Suwarno
    2018 4TH IEEE CONFERENCE ON POWER ENGINEERING AND RENEWABLE ENERGY (ICPERE 2018), 2018, : 165 - 170
  • [40] Research for the LED optical fiber sensor for the leakage current of the insulator string
    Wang, Jian
    Yao, Chenguo
    Mi, Yan
    Zhang, Ximing
    Li, Chengxiang
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,