Prediction of Change in Equivalent Circuit Parameters of Transformer Winding Due to Axial Deformation using Sweep Frequency Response Analysis

被引:4
|
作者
Sathya, M. Arul [1 ]
Usa, S. [1 ]
机构
[1] Anna Univ, Coll Engn, Dept Elect & Elect Engn, Div High Voltage Engn, Madras 600025, Tamil Nadu, India
关键词
Displacement; Finite element method; Short circuit forces; Transformer; Transient structural analysis; Sweep frequency response analysis;
D O I
10.5370/JEET.2015.10.3.983
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power transformer is one of the major and key apparatus in electric power system. Monitoring and diagnosis of transformer fault is necessary for improving the life period of transformer. The failures caused by short circuits are one of the causes of transformer outages. The short circuit currents induce excessive forces in the transformer windings which result in winding deformation affecting the mechanical and electrical characteristics of the winding. In the present work, a transformer producing only the radial flux under short circuit is considered. The corresponding axial displacement profile of the windings is computed using Finite Element Method based transient structural analysis and thus obtained displacements are, compared with the experimental result. The change in inter disc capacitance and mutual inductance of the deformed windings due to different short circuit currents are computed using Finite Element Method based field analyses and the corresponding Sweep Frequency Responses are computed using the modified electrical equivalent circuit. From the change in the first resonant frequency, the. winding movement can be quantified which will be useful for estimating the mechanical withstand capability of the winding for different short circuit currents in the design stage itself.
引用
收藏
页码:983 / 989
页数:7
相关论文
共 50 条
  • [31] Axial vibration equivalent one-degree analysis of power transformer winding under short-circuit
    Wang, Hongfang
    Wang, Naiqing
    Li, Tongsheng
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2000, 15 (05): : 39 - 41
  • [32] Sensitivity of Connection Schemes for Detection of Axial Displacement of Transformer Winding by Frequency Response Analysis
    Miyazaki, S.
    Tahir, M.
    Tenbohlen, S.
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [33] On Site Oil Test for a Transformer Using Sweep Frequency Response Analysis
    Simon, Al-Amin Ahmed
    Riad, Md. Mahbubul Huq
    Ahmed, Erfan
    Ahmed, S. Shahnawaz
    2014 INTERNATIONAL CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING (ICECE), 2014, : 85 - 87
  • [34] Modeling and Diagnostic Transformer Condition Using Sweep Frequency Response Analysis
    Purnomoadi, A. P.
    Fransisco, D.
    ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 1059 - +
  • [35] Review of Sweep Frequency Response Analysis -SFRA for assessment winding displacements and deformation in power transformers
    Secue Roncería, Janneth Rocío
    Mombello, E.
    Cardoso, C.V.
    IEEE Latin America Transactions, 2007, 5 (05) : 321 - 328
  • [36] Rotor Winding Diagnosis using Sweep Frequency Response Analysis and Comparison to RSO
    Froehlich, Pascal
    Oettl, Fabian
    2024 INTERNATIONAL CONFERENCE ON DIAGNOSTICS IN ELECTRICAL ENGINEERING, DIAGNOSTIKA 2024, 2024, : 18 - 23
  • [37] A novel methodology for high-frequency lumped equivalent circuit of an isolated transformer winding construction based on frequency response analysis signal morphology interpretation
    Amara, Abderrazak
    Gacemi, Abderrazak
    Houassine, Hamza
    Chaouche, Moustafa Sahnoune
    IET ELECTRIC POWER APPLICATIONS, 2021, 15 (02) : 171 - 185
  • [38] Detection of Winding Axial Displacement of a Real Transformer by Frequency Response Analysis without Fingerprint Data
    Miyazaki, Satoru
    ENERGIES, 2022, 15 (01)
  • [39] Application of Statistical Interpretation Technique for Frequency Response Analysis and Detection of Axial Displacement in Transformer Winding
    Sardar, Suman
    Kumar, Amrendra
    Chatterjee, Biswendu
    Dalai, Sovan
    2017 IEEE CALCUTTA CONFERENCE (CALCON), 2017, : 461 - 464
  • [40] Study on locating transformer internal faults using sweep frequency response analysis
    Khanali, Mahdi
    Hayati-Soloot, Amir
    Hoidalen, Hans Kristian
    Jayaram, Shesha
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 145 : 55 - 62