Virtual surface temperature sensor for multi-zone commercial buildings

被引:4
|
作者
Yu, Yuebin [1 ]
Woradechjumroen, Denchai [1 ]
Yu, Daihong [2 ]
机构
[1] Univ Nebraska, 1110 S67th ST,PKI104F, Omaha, NE 68182 USA
[2] Lawrence Technol Univ, Southfield, MI 48033 USA
关键词
System identification; Commercial Buildings; RTUs; Virtual sensor; Supervisory control;
D O I
10.1016/j.egypro.2014.11.896
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Multi-zone structure is commonly used in small commercial office buildings, retail stores and supermarket. While there is no adjacent wall between the zones, the impact of a neighbor zone on the current zone can be approximated and analyzed through the application of virtual walls. It is critical to accurately estimate the virtual wall surface temperature in order to evaluate the model uncertainty and apply improved supervisory control on multiple rooftop air-conditioning units (RTUs). We propose an innovative virtual surface temperature sensor based on system identification to solve this challenge. The validation of the virtual temperature model is processed by the three validation criteria: goodness of fit (G), mean squared error (MSE) and coefficient of determination (R-2) through off control conditions with data obtained from a building simulation platform. Further, the sensitivity analysis using the on-control three conditions (under-sizing, properly sizing and oversizing condition) is conducted for analyzing and evaluating the performance of this system-identification based virtual sensor. (C) 2014 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:21 / 24
页数:4
相关论文
共 50 条
  • [31] Estimation of pollutant sources in multi-zone buildings through different deconvolution algorithms
    Li, Mo
    Li, Fei
    Jing, Yuanqi
    Zhang, Kai
    Cai, Hao
    Chen, Lufang
    Zhang, Xian
    Feng, Lihang
    BUILDING SIMULATION, 2022, 15 (05) : 817 - 830
  • [32] Decentralized Control Design for User Comfort and Energy Saving in Multi-zone Buildings
    Dinh Hoa Nguyen
    Funabashi, Toshihisa
    5TH INTERNATIONAL CONFERENCE ON POWER AND ENERGY SYSTEMS ENGINEERING (CPESE 2018), 2019, 156 : 172 - 176
  • [33] Distributed Diagnosis of Sensor and Actuator Faults in Air Handling Units in Multi-Zone Buildings: A Model-Based Approach
    Papadopoulos, Panayiotis M.
    Lymperopoulos, Georgios
    Polycarpou, Marios M.
    Ioannou, Petros
    ENERGY AND BUILDINGS, 2022, 256
  • [34] Context-aware Model Predictive Control framework for multi-zone buildings
    Mtibaa, Fatma
    Kim-Khoa Nguyen
    Dermardiros, Vasken
    Cheriet, Mohamed
    JOURNAL OF BUILDING ENGINEERING, 2021, 42
  • [35] Study on the distributed model predictive control for multi-zone buildings in personalized heating
    Li, Zhiwei
    Zhang, Jili
    ENERGY AND BUILDINGS, 2021, 231
  • [36] Selective Distributed Model Predictive Control For Comfort Satisfaction in Multi-Zone Buildings
    Roshany-Yamchi, Samira
    Witheepanich, Kritchai
    Escano, Juan M.
    McGibney, Alan
    Rea, Susan
    2017 21ST INTERNATIONAL CONFERENCE ON SYSTEM THEORY, CONTROL AND COMPUTING (ICSTCC), 2017, : 648 - 653
  • [37] Estimation of pollutant sources in multi-zone buildings through different deconvolution algorithms
    Mo Li
    Fei Li
    Yuanqi Jing
    Kai Zhang
    Hao Cai
    Lufang Chen
    Xian Zhang
    Lihang Feng
    Building Simulation, 2022, 15 : 817 - 830
  • [38] Multi-Agent Control for Centralized Air Conditioning Systems Serving Multi-Zone Buildings
    Cai, Jie
    Kim, Donghun
    Putta, Vamsi K.
    Braun, James E.
    Hu, Jianghai
    2015 AMERICAN CONTROL CONFERENCE (ACC), 2015, : 986 - 993
  • [39] Air quality and comfort constrained energy efficient operation of multi-zone buildings
    Naqvi, S.
    Kar, K.
    Bhattacharya, S.
    Chandan, V.
    Mishra, S.
    Salsbury, T.
    BUILDING AND ENVIRONMENT, 2023, 244
  • [40] Detailed Thermodynamic Modeling of Multi-Zone Buildings with Resistive-Capacitive Method
    Belic, Filip
    Sliskovic, Drazen
    Hocenski, Zeljko
    ENERGIES, 2021, 14 (21)