VELOCITY BASED DEFROST AND FROST INHIBITION OF EVAPORATOR COILS OF HEAT PUMP

被引:0
|
作者
Muthusubramanian, Kamalakkannan [1 ]
Dessiatoun, Serguei V. [1 ]
Shooshtari, Amir H. [1 ]
Ohadi, Michael M. [1 ]
机构
[1] Univ Maryland, College Pk, MD 20742 USA
关键词
D O I
暂无
中图分类号
O414.1 [热力学];
学科分类号
摘要
Researchers in the past have reported various methods to either retard frost formation or minimize energy expenditure during defrosting, but the methods reported in this paper is novel. Use of air flow during heating and defrosting cycles has not been studied and reported so far. The effect of using air flow during heating and defrosting cycles of heat pump were investigated experimentally. In the heating cycle, it is found that at higher air flow velocities, it is possible to retard the rate at which frost grows on the evaporator coils of the heat pump. Changing the air velocity from 0.8 m/s to 2 m/s caused a significant reduction in the frost growth rate. The AT of the working fluid for the 2 m/s experiment stayed at least 0.5 similar to 1.0 degrees C more than the corresponding value of the 0.8 m/s experiment for the entire 90 minute duration of the heating cycle. In the defrost cycle, it is found that using air flow in the direction opposite to the normal air flow on the evaporator coil provides an energy saving opportunity by increasing the time interval between subsequent defrosting. It was seen that a reduction of 1 similar to 2 defrost cycle was possible in 1 hour of operation, depending on the level of frost formation.
引用
收藏
页数:7
相关论文
共 50 条
  • [31] Modeling of the heat transfer process in an air heat pump fanless evaporator
    Kopec, Piotr
    Niezgoda-Zelasko, Beata
    XI INTERNATIONAL CONFERENCE ON COMPUTATIONAL HEAT, MASS AND MOMENTUM TRANSFER (ICCHMT 2018), 2018, 240
  • [32] Performance analysis of vapor-injection heat pump based on PVT collector/evaporator
    Shou C.
    Yao J.
    Zheng S.
    Peng H.
    Zhao Y.
    Dai Y.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2022, 43 (06): : 138 - 144
  • [33] Research on gas-liquid interface parameters related to thermal performance of frost-free evaporator of air source heat pump
    Zhou, Dan
    Zhang, Yi
    Wu, Yuting
    Wang, Yunfei
    Zhang, Guanmin
    Renewable Energy, 2024, 237
  • [34] Experimental study on dynamic characteristics of an R290 heat pump during defrost
    Du, Yanjun
    Wu, Jianhua
    Wang, Che
    ENERGY AND BUILDINGS, 2020, 223 (223)
  • [35] Transient simulation of air-source heat pump during the reverse cycle defrost
    Liu, ZQ
    Tang, GF
    Zhao, FY
    CRYOGENICS AND REFRIGERATION - PROCEEDINGS OF ICCR'2003, 2003, : 695 - 698
  • [36] Experiments of a Heat Pump Water Heating System Using Stored Solar Energy to Defrost
    Liu, Tianji
    Li, Zhiyuan
    He, Guoqing
    8TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY (ICAE2016), 2017, 105 : 1130 - 1135
  • [37] FROST MEASUREMENT OF AIR SOURCE HEAT PUMP HEAT EXCHANGERS BASED ON IMAGE RECOGNITION PROCESSING TECHNOLOGY
    Chen, Liming
    Xie, Bin
    THERMAL SCIENCE, 2024, 28 (2B): : 1363 - 1370
  • [38] Structural optimization simulation of collector/evaporator for hybrid heat source heat pump
    Fang L.
    Li S.
    Xu C.
    Zhongnan Daxue Xuebao (Ziran Kexue Ban)/Journal of Central South University (Science and Technology), 2020, 51 (04): : 1125 - 1134
  • [39] Frosting in a heat pump evaporator part B: Numerical analysis
    Popovac, M.
    Emhofer, J.
    Reichl, Ch.
    APPLIED THERMAL ENGINEERING, 2021, 199
  • [40] FLOODED EVAPORATOR IN SMALL REFRIGERATION- AND HEAT PUMP SYSTEMS
    Ericsson, S.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 4104 - 4111