Above -roof air temperature effects on HVAC and cool roof performance: Experiments and development of a predictive model

被引:11
|
作者
Green, Alan [1 ]
Gomis, Laia Ledo [1 ]
Paolini, Riccardo [2 ]
Haddad, Shamila [2 ]
Kokogiannakis, Georgios [1 ]
Cooper, Paul [1 ]
Ma, Zhenjun [1 ]
Kosasih, Buyung [1 ]
Santamouris, Mattheos [2 ]
机构
[1] Univ Wollongong, Sustainable Bldg Res Ctr, Wollongong, NSW 2522, Australia
[2] Univ New South Wales, Fac Built Environm, Sydney, NSW 2052, Australia
关键词
CONVECTIVE HEAT-TRANSFER; RESIDENTIAL BUILDINGS; TRANSFER COEFFICIENTS; THERMAL PERFORMANCE; ENERGY; COATINGS; SIMULATION; REFLECTANCE; COMFORT;
D O I
10.1016/j.enbuild.2020.110071
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In building performance simulations it is typically assumed that outdoor HVAC equipment is exposed to air at the outdoor ‘ambient’ temperature, obtained from a weather file. However, in reality, significant spatial variations in the outdoor air temperature can exist close to buildings. This simplification may lead to significant errors, especially when comparing simulations of buildings with and without cool roofs, since the colder surface of the cool roof would reduce above-roof air temperatures, thereby influencing the energy consumption of rooftop HVAC equipment. Above-roof temperature variations were measured in detail at three shopping centre buildings, and the experimental data was used to develop a model that can estimate air temperatures above hot or cold roof surfaces. The model requires only four input variables, all of which are available in typical building simulation tools. Implementation of the model in a set of case-study simulations revealed that above-roof air temperatures can have a large effect on the predicted performance of cool roofs. In cases where cooling equipment and ventilation inlet ducts were both located on the roof, the electricity savings and gas ‘penalties’ attributable to cool roofs would have been underestimated by 44–85% (61% on average) if above-roof air temperature variations had not been modelled accurately. © 2020 Elsevier B.V.
引用
收藏
页数:13
相关论文
共 35 条
  • [21] Development of a simplified cool coating thermal model for predicting street canyon air temperature
    Donthu, E. V. S. Kiran Kumar
    Shashwat, S.
    Zingre, Kishor T.
    Wan, Man Pun
    BUILDING AND ENVIRONMENT, 2024, 251
  • [22] PREDICTIVE MODEL OF LAYING HEN PERFORMANCE TO AIR-TEMPERATURE AND EVAPORATIVE COOLING
    TIMMONS, MB
    GATES, RS
    TRANSACTIONS OF THE ASAE, 1988, 31 (05): : 1503 - 1509
  • [23] Development of a Data-Driven Predictive Model of Supply Air Temperature in an Air-Handling Unit for Conserving Energy
    Hong, Goopyo
    Kim, Byungseon Sean
    ENERGIES, 2018, 11 (02)
  • [24] Effects of pressure waves on the cooling-fan performance and indoor flow of air-conditioning units on the roof of a high-speed maglev train
    Guo, Haixia
    Zhang, Kunlun
    Xu, Gang
    Niu, Jiqiang
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2024, 145
  • [25] Effects of high air temperature on ripening in rice plants - Analysis of ripening performance in growth chamber experiments
    Morita, S
    JAPANESE JOURNAL OF CROP SCIENCE, 2000, 69 (03) : 391 - 399
  • [26] Development of a predictive model to describe the effects of temperature and water activity on the growth of spoilage pseudomonads
    Neumeyer, K
    Ross, T
    McMeekin, TA
    INTERNATIONAL JOURNAL OF FOOD MICROBIOLOGY, 1997, 38 (01) : 45 - 54
  • [27] Modeling the effects of water temperature on rice growth and yield under a cool climate: I. Model development
    Shimono, Hiroyuki
    Hasegawa, Toshihiro
    Iwama, Kazuto
    AGRONOMY JOURNAL, 2007, 99 (05) : 1327 - 1337
  • [28] Practical factors of envelope model setup and their effects on the performance of model predictive control for building heating, ventilating, and air conditioning systems
    Blum, D. H.
    Arendt, K.
    Rivalin, L.
    Piette, M. A.
    Wetter, M.
    Veje, C. T.
    APPLIED ENERGY, 2019, 236 : 410 - 425
  • [29] Model predictive control for the performance improvement of air source heat pump heating system via variable water temperature difference
    Wang, Wenyi
    Hu, Bin
    Wang, R. Z.
    Luo, Mingwen
    Zhang, Guangpeng
    Xiang, Bo
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 138 : 169 - 179
  • [30] Development, implementation and performance of a model predictive controller for packaged air conditioners in small and medium-sized commercial building applications
    Kim, Donghun
    Braun, James E.
    ENERGY AND BUILDINGS, 2018, 178 : 49 - 60