Numerical modelling and parametric study of an air-cooled desiccant coated cross-flow heat exchanger

被引:30
|
作者
Liu, Lin [1 ,2 ]
Zeng, Tao [1 ]
Huang, Hongyu [1 ]
Kubota, Mitsuhiro [3 ]
Kobayashi, Noriyuki [3 ]
He, Zhaohong [1 ]
Li, Jun [3 ]
Deng, Lisheng [1 ,4 ]
Li, Xing [1 ]
Feng, Yuheng [4 ,5 ]
Yan, Kai [5 ]
机构
[1] Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, Guangdong Prov Key Lab New & Renewable Energy Res, 2 Nengyuan Rd, Guangzhou 510640, Peoples R China
[2] Univ Chinese Acad Sci, Beijing 100049, Peoples R China
[3] Nagoya Univ, Chikusa Ku, Furo Cho, Nagoya, Aichi 4648603, Japan
[4] Tongji Univ, Thermal & Environm Engn Inst, 1239 Siping Rd, Shanghai 200092, Peoples R China
[5] Shanghai Boiler Works Co Ltd, Shanghai 200245, Peoples R China
关键词
Numerical modeling; Solid dehumidification; Cross-flow heat exchanger; Desiccant coated heat exchanger; Air conditioning; PERFORMANCE; DEHUMIDIFICATION; WHEEL; MASS;
D O I
10.1016/j.applthermaleng.2020.114901
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air-cooled desiccant coated cross-flow heat exchanger (DCCFHE) system provides a simple and effective approach to improve dehumidification performance by using cooling air to remove adsorption heat during adsorption process. In this study, a novel numerical model validated by experimental data was established to predict the performance of a conventional silica gel DCCFHE system. The fin efficiency, as a variable due to the release of adsorption heat, was taken into account in the model. Parametric study for various air velocity and structural parameters was conducted to reveal their effects on the dehumidification performance. Results show that the smaller process air velocity is conducive to improve dehumidification performance, but the performance increases with the increase in cooling air velocity. Compared to the operation case without cooling air, the moisture removal capacity and dehumidification coefficient of performance can obtain about 35% improvement at the cooling air velocity of 1 m/s. The results also indicate that thicker desiccant layer thickness and smaller fin pitch improve moisture removal capacity and dehumidification coefficient of performance but result in greater total pressure drop Delta P, while the performance is insensible to fin thickness and fin height. Besides, effect of heat transfer performance in dehumidification and cooling sides on dehumidification performance was also analyzed. It was found that the heat transfer performance in dehumidification side is the dominant factor affecting dehumidification performance.
引用
收藏
页数:16
相关论文
共 50 条
  • [21] Improve Air-Cooled Heat Exchanger Performance
    Boes, Steve
    CHEMICAL ENGINEERING PROGRESS, 2017, 113 (01) : 39 - 45
  • [22] Experimental Investigation of the Flow Maldistribution Inside an Air-Cooled Heat Exchanger
    Habib, M. A.
    Said, S. A.
    Khalifa, A.
    Nemitallah, M. A.
    Ayinde, T.
    ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2014, 39 (11) : 8187 - 8198
  • [23] Numerical study on thermal performance of an air-cooled heat exchanger: Effects of hybrid nanofluid, pipe arrangement and cross section
    Karimi, Ali
    Afrand, Masoud
    ENERGY CONVERSION AND MANAGEMENT, 2018, 164 : 615 - 628
  • [24] Experimental study on heat transfer and flow resistance performance of an air-cooled fluoride salt heat exchanger
    Li, Qi-Ming
    Tian, Jian
    Fu, Yao
    Zhou, Chong
    Zou, Yang
    Fu, Yuan
    Hou, Jie
    Yu, Xiao-Han
    APPLIED THERMAL ENGINEERING, 2025, 269
  • [25] Numerical investigation of the effect of inlet flow distortions on forced draught air-cooled heat exchanger performance
    Meyer, CJ
    APPLIED THERMAL ENGINEERING, 2005, 25 (11-12) : 1634 - 1649
  • [26] DEVELOPMENT OF CROSS FLOW AIR-COOLED PLATE HEAT EXCHANGERS
    Kim, Minsung
    Baik, Young-Jun
    Shin, Kwang-Ho
    Park, Sung-Ryung
    Ra, Ho-Sang
    Jeong, Jac-Hun
    Lim, Hyug
    ACRA 2009: PROCEEDINGS OF THE 4TH ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, 2009, : 334 - 339
  • [27] Performance of Air-Cooled Heat Exchanger with Laminar, Transitional, and Turbulent Tube Flow
    Taler, Dawid
    XI INTERNATIONAL CONFERENCE ON COMPUTATIONAL HEAT, MASS AND MOMENTUM TRANSFER (ICCHMT 2018), 2018, 240
  • [28] Lift and Drag Characteristics of an Air-Cooled Heat Exchanger Axial Flow Fan
    Louw, Francois G.
    von Backstroem, Theodore W.
    van der Spuy, Sybrand J.
    JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME, 2015, 137 (08):
  • [29] Dehumidification behavior of cross-flow heat exchanger type adsorber coated with aluminophosphate zeolite for desiccant humidity control system
    Kubota, Mitsuhiro
    Hanaoka, Noriko
    Matsuda, Hitoki
    Kodama, Akio
    APPLIED THERMAL ENGINEERING, 2017, 122 : 618 - 625
  • [30] Numerical Simulation and Field Synergy Analysis of IGBT Air-Cooled Heat Exchanger for EMUs
    Guan, Ying
    Li, Minghai
    Cui, Hongjiang
    INTERNATIONAL JOURNAL OF HEAT AND TECHNOLOGY, 2020, 38 (03) : 650 - 658