EXPERIMENTAL INVESTIGATION OF CONTROL STRATEGIES FOR OFF-DESIGN OPERATION OF A TRANSCRITICAL CO2 TWO-PHASE EJECTOR REFRIGERATION SYSTEM FOR THE COLD CHAIN

被引:0
|
作者
Lawrence, Neal [1 ]
Elbel, Stefan [1 ,2 ]
机构
[1] Univ Illinois, Dept Mech Sci & Engn, Air Conditioning & Refrigerat Ctr, 1206 West Green St, Urbana, IL 61801 USA
[2] Creat Thermal Solut Inc, 2209 North Willow Rd, Urbana, IL 61802 USA
关键词
Two-phase ejector; carbon dioxide; high-side pressure control; capacity modulation; WORK RECOVERY; PERFORMANCE;
D O I
10.18462/iir.iccc.2016.0034
中图分类号
O414.1 [热力学];
学科分类号
摘要
The use of two-phase ejectors to improve the performance of CO2 refrigeration systems has been investigated extensively in recent years. Studies have shown that ejectors offer significant opportunity for COP and capacity improvement at conditions favorable to the ejector; however, performance improvement is known to be less significant at ejector off-design conditions. In this paper, methods for controlling the high-side pressure of a transcritical CO2 ejector cycle are investigated. The use of a simple expansion valve in series or parallel with the ejector to actively control high-side pressure is investigated experimentally and compared to other studies using an adjustable ejector. Control of the evaporator flow rate for different conditions is also investigated. Tests are performed at multiple capacities and ambient temperatures in order to investigate the performance improvement offered by an ejector cycle compared to an expansion valve cycle at off-design conditions with and without active control strategies.
引用
收藏
页码:256 / 263
页数:8
相关论文
共 50 条
  • [21] Thermodynamic design and simulation of a CO2 based transcritical vapour compression refrigeration system with an ejector
    Ahammed, Md. Ezaz
    Bhattacharyya, Souvik
    Ramgopal, M.
    International Journal of Refrigeration, 2014, 45 : 177 - 188
  • [23] Thermodynamic design and simulation of a CO2 based transcritical vapour compression refrigeration system with an ejector
    Ahammed, Md. Ezaz
    Bhattacharyya, Souvik
    Ramgopal, M.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 45 : 177 - 188
  • [24] Critical comparison between single-phase ejector and two-phase ejector in simulated CO2 transcritical commercial cooling system
    Paez, Ana
    Haberschill, Philippe
    Revellin, Remi
    Michel, Benoit
    Tobaly, Pascal
    Ballot-Miguet, Benedicte
    15TH IIR-GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS, 2022, : 718 - 732
  • [25] Experimental investigation on the malfunction characteristics of the two-phase ejector in a typical enhanced refrigeration system
    Bai, Tao
    Lu, Yu
    Wan, Jiahao
    Yu, Jianlin
    APPLIED THERMAL ENGINEERING, 2025, 262
  • [26] Off-design performance analysis of a transcritical CO2 Rankine cycle with LNG as cold source
    Wang, Jianyong
    Wang, Jiangfeng
    Dai, Yiping
    Zhao, Pan
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2017, 14 (09) : 774 - 783
  • [27] Experimental investigation on the effect of mixing length on the performance of two-phase ejector for CO2 refrigeration cycle with and without heat exchanger
    Nakagawa, M.
    Marasigan, A. R.
    Matsukawa, T.
    Kurashina, A.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (07): : 1604 - 1613
  • [28] Experimental Study on Performance of Double-Throttling Device Transcritical CO2 Ejector Refrigeration System
    Huai, Yanshuang
    Guo, Xianmin
    Shi, Yaoguang
    8TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY (ICAE2016), 2017, 105 : 5106 - 5113
  • [29] Development and exergo-energetic analysis of an energy-efficient solar-assisted transcritical CO2 refrigeration system with two-phase ejector
    Boupda, Orelien T.
    Lontsi, Frederic
    Djiako, Thomas
    Ekani, Roger
    ENERGY CONVERSION AND MANAGEMENT-X, 2025, 25
  • [30] Thermodynamic approach for designing the two-phase motive nozzle of the ejector for transcritical CO2 heat pump system
    Al-Tameemi, Mohammed Ridha Jawad
    Yu, Zhibin
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 1206 - 1212