Performance characterization and optimization of counter-flow dew point indirect evaporative cooler through response surface methodology

被引:4
|
作者
Kousar, Rubeena [1 ]
Ali, Muzaffar [2 ]
Amja, Muhammad Kamal [3 ]
Sheikh, Nadeem Ahmed [4 ]
Ahmad, Waqas [2 ]
机构
[1] Univ Engn & Technol, Mech Engn Dept, Taxila, Pakistan
[2] Univ Engn & Technol, Energy Engn Dept, Taxila, Pakistan
[3] Natl Univ Sci & Technol, Sch Mech & Mfg Engn, Islamabad, Pakistan
[4] Int Islamic Univ, Fac Engn & Technol, Dept Mech Engn, Islamabad, Pakistan
关键词
Indirect evaporative cooler; dew point effectiveness; wet bulb effectiveness; cooling capacity; response surface method; desirability function; optimization; M-CYCLE; HEAT-EXCHANGERS; DESIGN; MODELS;
D O I
10.1177/09576509211007976
中图分类号
O414.1 [热力学];
学科分类号
摘要
The optimal performance of dew point indirect evaporative cooler with respect to the operational environment is a challenging task as the same is affected by many parameters. This paper reports the regression modeling and optimization of a counter flow indirect evaporative cooler using the response surface methodology. Experimentation is conducted using the central composite design and regression models are statistically evaluated for adequacy and found within 7% maximum error limit as compared with literature. Results show that supply temperature and cooling capacity increase with increasing inlet air velocity and inlet air temperature. Moreover, dew point and wet bulb effectiveness have a direct relationship with inlet air temperature and an inverse relationship with inlet air velocity. After validation, the regression models are subjected to single-objective and multi-objective optimization based upon the desirability function technique. The multi-objective formulation reveals that optimal performance of the system is achieved at 41.31 degrees C inlet air temperature, 3.61 m/sec inlet air velocity, 12 g/kg inlet air humidity, and 24.48 degrees C water temperature. Finally, an operational envelope is proposed to evolve a zone for the best-suited operation of such a device which ensures a reasonable cooling capacity within 1.5 - 2.5 kW while enabling thermal comfort for the conditioned space.
引用
收藏
页码:1789 / 1805
页数:17
相关论文
共 50 条
  • [21] Numerical study of a novel counter-flow heat and mass exchanger for dew point evaporative cooling
    Zhao, X.
    Li, J. M.
    Riffat, S. B.
    APPLIED THERMAL ENGINEERING, 2008, 28 (14-15) : 1942 - 1951
  • [22] Prediction and Analysis of Dew Point Indirect Evaporative Cooler Performance by Artificial Neural Network Method
    Sun, Tiezhu
    Huang, Xiaojun
    Liang, Caihang
    Liu, Riming
    Huang, Xiang
    ENERGIES, 2022, 15 (13)
  • [23] Performance Analysis of the Multi-Stage Dew-Point Indirect Evaporative Air Cooler
    Pacak, Anna
    Jurga, Anna
    Sierpowski, Korneliusz
    Panek, Magdalena
    Skolowska, Agata
    Pandelidis, Demis
    APPLIED SCIENCES-BASEL, 2022, 12 (13):
  • [24] Unsteady-state entropy generation analysis of the counter-flow dew-point evaporative coolers
    Yang, Cheng
    Chen, Haonan
    Miyazaki, Takahiko
    Kim, Young-Deuk
    Thu, Kyaw
    APPLIED THERMAL ENGINEERING, 2024, 257
  • [25] A new method for prediction and analysis of heat and mass transfer in the counter-flow dew point evaporative cooler under diverse climatic, operating and geometric conditions
    Wan, Yangda
    Lin, Jie
    Chua, Kian Jon
    Ren, Chengqin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 127 : 1147 - 1160
  • [26] Numerical study and performance correlation development on counter-flow indirect evaporative air coolers
    Wan, Yangda
    Ren, Chengqin
    Wang, Zhao
    Yang, Yang
    Yu, Lei
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 115 : 826 - 830
  • [27] Performance assessment of a high-efficiency indirect dew-point evaporative cooler through three-dimensional modeling
    Wang, B. C.
    Chen, Z.
    You, G. L.
    Ding, J. N.
    Cheng, G. G.
    Bui, T. D.
    ENERGY, 2024, 312
  • [28] Comparative study on performance of counter-flow dew-point indirect evaporative cooling systems via a more realistic and experimentally validated three-dimensional model
    Wan, Yangda
    Xue, Tinghui
    Huang, Zhifeng
    Soh, Alexandera
    Liu, Haibo
    Chua, Kian Jon
    JOURNAL OF BUILDING ENGINEERING, 2024, 82
  • [29] Regression models for performance prediction of counter flow dew point evaporative cooling systems
    Pakari, Ali
    Ghani, Saud
    ENERGY CONVERSION AND MANAGEMENT, 2019, 185 : 562 - 573
  • [30] Developing a performance correlation for counter-flow regenerative indirect evaporative heat exchangers with experimental validation
    Cui, X.
    Islam, M. R.
    Mohan, B.
    Chua, K. J.
    APPLIED THERMAL ENGINEERING, 2016, 108 : 774 - 784