Influence of Axial Magnetic Field on Cathode Plasma Jets in High-Current Vaccum Arc

被引:3
|
作者
Yang, Dingge [1 ,2 ]
Jia, Shenli [2 ]
Qi, Weidong [1 ]
Wu, Jingfeng [1 ]
Wang, Sen [1 ]
Han, Yanhua [1 ]
Ding, Bin [1 ]
Zhang, Heng [3 ]
Li, Wenhui [1 ]
机构
[1] State Grid Shaanxi Elect Power Res Inst, Xian 710054, Shaanxi, Peoples R China
[2] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Shaanxi, Peoples R China
[3] State Grid Xian Elect Power Supply Co, Xian 710082, Shaanxi, Peoples R China
关键词
Axial magnetic field (AMF); cathode plasma jets; vacuum arc plasma; CURRENT VACUUM ARCS; INCLINATION; EXPANSION;
D O I
10.1109/TPS.2017.2726347
中图分类号
O35 [流体力学]; O53 [等离子体物理学];
学科分类号
070204 ; 080103 ; 080704 ;
摘要
The cathode plasma jets in vacuum arc and the effect of magnetic field on them have been studied for several years and these studies are helpful to understand the arc characteristics and improve the controlling effect of magnetic field on arc plasma. In this paper, the experiments of the cup-shaped axial magnetic field (AMF) contacts were conducted in which a Helmholtz coil was introduced to generate different external imposed AMFs. It was found that the appearance of arc plasma was changed by variation of the external imposed AMF. If the composite AMF in arc column increased gradually, the obvious individual cathode plasma jets were detected, the arc constriction decreased, and the arc stability increased. Meanwhile, the inclination of cathode plasma jets was observed and the inclination direction was found to be consistent with the magnetic field vector direction which is closely related to the composite AMF. By variation of the external imposed AMF and its direction, the inclination direction of cathode plasma jets also changed. The criterion to detect obvious cathode jets in arc column is obtained that at the contact peripheral where R> 80.5% R-0 (R-0 is the contact radius), the AMF strength is no less than 4.5 mT/kA. It was also found that if the composite AMF in interelectrode gap points to different directions at a certain moment, it may lead to the transfer of arc column from the center to the edge of the interelectrode region and the arc instability until when the composite AMF in the interelectrode gap points to the same direction. It can be concluded that the appearance of individual cathode plasma jets can be manipulated by the variation of AMF, which is helpful to study the interaction between arc plasma and electrodes, especially the anode, and improve the interruption performance at higher current.
引用
收藏
页码:2596 / 2603
页数:8
相关论文
共 50 条
  • [11] Cathode Spots Dynamic in the Initial Expansion Stage of High-Current Triggered Vacuum Arc and the Influence of Axial Magnetic Field
    Shi, Zongqian
    Song, Xiaochuan
    Wang, Cong
    Jia, Shenli
    Wang, Lijun
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2014, 42 (08) : 2124 - 2130
  • [12] Influence of a Pulsed Axial Magnetic Field on a High-Current Arc of a Vacuum Circuit Breaker
    A. V. Schneider
    S. A. Popov
    E. L. Dubrovskaya
    Russian Physics Journal, 2021, 64 : 348 - 354
  • [13] Influence of a Pulsed Axial Magnetic Field on a High-Current Arc of a Vacuum Circuit Breaker
    Schneider, A., V
    Popov, S. A.
    Dubrovskaya, E. L.
    RUSSIAN PHYSICS JOURNAL, 2021, 64 (02) : 348 - 354
  • [14] Investigation on the influence of axial magnetic field on anode melting in high-current vacuum arc
    Yang, Dingge
    Jia, Shenli
    Wang, Lijun
    Shi, Zongqian
    PROCEEDINGS OF THE 27TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV), VOL 1, 2016, : 243 - 246
  • [15] The Combined Influence of Contact Gap and Axial Magnetic Field on the Expansion Speed of Cathode Spots in High-Current Triggered Vacuum Arc
    Shi, Zongqian
    Song, Xiaochuan
    Wang, Cong
    Jia, Shenli
    Liu, Chang
    Wang, Lijun
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2014, 42 (01) : 185 - 190
  • [16] High-current vacuum arc appearance in nonhomogeneous axial magnetic field
    Chaly, AM
    Logatchev, AA
    Zabello, KK
    Shkol'nik, SM
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2003, 31 (05) : 884 - 889
  • [17] Modeling of the effect of an axial magnetic field on the high-current vacuum arc
    Keidar, M
    Schulman, MB
    ISDEIV: XIXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS, 2000, 19 : 210 - 213
  • [18] The influence of axial magnetic filed distribution on high-current vacuum arc
    Shi, Zongqian
    Jia, Shenli
    Song, Xiaochuan
    Liu, Zhigang
    Dong, Hong
    Wang, Lijun
    ISDEIV 2008: PROCEEDINGS OF THE XXIIIRD INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, 2008, : 264 - 267
  • [19] ANODE SPOT IN A HIGH-CURRENT VACCUM ARC.
    NEMCHINSKII, V.A.
    1982, V 27 (N 1): : 20 - 25
  • [20] Emission spectra of high-current vacuum arc stabilized by axial magnetic field
    Bugaev, V. A.
    Dernovskij, V. L.
    Logatchev, A. A.
    Zabello, K. K.
    Shkol'nik, S. M.
    ISDEIV 2008: PROCEEDINGS OF THE XXIIIRD INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, 2008, : 284 - +