Synchronization and Reactive Current Support of PMSG-Based Wind Farm During Severe Grid Fault

被引:180
作者
Geng, Hua [1 ]
Liu, Lu [2 ]
Li, Ruiqi [1 ]
机构
[1] Tsinghua Univ, Dept Automat, Beijing 100084, Peoples R China
[2] Wuhan Univ Sci & Technol, Automat Sch, Wuhan 430070, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
Low voltage ride through (LVRT); permanent magnet synchronous generator (PMSG); wind farm; coordinated current control; VOLTAGE RIDE-THROUGH; COORDINATED CONTROL; FREQUENCY-RESPONSE; POWER CONVERTERS; STABILITY; WECS; GENERATORS; CAPABILITY; TURBINES; IMPACT;
D O I
10.1109/TSTE.2018.2799197
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Grid codes require wind farm to remain on-grid and inject specific reactive current when grid fault occurs. To satisfy the requirements, reactive power devices, such as the static synchronous compensator (STATCOM), are usually used in modern wind farms. In order to produce reactive currents, the wind energy generation system (WECS) and the STATCOM are normally controlled with the phase-locked loop (PLL) oriented vector control methods. Due to the active power imbalance between the generation and consumption, the wind farm has the risk of losing synchronization with the grid under severe fault conditions. This paper analyzes the dynamic synchronization mechanism and stability criteria of the wind farm and proposes a coordinated current control scheme for the WECS and the STATCOM during severe grid-fault period. The synchronization stability of both the WECS and the STATCOM is remained by the active power balancing control of the wind farm. The control objectives of the generator- and gridside converters for the WECS are swapped to avoid the interaction between the dc-link voltage control loop and the synchronization loop. The synchronized STATCOM produces additional reactive currents to help the wind farm meet the requirements of the grid code. Effectiveness of the theoretical analyses and the proposed control method is verified by simulations.
引用
收藏
页码:1596 / 1604
页数:9
相关论文
共 30 条
[1]  
[Anonymous], 2009, P IEEE POW EN SOC GE
[2]  
[Anonymous], BDEW TECHNICAL GUIDE
[3]   Control of permanent-magnet generators applied to variable-speed wind-energy systems connected to the grid [J].
Chinchilla, M ;
Arnaltes, S ;
Burgos, JC .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (01) :130-135
[4]   Low-voltage ride-through of a full converter wind turbine with permanent magnet generator [J].
Conroy, J. F. ;
Watson, R. .
IET RENEWABLE POWER GENERATION, 2007, 1 (03) :182-189
[5]   Frequency response capability of full converter wind turbine generators in comparison to conventional generation [J].
Conroy, James F. ;
Watson, Rick .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (02) :649-656
[6]   Analysis of Phase-Locked Loop Low-Frequency Stability in Three-Phase Grid-Connected Power Converters Considering Impedance Interactions [J].
Dong, Dong ;
Wen, Bo ;
Boroyevich, Dushan ;
Mattavelli, Paolo ;
Xue, Yaosuo .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) :310-321
[7]  
Dong D, 2012, APPL POWER ELECT CO, P1887, DOI 10.1109/APEC.2012.6166080
[8]   Advanced Vector Control for Voltage Source Converters Connected to Weak Grids [J].
Egea-Alvarez, Agust ;
Fekriasl, Sajjad ;
Hassan, Fainan ;
Gomis-Bellmunt, Oriol .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (06) :3072-3081
[9]   LVRT Capability of DFIG-Based WECS Under Asymmetrical Grid Fault Condition [J].
Geng, Hua ;
Liu, Cong ;
Yang, Geng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (06) :2495-2509
[10]   Unified Power Control for PMSG-Based WECS Operating Under Different Grid Conditions [J].
Geng, Hua ;
Yang, Geng ;
Xu, Dewei ;
Wu, Bin .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2011, 26 (03) :822-830