Modeling of asymmetrical operating states of AC electric arc furnace in the power system

被引:0
|
作者
Gala, Marek [1 ]
Sawicki, Antoni [1 ]
Jagiela, Kazimierz [2 ]
机构
[1] Czestochowa Tech Univ, Fac Elect Engn, SEP Assoc Polish Elect Engineers, Czestochowa, Poland
[2] Univ Bielsko Biala, Fac Mech Engn & Comp Sci, SEP Assoc Polish Elect Engineers, Czestochowa, Poland
关键词
arc furnaces; voltage and current asymmetry; arc model; power quality;
D O I
10.23919/ptze.2019.8781701
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The structural and operational factors influencing the asymmetrical work of steel arc furnaces in the power system are presented. In order to map the asymmetry of network load using a system of three electric arcs, the Pentegov mathematical model with different static-voltage characteristics was used. In addition, the asymmetry of the high-current path was taken into account by increasing the phase impedances under conditions of symmetrical arcing load. The simulation method examined the effect of load asymmetry on the values of asymmetry indicators, determined on the primary and secondary side of the furnace transformer.