Calculation of Interference Voltage on the Nearby Underground Metal Pipeline due to the Grounding Fault on Overhead Transmission Lines

被引:31
|
作者
Qi, Lei [1 ]
Yuan, Hui [1 ]
Li, Lin [1 ]
Cui, Xiang [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
关键词
Grounding fault; method of moment (MoM); overhead transmission line; transmission line model; underground metal pipeline; INDUCTIVE INTERFERENCE; PART I; EARTH; IMPEDANCES; RETURN; CABLES; ADMITTANCES; SOIL;
D O I
10.1109/TEMC.2013.2240391
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Electromagnetic interference on the underground metal pipelines in parallel with the faulted power transmission lines includes two parts: inductive and resistive coupling. Based on the multiconductor transmission line model consisting of overhead power lines and underground pipeline, the tower grounding resistance is, respectively, modeled by the lumped-parameter processing and distributed-parameter equivalent method. Then, the formulas of voltages and currents along the transmission lines are derived combined with the constraints of voltages and currents at the transmission line's ends and the location of grounding fault. Regarding the earth-fault currents along the towers as the excitations, the method of moment is used to investigate the resistive coupling voltage on the nearby underground metal pipeline. Compared with the results of commercial software CDEGS employing the electromagnetic field analysis, the proposed method is proved to be correct and effective. The simulations also show that the results by the lumped-parameter processing method are more accurate than those by the distributed-parameter equivalent method during the tower grounding resistance modeling. Finally, the proposed method is applied to investigate the influence of parallelism length, separation distance, soil resistivity, tower grounding resistance, insulation coating resistivity, grounding fault location, and fault currents from the substations on the pipeline's coating stress voltage.
引用
收藏
页码:965 / 974
页数:10
相关论文
共 45 条
  • [41] Calculation study regarding hot gases rising due to arcs and arc jets generated between arcing horns on 66 kV overhead transmission lines
    Iwata, Mikimasa
    Ohtaka, Toshiya
    Goda, Yutaka
    Tanezaki, Masatoshi
    Hamakawa, Tomohito
    Kamimura, Kentaro
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2019, 14 (11) : E14 - E20
  • [42] Calculation study regarding hot gases rising due to arcs and arc jets generated between arcing horns on 66 kV overhead transmission lines
    Central Research Institute of Electric Power Industry , 2-6-1 Nagasaka, Yokosuka
    Kanagawa
    240-0196, Japan
    不详
    Saga
    840-0804, Japan
    不详
    Osaka
    573-8521, Japan
    IEEJ Trans. Electr. Electron. Eng., 11 (e14-e20):
  • [43] A New Fault Location Algorithm of Line Voltage Cross-correction for Three-terminal Transmission Lines Based on Dynamic Calculation of Real-time Parameters
    Li Z.
    Zhang J.
    Chen Y.
    Weng H.
    Lü L.
    Dianwang Jishu/Power System Technology, 2020, 44 (02): : 761 - 768
  • [44] Investigations regarding a mechanism and a countermeasure against the phase-to-phase short-circuit fault due to arc jets spouting from the arcing horns for 66 kV overhead transmission lines
    Iwata, Mikimasa
    Ohtaka, Toshiya
    Goda, Yutaka
    Tanezaki, Masatoshi
    Hamakawa, Tomohito
    Kamimura, Kentaro
    IEEJ Transactions on Power and Energy, 2015, 135 (06) : 380 - 387