Severity diagnosis and assessment on defects in GIS based on partial discharge detection

被引:0
|
作者
Xie Yaoheng [1 ]
Zhou Weihua [1 ]
Ye Huisheng [1 ]
Liu Yun [1 ]
Tang Zhiguo [2 ]
Wang Caixiong [2 ]
机构
[1] State Grid Hunan Elect Power Co, Elect Power Res Inst, Changsha, Hunan, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing, Peoples R China
关键词
partial discharge; diagnose and assessment; severity levels; insulation condition; defects; PD; RECOGNITION;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In complex high voltage components local insulation defects can cause partial discharges (PD), especially in highly stressed gas insulated switchgear (GIS) these PD affected defects can lead to major blackouts. PD detection is recognized as one of the most effective and most important methods of insulation condition assessment in GIS. In this paper, we designed a scheme to diagnose and assess the severity levels of the PD provoked by defects in GIS. With the application of gradually increased voltage, long-term tests were conducted on a well-established 252kV GIS experiment platform to observe the entire evolution process of PD from its very initiation till the eventual flashover. Ream-time measurement was undertaken during the tests to capture the trend curve of as a result of test time, including the scatter plot, histogram, grey-scale map, etc. The results indicate that PD initiated by defects in GIS can be classified into three severity levels, namely, petty discharge, medium discharge, and threatening discharge. Moreover, on the basis of the features of phase distribution and the corresponding spectra, a procedure based on k-means cluster analysis are proposed to diagnosis and assess severity of PD automatically.
引用
收藏
页码:928 / 931
页数:4
相关论文
共 50 条
  • [41] Investigation of the Evaluation of the PD Severity and Verification of the Sensitivity of Partial-Discharge Detection Using the UHF Method in GIS
    Gao, Wensheng
    Ding, Dengwei
    Liu, Weidong
    Huang, Xinhong
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (01) : 38 - 47
  • [42] The Characteristics of Partial Discharge on Corona Defect in GIS based on Multi-Detection method
    Kou, Xiaokuo
    Li, Junhao
    Yang, Jinggang
    Li, Yanming
    PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (10A): : 176 - 179
  • [43] Experimental research of UHF method for the detection of partial discharge in GIS
    Shao, T.
    Zhou, W.J.
    Zhu, Y.F.
    Wu, S.H.
    Gaodianya Jishu/High Voltage Engineering, 2001, 27 (03):
  • [44] Development of portable GIS partial discharge source detection equipment
    Cui, JM
    Jai, HL
    Wang, RF
    ISTM/2005: 6th International Symposium on Test and Measurement, Vols 1-9, Conference Proceedings, 2005, : 292 - 295
  • [45] Design of Dipole Antenna Model for Partial Discharge Detection in GIS
    Khotimah, Khusnul
    Khayam, Umar
    Suwarno
    Tai, Yuki
    Kozako, Masahiro
    Hikita, Masayuki
    5TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING AND INFORMATICS 2015, 2015, : 186 - 191
  • [46] Study on external sensors for UHF partial discharge detection of GIS
    Li, Zhong
    Chen, Jiehua
    Hu, Dijun
    Feng, Yunping
    Gaodianya Jishu/High Voltage Engineering, 2003, 29 (06):
  • [47] Wavelet analysis used in UHF partial discharge detection in GIS
    Li, ZM
    Feng, YP
    Chen, JQ
    Zheng, XG
    POWERCON '98: 1998 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - PROCEEDINGS, VOLS 1 AND 2, 1998, : 163 - 166
  • [48] A Rectangular Planar Spiral Antenna for GIS Partial Discharge Detection
    Zhang, Xiaoxing
    Han, Yefei
    Li, Wei
    Duan, Xuetao
    INTERNATIONAL JOURNAL OF ANTENNAS AND PROPAGATION, 2014, 2014
  • [49] An Ultraviolet Spectroscopy Method for Rapid Partial Discharge Detection in GIS
    Dai Dang-dang
    Wang Xian-pei
    Hu Hong-hong
    Zhao Yu
    Long Jia-chuan
    Zhu Guo-wei
    Tian Meng
    Huang Yun-guang
    SPECTROSCOPY AND SPECTRAL ANALYSIS, 2014, 34 (12) : 3312 - 3316
  • [50] Analysis of UHF method used in partial discharge detection in GIS
    Tang, Ju
    Zhu, Wei
    Sun, Caixin
    Shi, Haijun
    Wei, Gang
    Gaodianya Jishu/High Voltage Engineering, 2003, 29 (12):