Analysis of the Influence of Installing Synchronous Condenser in HVDC Inverter Station to Receiving End Grid

被引:0
|
作者
Min, Fu [1 ]
Yin Zhaoyang [1 ]
Hai, Yan [1 ]
Cui Cancan [1 ]
机构
[1] Harbin Univ Sci & Technol, Sch Elect & Elect Engn, Harbin, Peoples R China
关键词
synchronous condenser; HVDC; weak receiving grid; operating characteristics; commutation failure;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As multi-infeed HVDC systems are fed into the AC grid, the problem of insufficient dynamic power reserve and insufficient voltage support of receiving-end grid is increasingly prominent. Short-circuit capacity and short-circuit ratio of the system, transient voltage level, and DC commutation failure probability before and after the installation of synchronous condenser are compared by simulation. The results prove the application effect of synchronous condenser in HVDC inverter station. Combined with the operating characteristics of synchronous condenser, the law of system voltage recovery time changing with transient time constant is revealed. The research provides a theoretical basis for dynamic reactive power compensation of synchronous condenser in HVDC inverter station.
引用
收藏
页码:4105 / 4109
页数:5
相关论文
共 50 条
  • [31] Grid Strengthening IBR: An Inverter-Based Resource Enhanced by a Co-Located Synchronous Condenser for High Overcurrent Capability
    Li, Haiguo
    Nie, Cheng
    Wang, Fred
    IEEE OPEN JOURNAL OF POWER ELECTRONICS, 2022, 3 : 535 - 548
  • [32] Multi-Mode Coordinated Control Strategy for DC Receiving Converter Station with Synchronous Condenser under Full Operating Conditions
    Li H.
    Wang Z.
    Zhou T.
    Mao W.
    Wang X.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2020, 35 (17): : 3678 - 3690
  • [33] Fault Analysis of Grid-connected Inverter Station at Fault Initial Stage
    Liu, Wei
    Tu, Qingrui
    2022 4TH INTERNATIONAL CONFERENCE ON SMART POWER & INTERNET ENERGY SYSTEMS, SPIES, 2022, : 1170 - 1174
  • [34] SYNCHRONOUS STABILITY ANALYSIS AND OPTIMIzATION STRATEGY OF LvRT FOR GRID-CONNECTED INvERTER
    Wang J.
    Zhang X.
    Han F.
    Fu X.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2024, 45 (02): : 309 - 317
  • [35] Sensitivity Analysis of the Cascaded Virtual Synchronous Generator based Grid Forming Inverter
    Liyanage, Chalitha
    Nutkani, Inam
    Meegahapola, Iasantha
    Jalili, Mandi
    2022 IEEE PES 14TH ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE, APPEEC, 2022,
  • [36] AC fault characteristics analysis and coordinated control strategy on the inverter side of a receiving-end hybrid multi-terminal HVDC system
    Deng N.
    Hao L.
    He J.
    Chen Z.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2023, 51 (10): : 54 - 64
  • [37] Analysis and improvement of the reactive power cascade control strategy for MMC-HVDC receiving-end converter connected to weak grid
    Xu, Junhua
    He, Guopeng
    Liu, Yong
    Tang, Songqin
    Xie, Daiyu
    Chen, Mingyuan
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2024, 18 (16) : 2677 - 2687
  • [38] Control strategy of suppressing wind turbine tripping based on coordination between synchronous condenser and SVC in sending-end network of HVDC
    Zhu L.
    Liu W.
    Shao C.
    Xu H.
    Niu S.
    Chen S.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (06): : 107 - 113
  • [39] Transient Voltage Control of Sending-End Wind Farm Using a Synchronous Condenser Under Commutation Failure of HVDC Transmission System
    Li, Wei
    Qian, Ziwei
    Wang, Qi
    Wang, Yu
    Liu, Fusuo
    Zhu, Ling
    Cheng, Shuo
    IEEE ACCESS, 2021, 9 : 54900 - 54911
  • [40] Mechanism Analysis of Receiving End Commutation Failure Caused by Sending End Oscillation in HVDC Transmission System
    Zheng L.
    Wu J.
    Xu Y.
    Sun Y.
    Liu C.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2024, 39 (09): : 2743 - 2754