Analysis on Thermal Environment of Office Room Equipped with Radiant Cooling Workstation

被引:0
|
作者
Song, Chunhui [1 ]
Li, Nianping [1 ]
He, Yingdong [1 ]
He, De [1 ]
He, Meiling [1 ]
Chen, Haowen [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Hunan, Peoples R China
基金
中国国家自然科学基金;
关键词
Radiant cooling workstation (RCW); Thermal environment; Computational fluid dynamics (CFD); SYSTEMS;
D O I
10.1016/j.proeng.2017.09.837
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper, an experiment was designed to compare the thermal environment between the fan coil unit system (Case 2) and the combination of radiant cooling workstation and fan coil unit system (Case 1). Through the numerical simulation software, namely Airpak, the indoor air temperature and velocity were compared in two cases. Compared to Case 2, there are 81.82% and 7.81% decrease in vertical and horizontal temperature difference, respectively. However, the vertical air temperature difference between head and feet is 0.97 degrees C, which is higher than Case 2. Also, the mean air velocity in Case 1 is lower than Case 2, and the air velocity in occupied zone of Case 1 ranges from 0.065 m/s to 0.12 m/s. (C) 2017 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:658 / 664
页数:7
相关论文
共 50 条
  • [21] Experimental Data and Simulations of Performance and Thermal Comfort in a Patient Room Equipped with Radiant Ceiling Panels
    Valdiserri, Paolo
    Cesari, Silvia
    Coccagna, Maddalena
    Romio, Pasquale
    Mazzacane, Sante
    BUILDINGS, 2020, 10 (12) : 1 - 18
  • [22] Thermal and flow analysis in a room with a radiant ceiling panel
    Alexander Nee
    Ali J. Chamkha
    Journal of Thermal Analysis and Calorimetry, 2022, 147 : 8367 - 8380
  • [23] Effect of thermal storage performance of concrete radiant cooling room on indoor temperature
    Xin Ya-juan
    Wang Zhi-qiang
    Tian Zhe
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2012, 19 (03): : 709 - 714
  • [24] Effect of thermal storage performance of concrete radiant cooling room on indoor temperature
    Ya-juan Xin
    Zhi-qiang Wang
    Zhe Tian
    Journal of Central South University, 2012, 19 : 709 - 714
  • [25] Effect of thermal storage performance of concrete radiant cooling room on indoor temperature
    辛亚娟
    王志强
    田喆
    JournalofCentralSouthUniversity, 2012, 19 (03) : 709 - 714
  • [26] Anticipating an efficient relative humidity in a room under direct solar radiation and equipped by radiant cooling panel system
    Najafi, N. Z.
    Haghighi, A. P.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 98 : 98 - 108
  • [27] Cooling Performance Analysis and Optimization of a Room with Radiant Panel using CFD
    Karimi, Abdullah
    Ghias, Reza
    2017 ASHRAE ANNUAL CONFERENCE PAPERS, 2017,
  • [28] Numerical prediction of thermal comfort and condensation risk in a ventilated office, equipped with a cooling ceiling
    Teodosiu, Catalin
    Ilie, Viorel
    Teodosiu, Raluca
    EENVIRO-YRC 2015 - BUCHAREST, 2016, 85 : 550 - 558
  • [29] Occupant's thermal comfort in a radiant ceiling cooling room with hot wall surface
    Wu, Xiaozhou
    Liu, Genglin
    Tian, Zhen
    Gao, Jie
    INDOOR AND BUILT ENVIRONMENT, 2023, 32 (04) : 699 - 718
  • [30] Analytical modeling of a radiant cooling system for thermal performance analysis
    Saha, Arup Chandra
    Verma, Vikas
    Tarodiya, Rahul
    Mahboob, M. R.
    Kumar, Rajesh
    MATERIALS TODAY-PROCEEDINGS, 2021, 47 : 2474 - 2480