Environmental Effects on the Performance of Electrical Grounding Systems

被引:0
|
作者
Lim, Siow Chun [1 ]
Choun, Lee Weng [1 ]
Gomes, Chandima [1 ]
Ab Kadir, Mohd Zainal Abidin [1 ]
机构
[1] Univ Putra Malaysia, Elect & Elect Engn Dept, Ctr Electromagnet & Lightning Protect Res CELP, Serdang 43400, Malaysia
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Effects of surrounding environment of grounding electrode locations on the performance of overall grounding system has been studied. Copper rods were buried at 25 different locations with various environmental settings and their respective variations in grounding resistance were monitored for up to 4 months. It was found that there is a clear dependence of grounding resistance on the condition of surrounding environment, in addition to the average soil resistivity. Installation of grounding electrodes near running waterways, huge trees as well as slopes should be avoided wherever possible as the ground resistance of electrodes in such environments may fluctuate significantly with time.
引用
收藏
页码:330 / 333
页数:4
相关论文