Experimental Investigating on On-line Monitoring Of Insulation System of Power Transformers

被引:0
|
作者
Shen, Ming [1 ]
Wu, Jiandong [1 ]
Yin, Yi [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Engn, Sch Elect & Elect Engn, Shanghai 200240, Peoples R China
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The insulation system of the transformer is a critical aspect of its health condition and the failure of the insulation system can make the transformers out of service. HV bushings and windings are the most important components of the transformer insulation system and failure statistics show that bushings and windings are the two of the major reasons for transformer failures, which motivates operators for continuous on-line monitoring of their insulation condition. Partial discharge (PD) measurements are also an important tool to assess the condition of the insulation system of the transformers, including the bushings and windings. The paper adopts a simple but effective method to not only monitor the bushings and the windings' health condition but detect the PD of the transformer. The 600 KHz similar to 1.2MHz sinusoidal signal based on direct digital synthesis (DDS), is applied on the bushings and the windings along with power frequency signal to assess the bushings and windings' health condition. Then the line-end and neutral-end high frequency currents are continuously measured by isolated precise current probes based on wide bandwidth Rogowski coils and related digital filtering methods. Meanwhile, the wide bandwidth Rogowski coils, which have double-channel outputs, can also detect the PD signals in the bushings and the windings. With the sinusoidal current data obtained from one channel of the probes, both the bushings' and the windings' insulation condition can be determined. And with the pulse current signal from PD obtained from the other channel of the probes, the PD of the bushings and the windings can be monitored all the time. Some simulations and experiments were made whose results showed that this detection method had high sensitivity and anti-interfere capability and it could wildly be used in insulation diagnose and partial discharge detection of power transformers.
引用
收藏
页码:327 / 330
页数:4
相关论文
共 50 条
  • [11] Data acquisition system for on-line temperature monitoring in power transformers
    Kunicki, Michal
    Borucki, Sebastian
    Zmarzly, Dariusz
    Frymus, Jerzy
    MEASUREMENT, 2020, 161
  • [12] Structure design of on-line monitoring system for power supply insulation
    Zhang Kai
    Hu Shunbin
    PROCEEDINGS OF THE 2007 INTERNATIONAL CONFERENCE ON AGRICULTURE ENGINEERING, 2007, : 340 - 344
  • [13] Application of PLC for on-line monitoring of power transformers
    Georges, B
    Aubin, J
    2001 IEEE POWER ENGINEERING SOCIETY WINTER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-3, 2001, : 483 - 486
  • [14] On-line and off-line monitoring-diagnosis system(MDS) for power transformers
    Nedelcut, Dorel
    Sacerdotianu, Dumitru
    Tanasescu, Gabriel
    Nicolae, Serban
    Voinescu, Lucian
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 949 - +
  • [15] On-line insulation diagnostics for current transformers
    Evert, R
    Hoch, D
    CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 512 - 517
  • [16] On-line Condition Monitoring of Power Transformers A Case History
    de Pablo, Alfonso
    Ferguson, Walter
    Mudryk, Anatoliy
    Golovan, Dmytro
    2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 285 - 288
  • [17] Research on on-line PD monitoring for large power transformers
    Ma, Weiping
    Dong, Xuzhu
    Wang, Zhongdong
    Zhu, Deheng
    Zheng, Lianghua
    Wang, Shuo
    Zhongguo Dianli/Electric Power, 2000, 33 (04): : 35 - 37
  • [18] Interference rejection for on-line PD monitoring of power transformers
    Wang, CC
    Jin, XH
    Jing, WH
    Cheng, TC
    Zhang, SB
    Dong, XZ
    Wang, ZD
    Lin, D
    Zhu, DH
    CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1998, : 24 - 27
  • [19] On-line partial discharge calibration and monitoring for power transformers
    Farag, AS
    Shewhdi, MH
    Jin, X
    Wang, C
    Cheng, TC
    Dong, X
    Gao, S
    Jing, W
    Wang, Z
    ELECTRIC POWER SYSTEMS RESEARCH, 1999, 50 (01) : 47 - 54
  • [20] Field experience with multigas on-line monitoring of power transformers
    Sparling, B
    Aubin, J
    Glodjo, A
    1999 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE, VOLS 1 & 2, 1999, : 895 - 900