Fire hazard due to electrical installations in modern multi-storey timber buildings

被引:3
|
作者
Engel, Thomas [1 ]
Moosmueller, Katharina [2 ]
Werther, Norman [1 ]
机构
[1] Tech Univ Munich, Ingn Fak Bau Geo Umwelt, Lehrstuhl Holzbau & Baukonstrukt, Arcisstr 21, D-80333 Munich, Germany
[2] Hans Segl Str 25, D-94486 Osterhofen, Germany
关键词
fire protection; timber construction; electrical installation; electrical fire; installation cable;
D O I
10.1002/bate.202000076
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Currently one third of all fires are due to electrical fires. An relevant question that has been raised, at the latest since the introduction of DIN VDE 0100-420 in 2016 and the general demand for arc fault detection devices (AFDDs) in timber buildings, is whether the combustible construction represents an increased fire hazard in the case of electrical fires and whether timber buildings therefore require more special protection. Within the scope of the study presented in this article that question was investigated for modern multi-storey timber buildings. Combustible insulation materials were not part of the scope of the investigation. In the course of the investigation it could be proven that the risk of an occurrence of electrical fires within the construction is low and that the existing protective devices of a building installation already cover a part of possible defects. An electric arc was determined as the decisive impact scenario. In all tests carried out, self-extinguishing occurred. After evaluation of the tests, it was not possible to identify a need for AFDDs in standard buildings.
引用
收藏
页码:353 / 364
页数:12
相关论文
共 50 条
  • [41] From Trees to Skyscrapers: Holistic Review of the Advances and Limitations of Multi-Storey Timber Buildings
    Gonzalez-Retamal, Marcelo
    Forcael, Eric
    Saelzer-Fuica, Gerardo
    Vargas-Mosqueda, Mauricio
    BUILDINGS, 2022, 12 (08)
  • [42] Performance-based and damage assessment of SFRP retrofitted multi-storey timber buildings
    Vahedian, Abbas
    Mahini, Seyed Saeed
    Glencross-Grant, Rex
    STRUCTURAL MONITORING AND MAINTENANCE, 2015, 2 (03): : 269 - 282
  • [43] Multi-storey timber construction: Approved for fire protection – Gaps in know-how
    Mehrgeschossiger Holzbau: brandschutztechnisch zugelassen – Knowhow-Lücken
    1600, John Wiley and Sons Inc (01): : 5 - 6
  • [44] FIRE RESISTANCE OF TIMBER ELEMENTS AND STRUCTURES IN MULTI-STOREY BUILDING DETERMINED BY EUROCODE 5
    Lesko, Robert
    Lopusniak, Martin
    ACTA FACULTATIS XYLOLOGIAE ZVOLEN, 2015, 57 (02): : 135 - 144
  • [45] Application of Iterative Fire Severity Analysis to Fire Safety Design of Multi-storey Mass Timber Structures
    Pau, Dennis
    Buchanan, Andrew
    Douglas, Cameron
    WOOD & FIRE SAFETY 2024, WFS 2024, 2024, : 265 - 274
  • [46] ADAS dampers for the hazard protection of multi-storey buildings with glazing envelopes: a feasibility study
    Bedon, C.
    Amadio, C.
    BOLLETTINO DI GEOFISICA TEORICA ED APPLICATA, 2019, 60 (02) : 197 - 220
  • [47] Modelling evacuation in multi-storey buildings with Simulex
    Thompson, Peter
    Wu, Jianhua
    Marchant, Eric
    Fire Engineers Journal, 1996, 56 (185):
  • [48] Unitised timber envelopes. A novel approach to the design of prefabricated mass timber envelopes for multi-storey buildings
    Gasparri, Eugenia
    Aitchison, Mathew
    JOURNAL OF BUILDING ENGINEERING, 2019, 26
  • [49] SPECIALISED MULTI-STOREY INDUSTRIAL BUILDINGS.
    Anon
    Hong Kong engineer, 1987, 15 (04): : 23 - 26
  • [50] Mitigation of Progressive Collapse in Multi-Storey Buildings
    Izzuddin, B. A.
    ADVANCES IN STRUCTURAL ENGINEERING, 2012, 15 (09) : 1505 - 1520