On-site measurement of winter indoor environment and air infiltration in an airport terminal

被引:17
|
作者
Liu, Xiaochen [1 ]
Liu, Xiaohua [1 ]
Zhang, Tao [1 ]
Guan, Bowen [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Airport terminal; Indoor environment; Large space; Air infiltration; Heat loss; BUILDINGS;
D O I
10.1177/1420326X18788601
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Currently, many airports in China are being built or retrofitted. Reducing energy consumption in airport terminals is of the utmost urgency. This paper describes on-site measurements of indoor thermal environment and air infiltration of a hub airport in winter in southwest China. Air velocity measurements with air volume balance check and thermal balance check were applied to assess air infiltration rates in terminal buildings. In unsecured halls, air infiltration rates were 0.61 air change per hour (ACH) (6.6 m(3)/(h m(2))) and 0.28 ACH (3.0 m(3)/(h m(2))) when space heating was on and off, respectively; while in secured piers, those two air infiltration rates were 0.42 ACH (2.6 m(3)/(h m(2))) and 0.24 ACH (1.5 m(3)/(h m(2))). Air infiltration consumed 66-92% of heat supplied by space heating systems, showing that winter air infiltration significantly affects indoor thermal environment and energy consumption in terminal buildings where air flows out through the doors of service walkways and open skylights on the roof. Furthermore, influences of building characteristics, space heating systems and outdoor temperatures on winter air infiltration in large space buildings were analysed. This research helps to clarify the key issues influencing indoor thermal environment and proposes solutions for energy saving in terminal buildings.
引用
收藏
页码:564 / 578
页数:15
相关论文
共 50 条
  • [32] Vertical temperature distribution in large space buildings in the heating season: On-site measurement and Block-Gebhart model prediction considering air infiltration
    Wang, Xin
    Zhou, Yujing
    Shi, Chenlu
    Xu, Yukun
    Huang, Chen
    Wang, Fei
    BUILDING AND ENVIRONMENT, 2021, 191
  • [33] Ventilation and Indoor Thermal Environment in Air-Conditioned Rooms with Open Windows in Winter
    Okamura, Akira
    Lee, Sihwan
    INDOOR ENVIRONMENTAL QUALITY PERFORMANCE APPROACHES (IAQ 2020), PT 1, 2021,
  • [34] NUMERICAL SIMULATION ON AIR DISTRIBUTION OF A TENNIS HALL IN WINTER AND EVALUATION ON INDOOR THERMAL ENVIRONMENT
    Sui, X.
    Han, G.
    Chen, F.
    ENGINEERING REVIEW, 2014, 34 (02) : 109 - 118
  • [35] Numerical evaluation on indoor environment quality during high numbers of occupied passengers in the departure hall of an airport terminal
    Zhao, Yu
    Feng, Yao
    Ma, Liangdong
    JOURNAL OF BUILDING ENGINEERING, 2022, 51
  • [36] A PORTABLE SYSTEM FOR ON-SITE MEASUREMENT OF INDOOR LUMINOUS PROPERTIES FOR HIGH-FIDELITY LIGHTING SIMULATION
    Chiou, Yun-Shang
    Thanh Quyet Mai
    BUILDING SIMULATION 2013: 13TH INTERNATIONAL CONFERENCE OF THE INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION, 2013, : 3376 - 3383
  • [37] On-site measurement and simulation of indoor particulate matter distributed in a single room with stratified flow field
    Lin, Ho-Hsiang
    Yuan, Chung-Shin
    Chen, Wang-Kun
    Chang, Chang-Tang
    Chen, Pei-Shih
    INDOOR AND BUILT ENVIRONMENT, 2021, 30 (07) : 886 - 905
  • [38] Formaldehyde emission behavior of building materials: On-site measurements and modeling approach to predict indoor air pollution
    Bourdin, Delphine
    Mocho, Pierre
    Desauziers, Valerie
    Plaisance, Herve
    JOURNAL OF HAZARDOUS MATERIALS, 2014, 280 : 164 - 173
  • [39] In situ, on-site and laboratory measurements of soil air permeability:: Boundary conditions and measurement scale
    Iversen, BV
    Schjonning, P
    Poulsen, TG
    Moldrup, P
    SOIL SCIENCE, 2001, 166 (02) : 97 - 106
  • [40] Integrating the living wall with the split air conditioner towards indoor heating environment improvement in winter
    Ding, Nan
    Liu, Fudan
    Pang, Feng
    Su, Jingyu
    Yan, Lianyu
    Meng, Xi
    CASE STUDIES IN THERMAL ENGINEERING, 2023, 47