The Development of Condition Based Maintenance for 33kV Oil- Filled Cable

被引:0
|
作者
Abu Zarim, Zairul Aida [1 ]
Anthony, Tashia Marie [1 ]
机构
[1] TNB Res Sdn Bhd, HV Cable Diagnost, Kajang, Malaysia
来源
PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012) | 2012年
关键词
component; oil-filled cable; condition based maintenance; dissolve gas analysis; moisture test;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The aim of the project is to identify suitable diagnostic test for Oil-Filled cable and subsequently to develop Condition Based Maintenance (CBM) guideline. From the literature review, Dissolve Gas Analysis (DGA) of the oil inside the cable is the most suitable screening test for Oil-Filled cable. Besides DGA test, another type of testing for the oil recommended is laboratory moisture test using the Karl Fischer method. From the DGA and laboratory moisture test results, the requirement of onsite tests is determined. The onsite tests namely Partial Discharge (PD) measurement and moisture evaluation using Frequency Dielectric Spectroscopy (FDS). Through this exercise a correlation between laboratory test results and requirement of the onsite test were developed. This correlation was then used to develop Condition Health Indexes calculation which is a part of CBM guideline. In the CBM guideline, besides Condition Health Indexes calculation, description of the identified test, step-by-step procedure to perform the identified test and interpretation of the test results are also available. As a conclusion, this project has successfully identified the suitable diagnostic test for Oil-Filled cable and the developed CBM guideline for Oil-Filled cable shall be incorporated into the existing Condition Based Maintenance (CBM) system for medium voltage underground cables.
引用
收藏
页码:225 / 228
页数:4
相关论文
共 50 条
  • [21] DEVELOPMENT OF +/-400 KV-+/-600-KV HIGH AND MEDIUM-PRESSURE OIL-FILLED PAPER INSULATED DC POWER CABLE SYSTEM
    BAHDER, G
    EAGER, GS
    SEMAN, GW
    FISCHER, FE
    CHU, H
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (06): : 2045 - 2056
  • [22] DEVELOPMENT OF 500-KV OIL-FILLED CABLES AND ACCESSORIES
    WATANABE, T
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1973, EI-8 (03): : 112 - 113
  • [23] DEVELOPMENT OF INTERNALLY OIL-COOLED OIL-FILLED CABLE (SEPARATED-TYPE)
    KOBAYASHI, T
    MORI, S
    OGINO, M
    KOSHISHI, M
    IWATA, Z
    ICHIYANAGI, N
    SHINDO, S
    INOUE, T
    IWANA, M
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (06): : 1234 - 1242
  • [24] DEVELOPMENT OF NEW 500KV LAMINATED PAPER INSULATED SELF-CONTAINED OIL-FILLED CABLE AND ITS ACCESSORIES
    WATANABE, Y
    FUKAGAWA, H
    IWATA, Z
    HATA, R
    YOSHIDA, S
    SAITOH, H
    FUJIWARA, Y
    IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (01) : 47 - 61
  • [25] 138KV PREFAB CAPACITIVE-GRADED JOINT FOR OIL-FILLED CABLE SYSTEMS
    ALLAM, EM
    MCKEAN, AL
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (01): : 20 - 26
  • [26] Electric Field and Thermal Analysis of 132 kV Ceramic Oil-Filled Cable Sealing Ends
    Zachariades, Christos
    Peesapati, Vidyadhar
    Gardner, Richard
    Cwikowski, Oliver
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (01) : 311 - 319
  • [27] INSTALLATION OF 115 KV OIL-FILLED SUBMARINE CABLE BETWEEN MARGARITA ISLAND AND MAINLAND VENEZUELA
    LEDEZMA, O
    MARQUEZ, R
    GOMEZ, JL
    TSUMOTO, M
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (04): : 1139 - 1139
  • [28] The Degradation Analysis of PVC Insulation Tape in 220kV Oil-filled Cable Terminal
    Yu, Shihu
    Yu, Xin
    Zhao, Yaohong
    Wang, Qing
    Yang, Xian
    Wang, Shihang
    2020 8TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD 2020), 2020, : 408 - 411
  • [29] DIRECT BURIED INSTALLATION OF 115 KV SELF-CONTAINED MEDIUM PRESSURE OIL FILLED CABLE
    WHITTEN, GW
    WATKINS, RHW
    SUBACH, A
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (03): : 1036 - &
  • [30] 525-KV SELF-CONTAINED OIL-FILLED CABLE SYSTEMS FOR GRAND-COULEE THIRD POWERPLANT DESIGN AND DEVELOPMENT
    RAY, JJ
    ARKELL, CA
    FLACK, HW
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1974, PA93 (02): : 630 - 639