Off-line Partial Discharge Measurement and Localization for a 33/6.9 kV In-Service Transformer

被引:0
|
作者
Selva, A. M. [1 ]
Azis, N. [2 ]
Yousof, M. F. M. [3 ]
Sallehuddin, N. [4 ]
Tadam, A. B. [4 ]
Saliang, A. D. [4 ]
机构
[1] Xair Energy Sdn Bhd, Sarawak, Malaysia
[2] Univ Putra Malaysia, Adv Lightning Power & Energy Res Ctr ALPER, Serdang, Malaysia
[3] Univ Tun Hussein Onn Malaysia, Fak Kejuruteraan Elekt & Elekt, Parit Raja, Malaysia
[4] Malaysia LNG Sdn Bhd, Sarawak, Malaysia
关键词
partial discharge; phase-resolved partial discharge; PD localization;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents an investigation on the off-line Partial Discharge (PD) and localization for 1 unit of in-service 5 MVA 33/6.9 kV oil immersed transformer. First, Dissolved Gas Analysis (DGA) was performed to confirm the existence of PD activities. Next, offline PD measurements were carried out on both LV and HV windings. Once the transformer has been energized, PD localization was performed at different sections of the transformer tank. It is found that HV windings are having possible multiples PD activities based on offline Phase-Resolved Partial Discharge (PRPD) pattern and PD localization.
引用
收藏
页码:505 / 508
页数:4
相关论文
共 26 条
  • [11] Medium voltage cable defects revealed by off-line partial discharge testing at power frequency
    Mashikian, M. S.
    Szatkowski, A.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2006, 22 (04) : 24 - 32
  • [12] On-line three-phase differential partial discharge localization in transformer bushings
    Meyer, Hans Kristian Hygen
    Eberg, Espen
    Lundgaard, Lars
    2021 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2021, : 80 - 83
  • [13] A Correction-Iteration Method for Partial Discharge Localization in Transformer Based on Acoustic Measurement
    Zhou, Lijun
    Cai, Junyi
    Hu, Junjie
    Lang, Guangya
    Guo, Lei
    Wei, Liao
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) : 1571 - 1581
  • [14] On-Line Partial Discharge Localization of 10-kV Covered Conductor Lines
    Yan, Yuan
    Zhao, Yinsong
    He, Weisheng
    Stievano, Igor S.
    Li, Hongjie
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (03) : 1688 - 1698
  • [15] Characteristics of on-line and off-line partial discharge on hydrogenerator stator windings using acoustic emission detection techniques
    Kaneko, T
    Ueda, T
    Takenouchi, O
    Otsubo, M
    Honda, C
    Tsuruta, Y
    Fukura, A
    Tanaka, K
    Proceedings of the 2005 International Symposium on Electrical Insulating Materials, Vols, 1-3, 2005, : 837 - 840
  • [16] Power transformer asset management on-line partial discharge measurement - A new approach
    Kuppuswamy, R
    Coquelin, P
    2005 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2005, : 445 - 448
  • [17] Off-line partial discharge measurements as a new data source about the technical condition of MV cables
    Noske, S.
    Rakowska, A.
    2014 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2014,
  • [18] Partial discharge localization in transformer windings using multi-conductor transmission line model
    Jafari, Ali Mazhab
    Akbari, Asghar
    ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (06) : 1028 - 1037
  • [19] RECENT DEVELOPMENTS IN IEEE AND IEC STANDARDS FOR OFF-LINE AND ON-LINE PARTIAL DISCHARGE TESTING OF MOTOR AND GENERATOR STATOR WINDINGS
    Stone, G. C.
    Stranges, Meredith K. W.
    Dunn, Donald G.
    2014 IEEE PETROLEUM AND CHEMICAL INDUSTRY TECHNICAL CONFERENCE (PCIC), 2014,
  • [20] Off-line diagnostics of insulation condition in 6kV motor windings using acoustic imaging of partial discharges
    Gulczynski, Marcin
    Adamowicz, Marek
    Olesz, Marek
    PRZEGLAD ELEKTROTECHNICZNY, 2024, 100 (03): : 60 - 67