Flashover Voltage of Outdoor Insulators in the Presence of Multiple Drybands

被引:0
|
作者
Ramesh, M. [1 ]
Gorur, R. S. [1 ]
机构
[1] Univ Alabama, Dept Elect & Comp Engn, Huntsville, AL 35816 USA
关键词
D O I
10.1109/ceidp47102.2019.9009761
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper a model to calculate the flashover voltage of polluted outdoor insulator in the presence of multiple dryband discharges is presented. Based on the power criterion for flashover, a generalized equation is proposed that can calculated the flashover voltage for serially burning multiple discharges on the surface of the polluted insulator. The model is further used to calculate the flashover voltage of standard insulator of rating 115kV. It was found that the presence of multiple smaller dryband discharges at every shed reduced the flashover voltage of 115kV insulator with a single predominant discharge by 15%.
引用
收藏
页码:401 / 404
页数:4
相关论文
共 50 条
  • [41] The estimation of the critical flashover voltage of insulators using the computational intelligence
    Dehyadegari L.
    Khajehasani S.
    Recent Advances in Computer Science and Communications, 2020, 13 (04) : 550 - 556
  • [42] Using corrected criteria to model flashover voltage of polluted insulators
    Ziari, Iman
    Gholami, Ahmad
    Jalilian, Alireza
    First International Power & Energy Conference (PECon 2006), Proceedings, 2006, : 602 - 606
  • [43] Flashover dynamic model of polluted insulators under ac voltage
    Dhahbi-Megriche, N
    Beroual, A
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2000, 7 (02) : 283 - 289
  • [44] Fixed least squares support vector machines for flashover modelling of outdoor insulators
    Mandjoubi, Abdelhalim
    Zegnini, Boubakeur
    Belkheiri, Mohammed
    Seghier, Tahar
    ELECTRIC POWER SYSTEMS RESEARCH, 2019, 173 : 29 - 37
  • [45] Simulation of Surface Charge Effect on Impulse Flashover Characteristics of Outdoor Polymeric Insulators
    Kumara, Sarath
    Serdyuk, Yuriy V.
    Gubanski, Stanislaw M.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (06) : 1754 - 1763
  • [46] Use of surface resistance for assessing vulnerability of HV outdoor insulators to contamination flashover
    Gorur, RS
    Subramanian, K
    2003 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2003, : 406 - 409
  • [47] An empirical expression for the determination of the effects of rain on the AC flashover voltage of high voltage insulators
    Lpizra, MA
    Egbert, RI
    ELECTRIC POWER SYSTEMS RESEARCH, 1997, 43 (01) : 29 - 36
  • [48] Prediction of Critical Flashover Voltage of High Voltage Insulators Leveraging Bootstrap Neural Network
    Niazi, M. Tahir Khan
    Arshad
    Ahmad, Jawad
    Alqahtani, Fehaid
    Baotham, Fatmah A. B.
    Abu-Amara, Fadi
    ELECTRONICS, 2020, 9 (10) : 1 - 21
  • [49] FLASHOVER VOLTAGE OF HIGH-VOLTAGE INSULATORS WITH UNIFORM SURFACE-POLLUTION FILMS
    WILKINS, R
    PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1969, 116 (03): : 457 - &
  • [50] Flashover forecasting on high-voltage insulators with a backpropagation neural net
    MejiaLavalle, M
    RodriguezOrtiz, G
    CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 1996, 21 (01): : 29 - 32