Load characteristics and operation strategies of building integrated with multi-story double skin facade

被引:46
|
作者
Joe, Jaewan [1 ]
Choi, Wonjun [1 ]
Kwon, Hansol [1 ]
Huh, Jung-Ho [1 ]
机构
[1] Univ Seoul, Dept Architectural Engn, Seoul 130743, South Korea
关键词
Multi-story double skin facades; Airflow network; Measurement and verification; EnergyPlus; BEMS; Operation strategies; NATURAL VENTILATION;
D O I
10.1016/j.enbuild.2013.01.015
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study measured an actual behavior of a multi-story double skin facade (DSF) in South Korea. The verification of simulation model was made against measured data, and a case study was conducted based on the verified model. Seasonal load characteristics of the DSF building were examined in comparison with the single skin facade (SSF) building, and seasonal operation strategies of the DSF were proposed. The DSF building resulted in 15.8% and 7.2% reductions in heating and cooling energy consumption respectively, compared to the SSF building. In the proposed model of heating seasons, heated air in the cavity was introduced to an outdoor air (OA) mixing box of a HVAC system. In the proposed model of cooling seasons, air in the cavity was flowed into an indoor space through inner layer openings for natural ventilation, and outdoor air supply in a AHU was controlled based on the amount of the natural ventilation. These seasonal proposed models resulted in 28.2% and 2.3% reductions in heating and cooling energy consumption respectively, compared to the DSF model to which operation strategies were not applied. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:185 / 198
页数:14
相关论文
共 50 条
  • [1] Optimal design of a multi-story double skin facade
    Joe, Jaewan
    Choi, Wonjun
    Kwak, Younghoon
    Huh, Jung-Ho
    ENERGY AND BUILDINGS, 2014, 76 : 143 - 150
  • [2] Investigation of convective heat transfer at the facade with balconies for a multi-story building
    Tao, Shiwen
    Yu, Nanyang
    Ai, ZhengTao
    Zhao, Kaiming
    Jiang, Fujian
    JOURNAL OF BUILDING ENGINEERING, 2023, 63
  • [3] Test of wind load characteristics of cylindrical building with double-skin facade
    Lou, Wenjuan
    Zhang, Min
    Huazhong Keji Daxue Xuebao (Ziran Kexue Ban)/Journal of Huazhong University of Science and Technology (Natural Science Edition), 2009, 37 (05): : 90 - 93
  • [4] Settlement Response of a Multi-Story Building
    Bhutto, Amjad Hussain
    Bhurgri, Ghulam Shabir
    Zardari, Shahnawaz
    Zardari, Muhammad Auchar
    Memon, Bashir Ahmed
    Babar, Muhammad Munir
    ENGINEERING TECHNOLOGY & APPLIED SCIENCE RESEARCH, 2020, 10 (05) : 6220 - 6223
  • [5] RSSI Evaluation for Multi-story Building
    Dama, Y. A. S.
    Masri, Ahmed
    Ghannam, Hidaya
    Shuaieb, W.
    Alhassan, H.
    Obeidat, H. A.
    Abd-Alhameed, R. A.
    2015 INTERNET TECHNOLOGIES AND APPLICATIONS (ITA) PROCEEDINGS OF THE SIXTH INTERNATIONAL CONFERENCE (ITA 15), 2015, : 414 - 416
  • [6] Is the Load Transfer Mechanism of Each Story in a Multi-Story Building the Same Subjected to Progressive Collapse?
    Yu, Jun
    Tian, Ji-wei
    STRUCTURES CONGRESS 2017: BLAST, IMPACT LOADING, AND RESPONSE OF STRUCTURES, 2017, : 165 - 179
  • [7] Floor Determination for Positioning in Multi-story Building
    Abd Rahman, Mohd Amiruddin
    Dashti, Marzieh
    Zhang, Jie
    2014 IEEE WIRELESS COMMUNICATIONS AND NETWORKING CONFERENCE (WCNC), 2014, : 2540 - 2545
  • [8] Natural cooling strategies efficiency in an office building with a double-skin facade
    Gratia, E
    De Herde, A
    ENERGY AND BUILDINGS, 2004, 36 (11) : 1139 - 1152
  • [9] A Study on the Improvement of Double-Skin Facade Operation for Reducing Heating Load in Winter
    Sung, Uk-Joo
    Kim, Seok-Hyun
    SUSTAINABILITY, 2019, 11 (22)
  • [10] Live load arrangements for multi-story frame analysis
    Ersoy, Ugur
    Teknik Dergi/Technical Journal of Turkish Chamber of Civil Engineers, 1992, 3 (01): : 163 - 170