Neutral Grounding via Low Resistance Step Voltage Calculation and Simulation

被引:0
|
作者
Ci, Yanan [1 ]
Niu, Shengsuo [1 ]
Liang, Zhirui [1 ]
机构
[1] North China Elect Power Univ, Baoding, Peoples R China
关键词
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this paper, the neutral point grounding via low resistance short circuit fault current single-phase ground short circuit fault were calculated and analyzed. The ground current will cause large step voltage, thus threatening the safety of pedestrians. In this paper, this step voltage uneven soil model of theoretical calculations and the use of finite element software to simulate the step voltage. Studying area neutral resistance grounding influence into the soil depth, soil resistivity, capacitance and other factors on the step voltage, step voltage underground cables for single- phase ground fault simulation. And it puts forward the measure of reducing step voltage, the step voltage to minimize the harm of human body.
引用
收藏
页码:65 / 69
页数:5
相关论文
共 50 条
  • [31] AN EXPRESSION FOR THE CALCULATION OF GROUNDING RESISTANCE IN UNIFORM SOIL
    CHEN, CX
    KASTEN, DG
    ELECTRIC POWER SYSTEMS RESEARCH, 1985, 9 (02) : 193 - 200
  • [32] Calculation of ground resistance and step voltage for buried ground rod with insulation lead
    Chen, Li-Hsiung
    Chen, Jiann-Fuh
    Liang, Tsorng-Juu
    Wang, Wen-I
    ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (06) : 995 - 1007
  • [33] The Effect of Mesh Size, Number of Rod, & Length of Rod Towards Touch Voltage, Step Voltage, and Ground Resistance In Grounding System
    Kasim, Ishak
    Abduh, Syamsir
    Fitryah, Nur
    2017 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND POWER SYSTEMS (ICHVEPS), 2017, : 356 - 361
  • [34] Neutral to Earth Voltage (NTEV) on the Commercial Building with Considering the Low and High Frequencies Mode of the Grounding System
    Yusoh, Mohd Abdul Talib Mat
    Abidin, Ahmad Farid
    Yasin, Zuhaila Mat
    Mat, Usamah
    TENCON 2017 - 2017 IEEE REGION 10 CONFERENCE, 2017, : 739 - 744
  • [35] Research on neutral grounding mode and technology of leakage protection in mine low-voltage electric network
    Chen, Kui
    Sun, Chang-Qing
    Tang, Yi
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (22): : 237 - 241
  • [36] Ensuring Electrical Safety in 20 kV Electrical Networks with Low-Resistance Neutral Grounding
    Mayorov A.V.
    Lvov M.Y.
    Chelaznov A.A.
    Nikitina S.D.
    Power Technology and Engineering, 2022, 56 (4) : 581 - 586
  • [37] Ensuring Electrical Safety in 20 kV Electrical Networks with Low-Resistance Neutral Grounding
    Mayorov, A.V.
    Lvov, M. Yu.
    Chelaznov, A.A.
    Nikitina, S.D.
    Power Technology and Engineering, 2022, 56 (04) : 581 - 586
  • [38] Nonlinear Modeling and Analytical Analysis of Arc High Resistance Grounding Fault in Distribution Network With Neutral Grounding via Arc Suppression Coil
    Wang B.
    Cui X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (11): : 3864 - 3872
  • [39] Development of the algorithm and software "MVES-TV 2012" for calculation of touch voltage in MV networks with low resistance neutral earthing
    Priedite-Razgale, Ilze
    Rozenkrons, Janis
    PROCEEDINGS OF THE 13TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2012, VOLS 1 AND 2, 2012, : 211 - 215
  • [40] Simulation of Impact of Vertical Grounding Electrode on Impulse Grounding Resistance of Substation Grounding Network
    Zhou, Lijun
    He, Jian
    Xu, Han
    Wang, Pengcheng
    Chen, Ying
    Chen, Sixiang
    2017 2ND IEEE INTERNATIONAL CONFERENCE ON INTEGRATED CIRCUITS AND MICROSYSTEMS (ICICM), 2017, : 18 - 22