Clustering and motif identification for occupancy-centric control of an air handling unit

被引:31
|
作者
Hobson, Brodie W. [1 ]
Gunay, H. Burak [1 ]
Ashouri, Araz [1 ,2 ]
Newsham, Guy R. [2 ]
机构
[1] Carleton Univ, Dept Civil & Environm Engn, 1125 Colonel Dr,Room 3432,CJ Mackenzie Bldg, Ottawa, ON K1S 5B6, Canada
[2] Natl Res Council Canada, Construct Res Ctr, 1200 Montreal Rd, Ottawa, ON K1K 2E1, Canada
关键词
Occupancy forecasting; Occupancy-centric controls; Clustering; Motif identification; Adaptive ventilation; DISTRICT-HEATING NETWORKS; ENERGY-CONSUMPTION; BUILDING ENERGY; HVAC CONTROL; PERFORMANCE ASSESSMENT; RESIDENTIAL BUILDINGS; DEMAND; COMFORT; SENSOR; PREDICTION;
D O I
10.1016/j.enbuild.2020.110179
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Commercial and institutional buildings often operate at a fraction of their full occupancy, yet ventilation is frequently provided assuming maximum occupancy during working hours. Forecasting building occupancy can improve the operation of system level equipment by reducing chronic overventilation. However, developing actionable occupancy forecasting techniques for controls applications is subject to technological, security, and financial barriers. This paper proposes an occupancy forecasting technique that can be implemented in a controller given these constraints. Seven months of Wi-Fi, plug-in equipment and lighting electricity data were collected from an academic office building. Using Wi-Fi data, the building's mean occupancy was demonstrated to be less than 25% of the 1000-person maximum. Representative daily occupancy profiles were produced by different clustering techniques. A classification tree was developed to determine motif occupancy profiles for day-ahead forecasting. Corresponding electrical profiles were taken to see if they followed the same trend as the occupancy profiles; 84.5% of days shared the same trends. The electrical data were fed through the classification tree, with a successful occupancy classification rate of 70.4% and error of 47 +/- 69 persons at 95% confidence. A controls implementation for adaptive outdoor air damper actuation based on this technique is proposed for future work. Crown Copyright (c) 2020 Published by Elsevier B.V. All rights reserved.
引用
收藏
页数:11
相关论文
共 45 条
  • [21] Robust Sliding Mode Control of Air Handling Unit for Energy Efficiency Enhancement
    Shah, Awais
    Huang, Deqing
    Chen, Yixing
    Kang, Xin
    Qin, Na
    ENERGIES, 2017, 10 (11):
  • [22] Model predictive control of supply air temperature and outside air intake rate of a VAV air-handling unit
    Yuan, Shui
    Perez, Ronald A.
    ASHRAE Transactions 2006, Vol 112, Pt 1, 2006, 112 : 145 - 161
  • [23] Experimental Study on the Control of the Positions of the Cycle Isotherms of the Heat Pump in the Air Handling Unit
    Frik, Anton
    Bielskus, Juozas
    Dzikevics, Mikelis
    ENVIRONMENTAL AND CLIMATE TECHNOLOGIES, 2023, 27 (01) : 889 - 899
  • [24] Practical receding-horizon optimization control of the air handling unit in HVAC systems
    Xu, M
    Li, SY
    Cai, WJ
    INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2005, 44 (08) : 2848 - 2855
  • [25] Fault detection in an air-handling unit using residual and recursive parameter identification methods
    Lee, WY
    Park, C
    Kelly, GE
    ASHRAE TRANSACTIONS 1996, VOL 102, PT 1, 1996, 102 : 528 - 539
  • [26] Coordinated control for Air Handling Unit and Variable Air Volume boxes in multi-zone HVAC system
    Ma, Shunjian
    Zou, Yuanyuan
    Li, Shaoyuan
    JOURNAL OF PROCESS CONTROL, 2021, 107 : 17 - 26
  • [27] Proposal for a new, hybrid control strategy of a solar desiccant evaporative cooling air handling unit
    Vitte, Thibaut
    Brau, Jean
    Chatagnon, Nadege
    Woloszyn, Monika
    ENERGY AND BUILDINGS, 2008, 40 (05) : 896 - 905
  • [28] Comparison of Behaviour and Energy Performance of Desiccant Air Handling Unit under Various Control Method
    Ukai, Makiko
    Okumiya, Masaya
    4TH ASIA CONFERENCE OF INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION, 2019, 238
  • [29] Energy-efficient control of an air handling unit for a single-zone VAV system
    Goyal, Siddharth
    Barooah, Prahir
    2013 IEEE 52ND ANNUAL CONFERENCE ON DECISION AND CONTROL (CDC), 2013, : 4895 - 4900
  • [30] Nonlinear Optimal Control of Air Handling Unit via State Dependent Riccati Equation Approach
    Liavoli, Fariba Bouzari
    Fakharian, Ahmad