Research on Application of Adjustable Reactor Technology in UHVDC Converter Transformer Partial Discharge Test

被引:0
|
作者
Wei Chao [1 ]
Yu Miao [1 ]
Lu Yuncai [1 ]
Wu Peng [1 ]
Tao Fengbo [1 ]
机构
[1] Jiangsu Elect Power Co Res Inst, Nanjing 211103, Jiangsu, Peoples R China
来源
2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON) | 2014年
关键词
Converter transformer; partial discharge test; adjustable reactor;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
As the most severe assessment method in transformer field handover tests, partial discharge test can effectively detect insulation faults inside transformer. In this article, the adjustable reactor has been firstly proposed and used in the partial discharge field handover test of the converter transformers in Jinping-Sunan 800kV DC Transmission Project. The capacitive reactive power of the converter transformer under test has been analyzed and inductive compensation has been calculated. The reluctance of adjustable reactor can be adjusted smoothly, therefore the inductive compensation can be changed continuously in real time and under-compensation or over-compensation problems of fixed reactor can be avoided. The test method has been validated in field handover test in Jin-su UHVDC project and the filed partial discharge test has been completed successfully.
引用
收藏
页数:5
相关论文
共 50 条
  • [21] Research on recognition of partial discharge and safe operation for large transformer
    Li, X
    Zhang, C
    Zhang, CL
    Yang, YM
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL V, PTS A AND B, 2005, 5 : 1985 - 1990
  • [22] Transformer Partial Discharge Detection Using Electical-Ultrasonic Technology
    Jiang, Wei
    Liu, Fan
    Wang, Zhiyuan
    Zhang, Xinghai
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [23] Transformer partial discharge location technology based on gradient oil temperature
    Yu, Ruidong
    Zhang, Zhousheng
    FRONTIERS IN ENERGY RESEARCH, 2024, 12
  • [24] Application research on UHVDC technology in asia-europe power transmission planning
    Zhang, Yantao
    Zhang, Zhiqiang
    Zhang, Yuhong
    Liang, Caihao
    Li, Yalou
    Yao, Liangzhong
    Dianwang Jishu/Power System Technology, 2015, 39 (08): : 2069 - 2075
  • [25] Partial Discharge Localization in a Power Transformer: Methods, Trends, and Future Research
    Mondal, Mithun
    Kumbhar, G. B.
    IETE TECHNICAL REVIEW, 2017, 34 (05) : 504 - 513
  • [26] Application of improved genetic algorithm in ultrasonic location of transformer partial discharge
    Youchan Zhu
    Li Zhou
    Haisheng Xu
    Neural Computing and Applications, 2020, 32 : 1755 - 1764
  • [27] Application of improved genetic algorithm in ultrasonic location of transformer partial discharge
    Zhu, Youchan
    Zhou, Li
    Xu, Haisheng
    NEURAL COMPUTING & APPLICATIONS, 2020, 32 (06): : 1755 - 1764
  • [28] The Application of Microfiber Coupler Sensor for Partial Discharge Detection in Transformer Oil
    Liu, Yiying
    Zhou, Yang
    Yu, Penghao
    Wang, Chengcheng
    Wang, Xuhong
    Wang, Pengzhao
    2020 8TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD 2020), 2020, : 226 - 229
  • [29] Research and Application Prospects of Subsea Transformer Technology in China
    Guo, Jiangyan
    Lei, Yang
    Guo, Hong
    Hong, Yi
    Qiu, Yinfeng
    Ship Building of China, 2019, 60 : 298 - 303
  • [30] Review on Partial Discharge and Charge Distribution Characteristics of Oil-paper Insulation in Converter Transformer
    Li Q.
    Wang L.
    Wang P.
    Li S.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (08): : 2815 - 2829