An experimental study on self-extinction of tunnel fire under natural ventilation condition

被引:30
|
作者
Wang, Kai-Hong [1 ]
Chen, Jun-Min [1 ]
Wang, Zhong-Kuan [1 ]
Gao, Dong-Li [1 ]
Wang, Guo-Yuan [1 ]
Lin, Peng [1 ]
机构
[1] Southwest Jiaotong Univ, Dept Fire Safety Engn, Chengdu, Sichuan, Peoples R China
基金
中国国家自然科学基金;
关键词
Methanol fire; Propane fire; Tunnel; Fire self-extinction; Limiting oxygen concentration; Vitiated air; CEILING-JET; TEMPERATURE DISTRIBUTION; HORIZONTAL TUNNEL; COMBUSTION; FLAME;
D O I
10.1016/j.tust.2018.11.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Fire tests with both methanol and propane fires ranging from 5.6 to 16.8 kW were conducted in two 1:20 reduced-scale tunnels with identical cross-section size of 0.45 m wide x 0.23 m high but different lengths, i.e., 20.8 m and 10 m long respectively. Natural smoke control was adopted for both tunnels. Fires were located at the center of the tunnels. Temperatures and gas concentrations (i.e., O-2, CO and CO2) were measured in the experiments. The experimental results showed that both methanol fires and propane fires self-extinguished in the 20.8 m-long tunnel within around 600 s, except the 5.6 kW methanol fire. The larger the heat release rates were, the quicker the self-extinction of fires were. The oxygen concentrations in the 20.8 m-long tunnel declined monotonously until they approached around 12% except for the 5.6 kW methanol fire, which kept well above the limiting oxygen concentration. For fires close to the self-extinction, the flames lifted from the burner surface and fluctuated strongly. Self-extinction was not observed with both methanol fires and propane fires of the same heat release rates in the 10 m-long tunnel. The oxygen concentrations in the 10 m-long tunnel decreased temporarily to 17% and rose up to around 20%. In the long tunnel with large fire sizes, the smoke layer descended to ground level at a certain distance away from the fire as the temperature of smoke layer dropped to ambient temperature. The descended smoke layer stopped the supply of fresh air reaching the fire seat. The backflow of air toward the fire was highly vitiated due to the mixing of combustion products with fresh air. The fires self-extinguished when the concentration of oxygen close to fire seat approached the limit of flammability. The self-extinguishment of fires in tunnel provides us new insight on the strategy of firefighting in tunnel fires.
引用
收藏
页码:177 / 188
页数:12
相关论文
共 50 条
  • [11] On the self-extinction time of pool fire in closed compartments
    Zhang, Jiaqing
    Lu, Shouxiang
    Li, Changhai
    Yuan, Man
    Yuen, Richard
    9TH ASIA-OCEANIA SYMPOSIUM ON FIRE SCIENCE AND TECHNOLOGY, 2013, 62 : 266 - 274
  • [12] A study on the temperature profile of bifurcation tunnel fire under natural ventilation
    Zhao, Jianlong
    Li, Yanfeng
    Li, Junmei
    Li, Jiaxin
    PLOS ONE, 2022, 17 (01):
  • [13] Self-extinction characteristics of fire extinguishing induced by nitrogen injection rescue in an enclosed urban utility tunnel
    Cai, Guobin
    Zheng, Xuezhao
    Gao, Wenjing
    Guo, Jun
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 59
  • [14] Experimental Study on Influence of Natural Ventilation on Near Wall Fire in Cable Tunnel
    Bai, Zhenpeng
    Yu, Yueyang
    Lv, Kefeng
    Qin, Hengjie
    Yao, Haowei
    Yang, Cunxiang
    ENGINEERING LETTERS, 2023, 31 (02)
  • [15] Experimental study on fire characteristics in cable compartment of utility tunnel with natural ventilation
    Bai, Z. P.
    Yao, H. W.
    Zhang, H. H.
    PLOS ONE, 2022, 17 (04):
  • [16] RUNAWAY EVOLUTION TO SELF-EXTINCTION UNDER ASYMMETRICAL COMPETITION
    MATSUDA, H
    ABRAMS, PA
    EVOLUTION, 1994, 48 (06) : 1764 - 1772
  • [17] An experimental study on critical velocity in sloping tunnel with longitudinal ventilation under fire
    Yi, Liang
    Xu, Qiqi
    Xu, Zhisheng
    Wu, Dexing
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2014, 43 : 198 - 203
  • [18] Experimental study on combustion characteristics of engineered bamboo considering smoldering and self-extinction
    Huang, Yujie
    Xu, Ming
    Zhang, Yudong
    Cui, Zhaoyan
    INDUSTRIAL CROPS AND PRODUCTS, 2024, 222
  • [19] Full-scale experimental study on fire under natural ventilation in the T-shaped and curved tunnel groups
    Cheng, Huihang
    Liu, Chang
    Chen, Junfeng
    Wu, Le
    Zhao, Yuting
    Zhong, Maohua
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2022, 123
  • [20] Experimental and numerical study on fire-induced smoke temperature in connected area of metro tunnel under natural ventilation
    Liu, Chang
    Zhong, Maohua
    Tian, Xiangliang
    Zhang, Peihong
    Xiao, Yan
    Mei, Qi
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2019, 138 : 84 - 97