Indoor environmental quality of green office buildings in China: Large-scale and long-term measurement

被引:48
|
作者
Geng, Yang [1 ,2 ,3 ]
Lin, Borong [1 ,2 ,3 ]
Yu, Juan [1 ,2 ,3 ]
Zhou, Hao [1 ,2 ,3 ]
Ji, Wenjie [1 ,2 ,3 ]
Chen, Hongzhong [1 ,2 ,3 ]
Zhang, Zhongchen [1 ,2 ,3 ]
Zhu, Yingxin [1 ,2 ,3 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
[2] Tsinghua Univ, Minist Educ, Key Lab Eco Planning & Green Bldg, Beijing, Peoples R China
[3] Tsinghua Univ, Beijing Key Lab Indoor Air Qual Evaluat & Control, Beijing, Peoples R China
基金
中国国家自然科学基金; 美国国家科学基金会;
关键词
Indoor environmental quality (IEQ); Green office building; Long-term measurement; Thermal comfort; Air quality; POSTOCCUPANCY EVALUATION; HEATING-SYSTEMS; THERMAL COMFORT; IEQ; SATISFACTION; HEALTH; PERCEPTION; SYMPTOMS; ENVELOPE; IMPACTS;
D O I
10.1016/j.buildenv.2019.01.014
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study aims to explore the actual indoor environmental quality (IEQ) in Chinese green office buildings, based on the large-scale and long-term measurement data. A total of 41 green office buildings throughout Cold zone, Hot-Summer-Cold-Winter (HSCW) zone and Hot-Summer-Warm-Winter (HSWW) zone were measured with 198 integrated environmental sensors from June, 2017 to August, 2018. The key findings of this study can be summarized as follows: 1) Indoor thermal comfort did not show a significant difference between climate zones in summer, while thermal environment of Cold zone was much warmer and drier than the counterpart of HSCW and HSWW zone in winter. The overall indoor thermal environment met the standard, although several thermal problems were found; 2) Indoor CO2 concentration was relatively high in summer or winter and low in transition seasons. The median values of indoor CO2 concentration were far below the threshold of 1000 ppm; 3) Indoor PM2.5 concentration was generally lower in HSWW zone and higher in winter. The median values of indoor PM2.5 concentration generally conformed to the standard guideline; 4) The median values of illuminance ranged from 340 lux to 522 lux and all of them reached the lower limit of 300 lux for common offices. The above results were compared with other findings from previous literature and several differences were illustrated. In addition, the correlations between indoor and outdoor environment were found. Other possible factors influencing IEQ were discussed qualitatively.
引用
收藏
页码:266 / 280
页数:15
相关论文
共 50 条
  • [31] Learning and Long-Term Retention of Large-Scale Artificial Languages
    Frank, Michael C.
    Tenenbaum, Joshua B.
    Gibson, Edward
    PLOS ONE, 2013, 8 (01):
  • [32] Scalable Long-Term Safety Certificate for Large-Scale Systems
    Hoshino, Kenta
    Wang, Zhuoyuan
    Nakahira, Yorie
    IEEE CONTROL SYSTEMS LETTERS, 2023, 7 : 1285 - 1290
  • [33] Indoor environment quality and work performance in "green" office buildings in the Middle East
    Elnaklah, Rana
    Fosas, Daniel
    Natarajan, Sukumar
    BUILDING SIMULATION, 2020, 13 (05) : 1043 - 1062
  • [34] Indoor environment quality and work performance in green office buildings in the Middle East
    Elnaklah, Rana
    Fosas, Daniel
    Natarajan, Sukumar
    Building Simulation, 2020, 13 (05): : 1043 - 1062
  • [35] Indoor environment quality and work performance in “green” office buildings in the Middle East
    Rana Elnaklah
    Daniel Fosas
    Sukumar Natarajan
    Building Simulation, 2020, 13 : 1043 - 1062
  • [36] Cost-optimal and indoor environmental quality assessment for residential buildings towards EU long-term climate targets
    Tanasa, C.
    Dan, D.
    Becchio, C.
    Corgnati, S. P.
    Stoian, V.
    ENERGY FOR SUSTAINABLE DEVELOPMENT, 2020, 59 : 49 - 61
  • [37] Indoor environmental quality and learning outcomes: protocol on large-scale sensor deployment in schools
    Temprano, Juan Palacios
    Eichholtz, Piet
    Willeboordse, Maartje
    Kok, Nils
    BMJ OPEN, 2020, 10 (03):
  • [38] Characterizing indoor environmental quality in Portuguese office buildings for designing an intervention program
    Felgueiras, Fatima
    Mourao, Zenaida
    Moreira, Andre
    Gabriel, Marta Fonseca
    BUILDING AND ENVIRONMENT, 2024, 254
  • [39] Unravelling the relationship between energy and indoor environmental quality in Australian office buildings
    Roumi, Soheil
    Stewart, Rodney A.
    Zhang, Fan
    Santamouris, Mattheos
    SOLAR ENERGY, 2021, 227 : 190 - 202
  • [40] Analysis of indoor environmental quality in some domiciles and office buildings in Guangzhou City
    Hu, DQ
    Zhu, DM
    Li, YW
    Zhang, SC
    BUILT ENVIRONMENT AND PUBLIC HEALTH, PROCEEDINGS, 2004, : 133 - 138