Investigation on Smoke Flow in Stairwells induced by an Adjacent Compartment Fire in High Rise Buildings

被引:8
|
作者
Zhang, Jun [1 ]
Weng, Jingwen [1 ]
Zhou, Tiannian [1 ]
Ouyang, Dongxu [1 ]
Chen, Qinpei [2 ]
Wei, Ruichao [1 ,3 ]
Wang, Jian [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230022, Anhui, Peoples R China
[2] Tianjin Fire Res Inst MEM, Tianjin 300381, Peoples R China
[3] City Univ Hong Kong, Dept Civil & Architectural Engn, Hong Kong 999077, Peoples R China
来源
APPLIED SCIENCES-BASEL | 2019年 / 9卷 / 07期
基金
国家重点研发计划;
关键词
stairwell; smoke flow; numerical simulation; temperature; building fire; EXPANDED POLYSTYRENE FOAM; HEAT-FLUX; VENTILATION; MOVEMENT; SPREAD; SHAFTS; MODEL;
D O I
10.3390/app9071431
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
The aim of this study was to evaluate the transport phenomena of smoke flow and vertical temperature distribution in a 21-story stairwell with multiple fire locations and openings. A large eddy simulation (LES) method was used to model the smoke flow in a stairwell model with a set of simulation parameters, wherein the fire heat release rate (HRR) and fire location were varied. Based on the results, a wall attachment effect was found in three-dimensional figures. Moreover, with an increase in the fire HRR, the effects were more pronounced. The simulation results verified that the vertical temperature distribution is an index model with a natural logarithm, where the pre-finger factor and attenuation coefficient increase considerably in accordance with an increase in the fire HRR. Moreover, there was a decrease in the maximum temperature (T-m) with an increase in the fire location factor (h*) due to the upward thermal smoke. Moreover, heat mainly accumulates in the area above a fire source. However, h* has a slight influence on the time required to reach T-m within the range of 53-64 s. Furthermore, the direction of the airflow at each side opening in the stairwell varied in accordance with the variation in the fire location changes, and a regular calculation was carried out.
引用
收藏
页数:18
相关论文
共 50 条
  • [21] Numerical Investigation on Tunnel Fire Smoke Flow
    Lu Guodong
    Qu Zhiming
    Li Jinxian
    Jiang Jie
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL VII, PTS A AND B, 2008, 7 : 653 - 657
  • [22] SMOKE AND FIRE CONTROL IN HIGH-RISE BUILDINGS .1. STUDIES OF NEW-YORK CITY FIRE TESTS
    DECICCO, PR
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1973, 15 (05): : 33 - 33
  • [23] Investigation on the unstability of vortex induced resonance of high-rise buildings
    Wang, Lei
    Liang, Shuguo
    Huang, Guoqing
    Song, Jie
    Zou, Lianghao
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2018, 175 : 17 - 31
  • [24] Fire Prevention and Countermeasure Analysis of High - rise Buildings
    Luo Ruihua
    Lu Guobin
    PROCEEDINGS OF THE 4TH INTERNATIONAL SYMPOSIUM ON MINE SAFETY (2012), 2012, : 234 - 237
  • [25] FIRE HAZARD PROBLEMS IN HIGH-RISE BUILDINGS
    POWERS, WR
    ASHRAE JOURNAL, 1971, 13 (12): : 34 - &
  • [26] A transient network model for cross-regional layered fire smoke diffusion in high-rise buildings
    Wan, Shanshan
    Zhou, Di
    Wang, Na
    Dang, Tianyu
    Qiu, Dongwei
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 63
  • [27] Turbulent smoke flow in evacuation staircases during a high-rise residential building fire
    Chen, Yanqiu
    Zhou, Xiaodong
    Zhang, Taolin
    Hu, Yuqi
    Yang, Lizhong
    INTERNATIONAL JOURNAL OF NUMERICAL METHODS FOR HEAT & FLUID FLOW, 2015, 25 (03) : 534 - 549
  • [28] Common smoke control approaches in high-rise buildings
    Wittasek, Nathan B.
    Consulting-Specifying Engineer, 2019, 56 (04): : 36 - 44
  • [29] Comments on design of smoke management in high-rise buildings
    Hu, XZ
    Zhou, L
    PROCEEDINGS OF THE 4TH INTERNATIONAL CONFERENCE ON INDOOR AIR QUALITY, VENTILATION AND ENERGY CONSERVATION IN BUILDINGS, VOLS I-III, 2001, : 1333 - 1338
  • [30] Smoke Control System for High-Rise Buildings in Japan
    Moriyama, Shuji
    JOURNAL OF DISASTER RESEARCH, 2011, 6 (06) : 551 - 557