In early 2003, CPFL Energia, a Brazilian utility, was interested on evaluating the performance of natural ester filled transformers, especially regarding the highly increased overloading capability. As a field test, in association with the transformer manufacturer "Itaipu Transformadores", they built two prototype transformers. Based on original overhead distribution line three phases transformers of 15kV/45kVA, after small adjustments in the windings and cooling system, keeping same core and tank, associated with the use of natural ester based dielectric liquid, and increasing the average winding temperature rise limit from 55 degrees C to 85 degrees C and a hotspot temperature rise limit of 100 degrees C, the transformer nominal rating was shifted to 88kVA. Trying to ensure very high loading conditions, this transformer has been installed in the network replacing a 15kV/112.5kVA transformer. Submitted to an average loading of 82kVA and a peak loading of 123kVA (273% of nominal 45kVA rating), one could expect it to have a premature failure on such extremely harshening conditions. However, both transformer presented no problem along the years of operation. In 2015, after 12 years of interrupt high loading condition, one of them has been removed from the network for a complete teardown to be performed, including full screening of insulation materials. This paper will present full details of the performed test and the surprisingly positive achieved results, both regarding the negligible degradation of the dielectric liquid and the excellent performance of the solid insulating materials. The reduction of the degradation rate of the Kraft paper has been completely confirmed, as lowest value of degree of polymerization from several samples of paper that have been taken was at the hotspot region of the LV winding, but still above 830, while the expectation would be to have consumed above 50% of the total life expectation.
引用
收藏
页码:364 / 367
页数:4
相关论文
共 50 条
  • [21] Comparative Study of Kraft Paper Aged in Natural Ester with XRD and TG/DTG Analysis
    Sari, Yulia Erina
    Ritonga, Alvin D. S.
    Suwarno
    PROCEEDING OF 2019 INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING AND INFORMATICS (ICEEI), 2019, : 564 - 569
  • [22] Thermal Aging Performance of Cellulose Insulation in Natural Ester Liquid
    Contreras, Jose E.
    Rodriguez, Josue
    Gaytan, Carlos
    Greaves, Brad
    Prevost, Tom
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (04) : 1357 - 1362
  • [23] Quantitative Analysis Ageing Status of Natural Ester-paper Insulation and Mineral Oil-paper Insulation by Polarization/Depolarization Current
    Hao, Jian
    Liao, Ruijin
    Chen, George
    Ma, Zhiqin
    Yang, Lijun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (01) : 188 - 199
  • [24] Space Charge Behaviors of Ester Liquid and Kraft Paper Double-Layer Insulation Systems at Polarity Reversal
    Alshehawy, Abdelrahman M.
    Mu, Zhou
    Matharage, Shanika
    Liu, Qiang
    Wang, Zhongdong
    2022 IEEE 21ST INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2022,
  • [25] Kraft and Diamond Dotted paper thermally aged in mineral oil and natural ester: mechanical characterisation
    Fernandez-Diego, Cristina
    Ortiz, Alfredo
    Carrascal, Isidro A.
    Fernandez, Inmaculada
    Delgado, Fernando
    Olmo, Cristian
    2019 IEEE 20TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2019,
  • [26] Kinetic analysis and modelling of the ageing process for Kraft paper aged in natural ester dielectric fluid
    Ding, H. -Z.
    Wang, Z. D.
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 505 - 508
  • [27] Fourier Transform Infrared Spectroscopy (FTIR) Analysis of Transformer Insulation Paper in Natural Ester
    Munajad, Abi
    Subroto, Cahyo
    Suwarno
    2017 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND POWER SYSTEMS (ICHVEPS), 2017, : 446 - 450
  • [28] Study on Aging Characteristics of Mineral Oil/Natural Ester Mixtures-Paper Insulation
    Liao, Ruijin
    Hao, Jian
    Yang, Lijun
    Grzybowski, Stanislaw
    2011 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2011,
  • [29] Performance Analysis of Transformer Oil/Paper Insulation with Ester and Mixed Dielectric Fluids
    Rao, U. Mohan
    Pulluri, Harish
    Kumar, N. Goutham
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (05) : 1853 - 1862