Using thermostats for indoor climate control in offices: The effect on thermal comfort and heating/cooling energy use

被引:30
|
作者
Wang, Haiying [1 ,2 ]
Olesen, Bjarne W. [2 ]
Kazanci, Ongun B. [2 ]
机构
[1] Qingdao Univ Technol, Dept Environm & Municipal Engn, 11 Fushun Rd, Qingdao, Peoples R China
[2] Tech Univ Denmark, Dept Civil Engn, Int Ctr Indoor Environm & Energy, Nils Koppels Alle,Bldg 402, DK-2800 Lyngby, Denmark
基金
中国国家自然科学基金;
关键词
Room temperature control; Air temperature; Operative temperature; Energy use; Thermal comfort; Heating/cooling system; Convective system; Radiant system;
D O I
10.1016/j.enbuild.2018.12.030
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The most commonly used thermostat control variable in heating, ventilating and air-conditioning systems is air temperature. However, people's thermal comfort responds to operative temperature more directly than air temperature. Will the adoption of operative temperature based control lead to better thermal comfort and how will this affect the energy use? To get a better understanding about these questions, simulations have been performed based on three heating and cooling systems in three different geographical locations (Copenhagen, Denmark, Paris, France and Rome, Italy). The three systems are fan-coil system representing convective system and two radiant systems: floor heating/cooling system and radiant ceiling heating/cooling panel system. The results show that air temperature based thermostat control and operative temperature based thermostat control had different impacts on fan-coil system and radiant systems. For fan-coil system, the use of operative temperature based thermostat control had better thermal comfort conditions and higher energy use than that of air temperature based thermostat control. For the two radiant systems, the results were the opposite. The results were almost the same in different locations. Besides, the thermal comfort difference between the two controls of north office was smaller than that of south office. For fan-coil system, in south office, compared with air temperature based thermostat control, the hours of Cat. I (-0.2 <= PMV <= 0.2) increased 8.3% for building in Copenhagen, 8.8% paris and 14.2% Rome hours of Cat. IV (PMV <-0.7 or PMV > 0.7) decreased 2.5%, 3.9% and 7.1%, respectively, when operative temperature based thermostat control was used. Meanwhile, total energy supply increased 13.7% in Copenhagen, 14.3% in Paris and 12.7% in Rome. For radiant systems, the total energy use reduced 3.3% to 8.3% depending on location and type of system when operative temperature based control was used. With this reduction of energy use, PMV index in south office was still within the range of +/- 0.7 in most cases, which satisfied the thermal comfort requirement of Cat. III (-0.7 <= PMV <= 0.7) of EN 15251. Based on the results, it is suggested that air temperature based thermostat control be used in fan-coil system and operative temperature based thermostat control be used in radiant system in north office. For south office, operative temperature based thermostat control was considered better for fan-coil system and could be more energy efficient when used in radiant heating and cooling systems. (C) 2019 Elsevier B.V. All rights reserved.
引用
收藏
页码:71 / 83
页数:13
相关论文
共 50 条
  • [1] Using Thermostats for Indoor Climate Control in Office Buildings: The Effect on Thermal Comfort
    Kontes, Georgios D.
    Giannakis, Georgios I.
    Horn, Philip
    Steiger, Simone
    Rovas, Dimitrios V.
    ENERGIES, 2017, 10 (09)
  • [2] Thermal comfort and use of thermostats in Finnish homes and offices
    Karjalainen, Sami
    BUILDING AND ENVIRONMENT, 2009, 44 (06) : 1237 - 1245
  • [3] Thermal comfort in offices:comfort values and optimization of indoor control variables
    徐巍
    陈祥光
    赵军
    胡鹤
    JournalofBeijingInstituteofTechnology, 2011, 20 (01) : 123 - 128
  • [4] Effect of ventilation patterns on indoor thermal comfort and air-conditioning cooling and heating load using simulation
    Dian Sekartaji
    Yuji Ryu
    Didit Novianto
    City and Built Environment , 1 (1):
  • [5] Thermal and Comfort Control for Radiant Heating/Cooling Systems
    Beghi, Alessandro
    Cecchinato, Luca
    Rampazzo, Mirco
    2011 IEEE INTERNATIONAL CONFERENCE ON CONTROL APPLICATIONS (CCA), 2011, : 258 - 263
  • [6] Using footwarmers in offices for thermal comfort and energy savings
    Zhang, Hui
    Arens, Edward
    Taub, Mallory
    Dickerhoff, Darryl
    Bauman, Fred
    Fountain, Marc
    Pasut, Wilmer
    Fannon, David
    Zhai, Yongchao
    Pigman, Margaret
    ENERGY AND BUILDINGS, 2015, 104 : 233 - 243
  • [7] Prediction of indoor climate and thermal comfort for cooling in ventilated residence rooms
    Yao, Runming
    Chen, Qigao
    Li, Baizhan
    Peng, Xuya
    Feng, Ya
    Nuantong Kongtiao/HV & AC, 27 (06): : 5 - 9
  • [8] Implications of indoor climate control for comfort, energy and environment
    Mahdavi, A
    Kumar, S
    ENERGY AND BUILDINGS, 1996, 24 (03) : 167 - 177
  • [9] Field study on indoor thermal comfort of office buildings using evaporative cooling in the composite climate of India
    Tewari, Priyam
    Mathur, Sanjay
    Mathur, Jyotirmay
    Kumar, Sanjay
    Loftness, Vivian
    ENERGY AND BUILDINGS, 2019, 199 : 145 - 163
  • [10] Impacts on Indoor Thermal Comfort and Heating Energy Use in Hellenic Dwellings from Occupant Behavioral Reactions
    Dascalaki, Elena G.
    Balaras, Constantinos A.
    APPLIED SCIENCES-BASEL, 2021, 11 (14):