Field tests on the operational energy consumption of Chinese district heating systems and evaluation of typical associated problems

被引:43
|
作者
Zhang, Yichi [1 ]
Xia, Jianjun [1 ]
Fang, Hao [2 ]
Jiang, Yi [1 ]
Liang, Zhongwei [3 ]
机构
[1] Tsinghua Univ, Bldg Energy Res Ctr, Beijing 100084, Peoples R China
[2] Fulong Engn & Res Ctr Heating, Chifeng 024050, Peoples R China
[3] Chifeng Fulong Heating Co, Chifeng 024050, Peoples R China
关键词
District heating; Energy consumption; Overheating; Heat loss; System operation; EXISTING RESIDENTIAL BUILDINGS; EFFICIENCY RETROFIT; REGIONS; ISSUES; PUMP;
D O I
10.1016/j.enbuild.2020.110269
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Worldwide, China has the largest district heating (DH) area and is also the fastest growing country. This paper presents field measurement results for operational energy consumption from 38 DHSs to fill in the gaps in understanding of the current operational issues of the district heating system (DHS). The average heat consumption during the heating period was 98.6 kWh/m(2) and the monthly average electricity consumption for circulating pumps in the primary and secondary networks was 0.27 kWh/(m(2) x month) and 0.29 kWh/(m(2) x month), respectively. Thereafter, a systematic method for breaking down the energy consumption and quantitatively evaluating the underlying problems is presented. Based on several detailed measurements conducted in typical heat-exchange substations (HESs), it was found that overheating was the most prominent problem in energy-efficient buildings, constituting 23% of the total heat consumption. Another problem encountered was heat loss through pipes, which constituted approximately 5%-10% of the total heat consumption and was highly dependent on the actual conditions. In distribution networks, problems such as high resistance, high operational flow, and low pump efficiency were also identified and analyzed. Finally, practical energy-efficiency suggestions and future potential targets for the Chinese DHS are discussed from both a design and operational perspective. (C) 2020 Elsevier B.V. All rights reserved.
引用
收藏
页数:17
相关论文
共 24 条
  • [21] Developing a strategy to reduce energy consumption and CO2 emissions from underfloor heating systems in mosques: A case study of a typical neighbourhood mosque
    Yuksel, Ahmet
    Arici, Muslum
    Krajcik, Michal
    Civan, Mihriban
    Karabay, Hasan
    ENERGY AND BUILDINGS, 2023, 287
  • [22] Simulation-based performance evaluation of large-scale thermal energy storage coupled with heat pump in district heating systems
    Tosatto, Alice
    Dahash, Abdulrahman
    Ochs, Fabian
    JOURNAL OF ENERGY STORAGE, 2023, 61
  • [23] Evaluation of CCHP systems performance based on operational cost, primary energy consumption, and carbon dioxide emission by utilizing an optimal operation scheme
    Cho, Heejin
    Mago, Pedro J.
    Luck, Rogelio
    Chamra, Louay M.
    APPLIED ENERGY, 2009, 86 (12) : 2540 - 2549
  • [24] Does heat pumps perform energy efficiently as we expected: Field tests and evaluations on various kinds of heat pump systems for space heating
    Deng, Jiewen
    Wei, Qingpeng
    Liang, Mei
    He, Shi
    Zhang, Hui
    ENERGY AND BUILDINGS, 2019, 182 : 172 - 186