Condition assesment of cable insulation systems in operating nuclear power plants

被引:43
|
作者
Anandakumaran, K [1 ]
Seidl, W
Castaldo, PV
机构
[1] Ontario Hydro Technol, Toronto, ON, Canada
[2] Ontario Hydro Nucl, Toronto, ON, Canada
关键词
This work was partially funded by the Candu Owners Group R&D program; and their support is greatly acknowledged. Technical assistance was provided by T. Mac and C. MacPhee. We also thank J. V. Lind-ley; J; Janis; S; Barreca; and D.J . Stonkus for useful suggestions and comments;
D O I
10.1109/94.775626
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Four crosslinked polyethylene (XLPE) and ethylene propylene rubber (EPR) insulated cables were subjected to accelerated thermal, radiation, and sequential radiation and thermal exposure to simulate 20, 30, and 40 yr in-service environments in Ontario Hydro Nuclear Plants. Two sets of samples were evaluated. The first set contained 15 cm cable specimens in tubular form with the conductors removed, while the second set was made up of 4.3 m cable samples wound on mandrels, The cable samples were sequentially irradiated and thermally aged and subjected to an additional accident radiation exposure followed by a simulated loss of coolant accident (LOCA)/main steam line break (MSLB) steam test. During the steam test, samples were energized and their electrical characteristics continuously monitored. The material performance of the insulation was assessed using the 15 cm specimens during the various stages of aging exposure by conventional elongation measurement and by the use of micro-specimens with differential scanning calorimeter (DSC), oxidation induction time (OIT) and infrared carbonyl absorption techniques. The results from these samples were compared with the electrical performance of the cable samples wound on mandrels that had been subjected to the LOCA/MSLB steam test. The test results indicate that with the use of micro-specimens meaningful changes were obtained until the elongation values of the samples were reduced to 50% absolute. Electrical test data obtained for XLPE and EPR during the steam tests indicate that 50% absolute elongation values provide sufficient margin to withstand additional accident radiation, and to function electrically during design basis events.
引用
收藏
页码:376 / 384
页数:9
相关论文
共 50 条
  • [41] Probabilistic model of degradation of cable insulations in nuclear power plants
    Chang, Yuan-Shang
    Mosleh, Ali
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART O-JOURNAL OF RISK AND RELIABILITY, 2019, 233 (05) : 803 - 814
  • [43] ADVANCED CABLE-TESTING TECHNIQUES FOR NUCLEAR POWER PLANTS
    Hashemian, Hashem M.
    Bean, Wendell C.
    NUCLEAR TECHNOLOGY, 2011, 176 (03) : 414 - 429
  • [44] Sealed cable lead-ins for nuclear power plants
    Kostyukov, N.S.
    Atomnaya Energiya, 1993, 75 (06): : 487 - 490
  • [45] Application of optical diagnosis to aged low-voltage cable insulation in nuclear plants
    Takezawa, Y
    Katagiri, J
    Shoji, H
    2004 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2004, : 290 - 293
  • [46] Application of optical diagnosis to aged low-voltage cable insulation in nuclear plants
    Katagiri, Junichi
    Takezawa, Yoshitaka
    Shouji, Hiroshi
    IEEJ Transactions on Fundamentals and Materials, 2008, 128 (06) : 421 - 426
  • [47] TRANSITION TO ONLINE CABLE INSULATION CONDITION MONITORING
    Glass, S. W.
    Fifield, Leonard S.
    Spencer, Mychal P.
    PROCEEDINGS OF 2021 48TH ANNUAL REVIEW OF PROGRESS IN QUANTITATIVE NONDESTRUCTIVE EVALUATION (QNDE2021), 2021,
  • [48] Monitoring the Condition of Safety Barriers in Nuclear Power Plants
    E. A. Ivanov
    I. V. Pyrkov
    S. E. Smirnov
    D. S. Smirnov
    V. P. Povarov
    K. Nurlybaev
    Yu. N. Martynyuk
    P. N. Shmakov
    Atomic Energy, 2015, 118 : 79 - 84
  • [49] Monitoring the Condition of Safety Barriers in Nuclear Power Plants
    Ivanov, E. A.
    Pyrkov, I. V.
    Smirnov, S. E.
    Smirnov, D. S.
    Povarov, V. P.
    Nurlybaev, K.
    Martynyuk, Yu. N.
    Shmakov, P. N.
    ATOMIC ENERGY, 2015, 118 (02) : 79 - 84
  • [50] Experimental research on ampacity of extruded power cable under complex operating condition
    Zhao, Jian-Kang
    Lei, Qing-Quan
    Wang, Xiao-Bing
    Fan, You-Bing
    Liu, Song-Hua
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (12): : 3123 - 3128