Arm Overcurrent Analysis and Calculation of MMC-HVDC System with DC-link Pole-to-Pole Fault

被引:5
|
作者
Jiang, Bin [1 ]
Gong, Yanfeng [1 ]
机构
[1] North China Elect Power Univ, Elect & Elect Engn Sch, 2 Beinong Rd, Beijing 102206, Peoples R China
关键词
arm overcurrent calculation; DC-link pole-to-pole short-circuit characteristics; MMC-HVDC; regulation coefficient; MODULAR MULTILEVEL CONVERTER; FREQUENCY;
D O I
10.1080/15325008.2018.1432725
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Modular multilevel converter-based high voltage direct current (MMC-HVDC) technology has aroused extensive research and discussion. DC-link pole-to-pole short-circuit, the most severe fault type on DC side, has also been studied. This paper analyzes the DC-link pole-to-pole short-circuit characteristics and models the equivalent circuit of the fault current of each arm during the initial stage of the fault before the control system blocks the sub modules. Then, an improved equivalent analytic formula of calculating the arm overcurrent based on a regulation coefficient is proposed and the changing rule of the regulation coefficient is discussed under different operation conditions to provide reference for system design and relay protection setting. The calculated fault current based on the proposed methods are compared with the simulation results from PSCAD/EMTDC to verify that the results from analytic formula are accurate.
引用
收藏
页码:177 / 186
页数:10
相关论文
共 50 条
  • [31] Single Pole-to-Ground Fault Location Method for MMC-HVDC System Using Wavelet Decomposition and DBN
    Ye, Xinjie
    Lan, Sheng
    Xiao, Si-jie
    Yuan, Yongbin
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2021, 16 (02) : 238 - 247
  • [32] Recursive Calculation Method of MMC-HVDC DC Fault Current with AC Effect
    Wang W.
    He Z.
    Li G.
    Xin Y.
    Gu H.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 : 313 - 320
  • [33] The Enhanced DC Fault Current Calculation Method of MMC-HVDC Grid With FCLs
    Xu, Jianzhong
    Zhu, Sicheng
    Li, Chengyu
    Zhao, Chengyong
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2019, 7 (03) : 1758 - 1767
  • [34] The DC Fault Current Calculation of DC Fault Current Limiter Action Included in Bipolar MMC-HVDC Grid
    Zhu S.
    Zhao C.
    Li C.
    Xu J.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2019, 39 (02): : 469 - 478
  • [35] Pole-to-pole fault characteristics in VSC-HVDC transmission system with a resistance-inductance type superconducting fault current limiter
    Zhang, Jing
    Dai, Shaotao
    Luo, Pandian
    Song, Meng
    Ma, Tao
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 217
  • [36] Single Pole-to-Ground Fault Location System for MMC-HVDC Transmission Lines Based on Active Pulse and CEEMDAN
    Wu, Jian-Yu
    Lan, Sheng
    Xiao, Si-Jie
    Yuan, Yong-Bin
    IEEE ACCESS, 2021, 9 : 42226 - 42235
  • [37] Voltage Correlation Based Single Pole-to-Ground Fault Detection of MMC-HVDC Transmission Line
    An, Na
    Shu, Hongchun
    Yang, Bo
    Cao, Pulin
    Song, Jian
    Guo, Yu
    IEEE ACCESS, 2021, 9 : 118124 - 118133
  • [38] Single Pole-to-Ground Fault Analysis of MMC-HVDC Transmission Lines Based on Capacitive Fuzzy Identification Algorithm
    Shu, Hongchun
    An, Na
    Yang, Bo
    Dai, Yue
    Guo, Yu
    ENERGIES, 2020, 13 (02)
  • [39] Wavelet entropy based single pole grounding fault detection approach for MMC-HVDC overhead lines
    Wang S.
    Bi T.
    Jia K.
    1600, Power System Technology Press (40): : 2179 - 2185
  • [40] Transient characteristic analysis of converter bridge arm short circuit fault in MMC-HVDC system
    Zhang F.
    Du X.
    Chen K.
    2020, Electric Power Automation Equipment Press (40): : 180 - 187