Fault Judgment Method for Feeder in Smart Distribution Network Based on Voltage Phase Comparison

被引:0
|
作者
Cong, Wei [1 ]
Wang, Zeqian [1 ]
Zhang, Zijin [2 ]
Wei, Zhen [2 ]
Han, Aoyang [2 ]
An, Shuhuai [2 ]
机构
[1] Shandong Univ, Key Lab Power Syst Intelligent Dispatch & Control, Jinan 250061, Peoples R China
[2] Qingdao Power Supply Co, Qingdao 266002, Peoples R China
基金
中国国家自然科学基金;
关键词
Index Terms-Fault judgment method; integrity of protected line model; reference voltage; voltage phase comparison; MICROGRID PROTECTION; SYSTEMS; ISSUES; GENERATION;
D O I
10.1109/TIA.2023.3270862
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A large number of distributed generations (DGs) are penetrating into smart distribution network (SDN). Due to complicated fault characteristics and control strategies of DG, it is difficult for pilot protection dependent on correct identification of fault direction to reliably locate fault. A fault detection method derived from the judgement on the integrity of the protected line model is proposed in this paper. Instead of the analysis on the explicit fault characteristics of DG, the proposed method emphasizes the mathematical model of the protected line. Firstly, an elaborately-selected physical quantity is defined based on the mathematical constraints of the model. Then, the integrity of the model can be judged by analyzing the variation trend of the defined physical quantity in case of the faults either internal or external to the line in question. The results of fault detection based on the integrity of the protected line model can be used as the basic information for pilot protection to constitute the fault judgment method. In this paper, the reference voltage is defined as the physical quantity to judge whether the line model is intact. The setting principles of the impedance in reference voltage are analyzed in detail, so that the proposed method can adapt to the operating characteristics of smart distribution network. Simulation confirms that the proposed method is basically unaffected by the fault characteristics of DG. With help of the identification on the integrity, the pilot protection is improved to accurately locate the fault section.
引用
收藏
页码:4904 / 4913
页数:10
相关论文
共 50 条
  • [31] A state estimation and fault processing method based on big data analysis of smart distribution network
    Zhao Q.
    Li Y.
    Tian S.
    Duan Y.
    Tan Y.
    Cao Y.
    2016, Power System Technology Press (40): : 774 - 780
  • [32] S-transform approach for detecting the single-phase fault feeder in distribution network
    Faculty of Electric Power Engineering, Kunming University of Science and Technology, Kunming 650051, China
    不详
    Gaodianya Jishu, 2009, 12 (2963-2969): : 2963 - 2969
  • [33] Fault section location method for single-phase grounding fault in distribution network based on ESMD
    Yin Z.
    Sun G.
    Ding J.
    Lü F.
    Yuan H.
    Wei Z.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2019, 39 (06): : 173 - 178and191
  • [34] A fault location method for a single-phase fault for a distribution network with DGs based on model recognition
    Xu S.
    Ouyang J.
    Chen Y.
    Chen J.
    Wang J.
    Xiong X.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2024, 52 (05): : 51 - 60
  • [35] Estimation Method for Distribution Network Voltage Utilizing Smart Meter Measurements
    Iwabuchi, Kazunori
    Kaneko, Takeshi
    Shimoo, Takahiro
    2014 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT ASIA), 2014, : 504 - 507
  • [36] Research on Fault Early Warning method of Medium Voltage Distribution Network
    Xie, Xinlin
    Lu, Jue
    Xian, Pengfei
    Zhang, Haitao
    Lan, Wenjun
    Bu, Chenglang
    Sun, Yunlian
    2019 11TH INTERNATIONAL CONFERENCE ON INTELLIGENT HUMAN-MACHINE SYSTEMS AND CYBERNETICS (IHMSC 2019), VOL 1, 2019, : 102 - 105
  • [37] Judgment on arc grounding fault of digitalized distribution network
    Wang, X. (984401827@qq.com), 1600, Central South University of Technology (44):
  • [38] A New Method of Fault Phase Identification for High Voltage Transmission Lines Based on the Fault Component of Phase Voltage
    Chen Yang
    Hu Yan
    Tai Neng-ling
    THERMAL, POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 732-733 : 1056 - 1064
  • [39] Data-driven Based Identification Method of Feeder-Consumer Connectivity in Low-voltage Distribution Network
    Tang J.
    Cai Y.
    Zhou L.
    Yi Y.
    Chen G.
    Liang S.
    Zhang Y.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (11): : 127 - 134
  • [40] A Single-phase Grounding Fault Judgment Method Based on Steady-state Current Characteristics in Distribution
    Xu Yuhang
    Li Tongning
    Lin Yibin
    Lu Chaoteng
    Lu Huiji
    Zhang Wei
    2018 3RD ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2018), 2018, 366