Flexible composite suppression method for ground arc in resonant grounding system

被引:4
|
作者
You, Jianzhang [1 ,2 ]
Guo, Moufa [1 ,2 ]
Zheng, Zeyin [1 ,2 ]
Liu, Xinbin [1 ]
机构
[1] Fuzhou Univ, Sch Elect Engn & Automat, Fuzhou, Peoples R China
[2] Fujian Prov Univ, Engn Res Ctr Smart Distribut Grid Equipment, Fuzhou, Peoples R China
基金
中国国家自然科学基金;
关键词
LOCATION; PHASE; COIL;
D O I
10.1049/hve2.12354
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A current-voltage composite controller for an arc suppression inverter is designed. The current and voltage at the fault point are reduced by injecting current and regulating the neutral point voltage to completely eliminate the risk of fire and overvoltage caused by a single-line-to-ground fault arc. A cascaded inverter is used, and the effects of the ground parameter measurement, line impedance voltage drop, harmonic current and arc suppression coil on the current control, voltage control and composite control methods are analysed and compared. Finally, software simulations and industrial prototype experiments show that the proposed composite control method is effective and less affected by ground parameter measurement and line impedance voltage drop and has better adaptability.
引用
收藏
页码:1296 / 1305
页数:10
相关论文
共 50 条
  • [1] A Novel Unified Measurement Method for Ground Capacitance and Arc Suppression Coil Inductance of Resonant Grounding System
    Xie, Dawei
    Wang, Jingjing
    Zhu, Zhenggao
    Ding, Chao
    Wang, Lei
    Tian, Hongqiang
    Li, Shenghu
    2022 INTERNATIONAL CONFERENCE ON MECHANICAL ENGINEERING AND POWER ENGINEERING, MEPE, 2022, : 7 - 12
  • [2] Measuring Method of Capacitance to Ground in Resonant Grounding System Based on Transient Information after Arc Extinguishing
    Xue Y.
    Li G.
    Xu B.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2020, 35 (07): : 1521 - 1528
  • [3] A Novel Measuring Method of Capacitance to Ground in Resonant Grounding System
    Zhu Liang
    Liu Yuling
    Yang Qi
    Yu Kun
    Zeng Xiangjun
    Guo Tingting
    Yang Miao
    2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 1650 - 1653
  • [4] Arc Extinction Moment Identifying Method for Flexible Grounding System Based on SOGI
    Li, Guang
    Zhang, Weiqi
    Zhang, Zhihua
    2024 7TH INTERNATIONAL CONFERENCE ON RENEWABLE ENERGY AND POWER ENGINEERING, REPE 2024, 2024, : 39 - 43
  • [5] Flexible Fusion Arc Suppression Method for Large Generator Stator Ground Fault
    Huang, Junjie
    Guo, Moufa
    Zhang, Binlong
    Dianwang Jishu/Power System Technology, 2024, 48 (11): : 4748 - 4757
  • [6] Novel flexible and adaptive arc suppression method for single-phase grounding fault in distribution network
    You, Jianzhang
    Guo, Moufa
    Cai, Wenqiang
    Gao, Wei
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2022, 42 (04): : 146 - 153
  • [7] Grounding Fault Analysis and Protection Measures Study of Composite Grounding Arc-suppression Modes
    Yu, B.
    Li, H.
    Zhu, W. J.
    Liu, H. F.
    Liang, W. W.
    Zhang, Z. D.
    Guo, S. Y.
    2018 2ND INTERNATIONAL CONFERENCE ON POWER AND ENERGY ENGINEERING (ICPEE 2018), 2018, 192
  • [8] Control Method of Displacement Overvoltage Suppression Switching to Ground Fault Arc-suppression for Flexible Power Source
    Jiang S.
    Ding Y.
    Shi X.
    Liu W.
    Tao Z.
    Shi Y.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2021, 45 (20): : 140 - 147
  • [9] Flexible Regulation Method of Single-phase Grounding Fault in Distribution Network Based on Rotating Arc Suppression
    Huang Z.
    Guo Q.
    Tu C.
    Hou Y.
    Jiang F.
    Lu B.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2022, 46 (24): : 152 - 161
  • [10] Suppression Strategy on Neutral Point Overvoltage in Resonant Grounding System Considering Single Line-to-ground Fault
    Wang, Hui
    Guo, Moufa
    Zheng, Zeyin
    Cai, Wenqiang
    Tang, Jie
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 206