Transient Synchronous Stability Analysis of Grid-Forming Photovoltaic Grid-Connected Inverters during Asymmetrical Grid Faults

被引:2
|
作者
He, Wenwen [1 ]
Yao, Jun [1 ]
Xu, Hao [1 ]
Zhong, Qinmin [1 ]
Xu, Ruilin [2 ]
Liu, Yuming [2 ]
Li, Xiaoju [2 ]
机构
[1] Chongqing Univ, Sch Elect Engn, State Key Lab Power Transmiss Equipment Technol, Chongqing 400044, Peoples R China
[2] State Grid Chongqing Elect Power Res Inst, Chongqing 401121, Peoples R China
关键词
grid-forming photovoltaic grid-connected converter; transient synchronous stability; asymmetric grid faults; grid code; SYNCHRONIZATION STABILITY;
D O I
10.3390/en17061399
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Compared with the traditional grid-following photovoltaic grid-connected converter (GFL-PGC), the grid-forming photovoltaic grid-connected converter (GFM-PGC) can provide voltage and frequency support for power systems, which can effectively enhance the stability of power electronic power systems. Consequently, GFM-PGCs have attracted great attention in recent years. When an asymmetrical short-circuit fault occurs in the power grid, GFM-PGC systems may experience transient instability, which has been less studied so far. In this paper, a GFM-PGC system is investigated under asymmetrical short-circuit fault conditions. A novel Q-V droop control structure is proposed by improving the traditional droop control. The proposed control structure enables the system to accurately control the positive- and negative-sequence reactive current without switching the control strategy during the low-voltage ride-through (LVRT) period so that it can meet the requirements of the renewable energy grid code. In addition, a dual-loop control structure model of positive- and negative-sequence voltage and current is established for the GFM-PGC system under asymmetrical short-circuit fault conditions. Based on the symmetrical component method, the composite sequence network of the system is obtained under asymmetrical short-circuit fault conditions, and positive- and negative-sequence power-angle characteristic curves are analyzed. The influence law of system parameters on the transient synchronous stability of positive- and negative-sequence systems is quantitatively analyzed through the equal area criterion. Finally, the correctness of the theoretical analysis is verified by simulation and hardware-in-the-loop experiments.
引用
收藏
页数:19
相关论文
共 50 条
  • [31] Singular Perturbation Model and Transient Stability Analysis of Grid-connected Converter Under Weak Grid Faults
    Zhang Z.
    Zhu D.
    Ma Y.
    Zou X.
    Hu J.
    Kang Y.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (02): : 454 - 465
  • [32] Selective Virtual Impedance for Overcurrent Limitation in Grid-Forming Inverters under Asymmetrical Faults
    Morales-Munoz, Alvaro
    Freijedo, Francisco D.
    Pugliese, Sante
    Liserre, Marco
    IEEE 15TH INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS FOR DISTRIBUTED GENERATION SYSTEMS, PEDG 2024, 2024,
  • [33] Transient Stability Analysis and Enhancement of Grid-Forming and Grid-Following Converters
    Xu, Chenhang
    Zou, Zhixiang
    Yang, Jiajun
    Wang, Zheng
    Chen, Wu
    Buticchi, Giampaolo
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN INDUSTRIAL ELECTRONICS, 2024, 5 (04): : 1396 - 1408
  • [34] Faults Classification in Grid-Connected Photovoltaic Systems
    Attouri, Khadija
    Hajji, Mansour
    Mansouri, Majdi
    Nounou, Hazem
    Kouadri, Abdelmalek
    Bouzrara, Kais
    2021 18TH INTERNATIONAL MULTI-CONFERENCE ON SYSTEMS, SIGNALS & DEVICES (SSD), 2021, : 1431 - 1437
  • [35] Control and Stability Analysis of Current-Controlled Grid-Connected Inverters in Asymmetrical Grids
    Akhavan, Ali
    Golestan, Saeed
    Vasquez, Juan C.
    Guerrero, Josep M.
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (12) : 14252 - 14264
  • [36] A DQ-Frame Asymmetrical Virtual Impedance Control for Enhancing Transient Stability of Grid-Forming Inverters
    Jin, Zheming
    Wang, Xiongfei
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (04) : 4535 - 4544
  • [37] Study on small-signal stability of grid-connected grid-forming inverter system based on hybrid-synchronous control
    Qiu X.
    Lin H.
    Zhou Y.
    Yan X.
    Zang T.
    Qiu Y.
    Zhou B.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2023, 43 (09): : 172 - 178and185
  • [38] Current Limitation Strategy For Grid-Forming Converters Under Symmetrical And Asymmetrical Grid Faults
    Rosso, Roberto
    Engelken, Soenke
    Liserre, Marco
    2020 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2020, : 3746 - 3753
  • [39] On The Implementation of an FRT Strategy for Grid-Forming Converters Under Symmetrical and Asymmetrical Grid Faults
    Rosso, Roberto
    Engelken, Soenke
    Liserre, Marco
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2021, 57 (05) : 4385 - 4397
  • [40] Transient Current Calculation of Grid-Connected Converters under Grid Faults
    Liu, Li
    Dai, Tao
    Huang, Meng
    2018 IEEE INTERNATIONAL POWER ELECTRONICS AND APPLICATION CONFERENCE AND EXPOSITION (PEAC), 2018, : 310 - 314