Optimal parameters setting for soft open point to improve power quality indices in unbalanced distribution systems considering loads and renewable energy sources uncertainty

被引:8
|
作者
Ebrahimi, Hasan [1 ]
Galvani, Sadjad [1 ]
Talavat, Vahid [1 ]
Farhadi-Kangarlu, Mohammad [1 ]
机构
[1] Urmia Univ, Fac Elect & Comp Engn, Dept Power Engn, Orumiyeh, Iran
关键词
Soft open point (SOP); Harmonic distortion; Voltage unbalance; Uncertainty; Data clustering; Power quality; NETWORK RECONFIGURATION; GENERATION; PLACEMENT;
D O I
10.1016/j.epsr.2024.110155
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The importance of power quality has increased in recent years due to ever-increasing nonlinear load demands. In addition, real distribution networks are inherently unbalanced, and load demands are not distributed equally among phases. Voltage harmonic distortion and unbalancing can undesirably damage/affect equipment operating and protective and measurement devices performance. On the other hand, uncertainties arising from renewable energy sources (RESs) and load demands increase the complexity of any action to improve the network operating performance. A soft open point (SOP) is a new power electronic device that is capable of being installed in a distribution system's end feeders, to improve network operating performance. This paper focuses on the optimal determination of the location and hourly control of SOP in a 4 -wire distribution network to achieve minimum harmonic distortion, voltage unbalance, and active power losses by active and reactive power control, as well as selective harmonic current injection. To efficiently encounter uncertainties, the K-medoids data clustering method has been used to select appropriate scenarios. Also, the multi-objective particle swarm optimization (MOPSO) algorithm is applied to solve the main optimization problem, and the technique for order of preference by similarity to ideal solution (TOPSIS) is applied to select a preferred result. To show the efficiency and applicability of the proposed technique, the method is implemented on a modified 4 -wire IEEE 33 -bus distribution network.
引用
收藏
页数:18
相关论文
共 42 条
  • [41] Active and reactive power coordination optimization of an active distribution network considering a three-terminal soft open point with energy storage and demand response
    Mi Y.
    Shen J.
    Lu C.
    Meng F.
    Nan Y.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2024, 52 (03): : 104 - 118
  • [42] Optimal placement and operation of soft open points, capacitors, and renewable distributed generators in distribution power networks to reduce total one-year energy loss
    Tran, Hai Van
    Truong, Anh Viet
    Phan, Tan Minh
    Nguyen, Thang Trung
    HELIYON, 2024, 10 (05)