Study on the performance enhancement of ice storage and melting processes in an ice-on-coil thermal energy storage system

被引:12
|
作者
Yan, Wei-Mon [1 ,2 ]
Huang, Chu-Yeh [1 ,2 ]
Gao, Kai-En [1 ,2 ]
Amani, Mohammad [3 ]
Chien, Liang-Han [1 ,2 ]
Homayooni, Ahmad [3 ]
机构
[1] Natl Taipei Univ Technol, Dept Energy & Refrigerating Air Conditioning Engn, Taipei 10608, Taiwan
[2] Natl Taipei Univ Technol, Res Ctr Energy Conservat New Generat Residential C, Taipei 10608, Taiwan
[3] Arak Univ Technol, Dept Mech Engn, Arak, Iran
关键词
Charge rate; Discharge rate; Phase change material; Finned coil; Thermal energy storage; Energy efficiency; PHASE-CHANGE MATERIALS; HEAT-TRANSFER ENHANCEMENT; PCM; NANOFLUIDS; WATER; TUBE; COMPOSITE; BEHAVIOR;
D O I
10.1016/j.est.2023.108410
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Air conditioners equipped with an ice storage system store a large amount of latent heat during the off-peak period at night, and use the stored cold energy for the air conditioner during the peak period of the day, thereby greatly reducing peak power consumption. In this study, an experimental analysis was conducted to evaluate the cold storage and cooling characteristics of an ice-on-coil storage system. Firstly, the influence of the inlet brine temperature, flowrate, and concentration on the discharge rate was studied. It was observed that all parameters were directly proportional to the discharge rate, and the effect of brine inlet temperature was more pronounced. Secondly, the alumina nanofluid as a phase change material was employed in the system for enhancing the thermal performance. The experimental results showed that using nanofluid shortened the freezing time, while it had a negative impact on the thermal behavior during the ice melting. Thirdly, the ice storage coils with spiral fins were used. It was concluded that the employment of finned coils reduced the melting time by 24.0 %, increased the average discharge rate by 74.4 %, and raised the cumulative discharge capacity by 63.5 % compared with original bare coil design.
引用
收藏
页数:15
相关论文
共 50 条
  • [21] Experimental study of water solidification phenomenon for ice-on-coil thermal energy storage application utilizing falling film
    Sait, Hani H.
    APPLIED THERMAL ENGINEERING, 2019, 146 : 135 - 145
  • [22] Experimental and numerical study of ice storage and melting process of external melting ice coil
    Chang, Chun
    Xu, Xiaoyu
    Guo, Xinxin
    Rasakhodzhaev, Bakhramzhan
    Zhao, Mingzhi
    Yuan, Guofeng
    JOURNAL OF ENERGY STORAGE, 2024, 77
  • [23] Influence of geometrical parameters arrangement on solidification process of ice-on-coil storage system
    Seyed Soheil Mousavi Ajarostaghi
    Kurosh Sedighi
    Mojtaba Aghajani Delavar
    Sébastien Poncet
    SN Applied Sciences, 2020, 2
  • [24] Influence of geometrical parameters arrangement on solidification process of ice-on-coil storage system
    Ajarostaghi, Seyed Soheil Mousavi
    Sedighi, Kurosh
    Delavar, Mojtaba Aghajani
    Poncet, Sebastien
    SN APPLIED SCIENCES, 2020, 2 (01):
  • [25] Experimental and numerical study of thin ring and annular fin effects on improving the ice formation in ice-on-coil thermal storage systems
    Jannesari, Hamid
    Abdollahi, Naeim
    APPLIED ENERGY, 2017, 189 : 369 - 384
  • [26] Experimental validation of a numerical model for an internal melt ice-on-coil thermal storage tank
    Neto, JHM
    Krarti, M
    ASHRAE TRANSACTIONS 1997, VOL 103, PT I, 1997, 103 : 125 - 138
  • [27] Performance enhancement of fin attached ice-on-coil type thermal storage tank for different fin orientations using constrained and unconstrained simulations
    Kim, M. H.
    Duong, X. Q.
    Chung, J. D.
    HEAT AND MASS TRANSFER, 2017, 53 (03) : 1005 - 1015
  • [28] Performance enhancement of fin attached ice-on-coil type thermal storage tank for different fin orientations using constrained and unconstrained simulations
    M. H. Kim
    X. Q. Duong
    J. D. Chung
    Heat and Mass Transfer, 2017, 53 : 1005 - 1015
  • [29] Direct external ice-on-coil storage tanks for buildings load management
    Habeebullah, Badr A.
    Zaki, Galal M.
    FIRST INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT, PROCEEDINGS VOLS 1-3, 2008, : 2002 - 2009
  • [30] Experimental investigation of discharge performance and temperature distribution of an external melt ice-on-coil storage tank
    Wang, BL
    Zhang, MY
    Li, XT
    Yang, XD
    HVAC&R RESEARCH, 2003, 9 (03): : 291 - 308