Synchro-Squeezing Transform for High-Impedance Fault Detection in Power Distribution Systems

被引:4
|
作者
Chandrakar, Ruchi [1 ]
Dubey, Rahul Kumar [2 ]
Panigrahi, Bijaya Ketan [1 ]
机构
[1] Indian Inst Technol, Dept Elect Engn, New Delhi 110016, India
[2] Bosch Engn & Business Solut, Bengaluru 560095, India
来源
IEEE SYSTEMS JOURNAL | 2023年 / 17卷 / 04期
关键词
Feature extraction; Discrete wavelet transforms; Phase distortion; Wavelet analysis; Switches; Standards; Power distribution; Distortion; high-impedance fault (HIF); phase current; reconstruction error; synchro-squeezing transform (SST); WAVELET TRANSFORM;
D O I
10.1109/JSYST.2023.3315958
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Distribution systems are most vulnerable to high-impedance faults (HIFs). These types of faults occur when the primary electrical conductor fails or comes into contact with high-impedance substances, such as asphalt, grass, sand, concrete, etc. The magnitude of fault current is particularly low for certain grounding materials due to the nonlinear and high impedance of resistive surfaces. As a result, traditional overcurrent relays usually fail to operate, which may lead to fire hazards. Also, they are unable to detect the characteristics of HIF accurately, leading to maloperation. The motive of this work is to overcome the above-mentioned challenges of conventional relays. This article proposes a linear time-frequency wavelet-based tool called synchro-squeezing transform (SST) for the distortion detection of HIF in power distribution networks. This study uses wavelet SST to redistribute signal energy in the frequency domain. The wavelet SST is applied to the measured phase current signal for maximum time-frequency ridge extraction. Then, the inverse SST operation is performed to reconstruct the signal from the time-frequency domain. The reconstruction error is calculated between the original signal and the reconstructed signal. The reconstruction error value is compared with the base value to discriminate HIF from other non-HIF events. The impact of distributed generation on HIF features are further explored by EV penetration in the RSCAD distribution system and validated on the IEEE-13 node test feeder using RTDS. The main contributions of the proposed method are viz., it can correctly distinguish HIF from severe faults, switching events, energization scenarios, and noisy environments. The algorithm has been compared with the previously reported HIF detection techniques, and the efficacy of SST is presented through real-time simulation results. SST has a fast detection time and less computation burden.
引用
收藏
页码:5920 / 5930
页数:11
相关论文
共 50 条
  • [31] High Impedance Fault Detection Protection Scheme for Power Distribution Systems
    Moloi, Katleho
    Davidson, Innocent
    MATHEMATICS, 2022, 10 (22)
  • [32] Review on High-Impedance Fault Detection Techniques
    Dhawas P.V.
    Bedekar P.P.
    Nandankar P.V.
    Journal of The Institution of Engineers (India): Series C, 2025, 106 (1) : 443 - 443
  • [33] Application of signal processing techniques and intelligent classifiers for high-impedance fault detection in ensuring the reliable operation of power distribution systems
    Varghese, P. Rini
    Subathra, M. S. P.
    George, S. Thomas
    Kumar, Nallapaneni Manoj
    Suviseshamuthu, Easter Selvan
    Deb, Sanchari
    FRONTIERS IN ENERGY RESEARCH, 2023, 11
  • [34] High impedance fault detection on distribution systems
    Wester, CG
    1998 RURAL ELECTRIC POWER CONFERENCE, 1998, : C51 - C55
  • [35] Gradient Characteristics of Fault Impedance in Distribution Network of Vegetation High-Impedance Fault
    Tang, Rui
    Zhang, Wenhai
    2024 7TH ASIA CONFERENCE ON ENERGY AND ELECTRICAL ENGINEERING, ACEEE 2024, 2024, : 150 - 154
  • [36] High-impedance fault detection and localization in distribution feeders with microprocessor based devices
    Uriarte, FM
    Centeno, V
    37TH NORTH AMERICAN POWER SYMPOSIUM, PROCEEDINGS, 2005, : 219 - 224
  • [37] Active High-Impedance Fault Detection Method for Resonant Grounding Distribution Networks
    Yao, Zhiwei
    Liu, Yang
    Chen, Jian
    Ji, Jinpeng
    Zhang, Mengdi
    Gong, Yanyong
    IEEE ACCESS, 2024, 12 : 10932 - 10945
  • [38] A new differential protection scheme based on Synchro-squeezing transform applied to AC Micro-Grid
    Moravej, Z.
    Ebrahimi, A.
    Barati, M.
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 231
  • [39] Detection of High Impedance Fault in Power Distribution Systems Using Mathematical Morphology
    Gautam, Suresh
    Brahma, Sukumar M.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) : 1226 - 1234
  • [40] Field experience with high-impedance fault detection relays
    Depew, Alvin C.
    Parsick, Jason M.
    Dempsey, Robert W.
    Benner, Carl L.
    Russell, B. Don
    Adamiak, Mark G.
    2006 59TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2006, : 84 - +