D-Distance Technique to Determine Failure Probability of Power Circuit Breaker

被引:0
|
作者
Kumpalavalee, Suphon [1 ]
Suwanasri, Thanapong [1 ]
Suwanasri, Cattareeya [2 ]
Phadungthin, Rattanakorn [3 ]
机构
[1] King Mongkuts Univ Technol North Bangkok, Sirindhorn Int Thai German Grad Sch Engn TGGS, Elect & Software Syst Engn, Bangkok 10800, Thailand
[2] King Mongkuts Univ Technol North Bangkok, Fac Engn, Dept Elect & Comp Engn, Bangkok 10800, Thailand
[3] King Mongkuts Univ Technol North Bangkok, Coll Ind Technol, Dept Elect Engn Technol, Bangkok 10800, Thailand
关键词
D-distance; power circuit breaker; condition index; renovation index; risk assessment; risk factor; weighting-scoring method; TIME;
D O I
10.3390/en16020847
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, a new D-distance factor is proposed to determine the failure probability and to prioritize maintenance actions of power circuit breakers in high-voltage substations. The D-distance factor is calculated by using the condition index and renovation index of a high-voltage circuit breaker (HVCB). To facilitate effective decision-making on maintenance with a simple method and less computational effort, the proposed model incorporates the weighting-scoring method (WSM) and analytical hierarchy process (AHP) with the various diagnostic methods for condition index assessments as well as the operation requirements of HVCBs for renovation index assessments. Many significant parameters from circuit breaker testing, such as insulation resistance, contact resistance, contact timing, SF6 gas measurements, gas leakage rate, visual inspection, etc., have been considered for condition index determination. In addition to these, other significant parameters, such as age of the circuit breaker, age of the interrupter and mechanism, number of fault current interruptions, actual load current to rated current ratio, actual short circuit current to rated interrupting current ratio, maintenance ability, spare parts availability, maintenance expertise level, etc., are also considered for renovation index determination. To validate the proposed model, the practical test data of twenty 115 kV HVCBs in various substations of a distribution utility in Thailand were utilized and tested. By analyzing the actual condition and operation requirement of the circuit breaker, the output, as the condition index and renovation index using the proposed method, is discussed with HVCB experts in the utility to adjust the scores and weights of all criteria to obtain the most accurate and reliable model. The results show that the D-distance technique measured from the risk matrix, which is defined as the failure probability, can be used to rank the maintenance schedule from urgent to normal maintenance tasks. In addition, various failure probabilities in the risk matrix of the circuit breaker can be used to determine the appropriate maintenance strategies for the power circuit breaker in each group. Finally, the proposed method could help the utility managers and maintenance engineers manage the maintenance planning effectively and easily for thousands of HVCBs in the grid, and it can be further applied with other high-voltage equipment in both transmission and distribution systems to facilitate the maintenance activities according to available costs and human resources.
引用
收藏
页数:17
相关论文
共 14 条
  • [1] Analysis of Failure Data to Determine the Failure Pattern of HV Circuit Breaker Components
    Suwanasri, Cattareeya
    Suwnansri, Thanapong
    Srisongkram, Warunee
    2014 INTERNATIONAL ELECTRICAL ENGINEERING CONGRESS (IEECON), 2014,
  • [2] Probability-Based Circuit Breaker Modeling for Power System Fault Analysis
    Lei, Chengwei
    Tian, Weisong
    Zhang, Yucheng
    Fu, Ruiyun
    Jia, Ruting
    Winter, Robb
    2017 THIRTY SECOND ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION (APEC), 2017, : 979 - 984
  • [3] Inventory Management of Power Circuit Breaker Using Failure Data Analysis
    Suwanasri, Thanapong
    Srisongkram, Warunee
    Suwanasri, Cattareeya
    2014 INTERNATIONAL CONFERENCE ON PROBABILISTIC METHODS APPLIED TO POWER SYSTEMS (PMAPS), 2014,
  • [4] Design of generator circuit breaker failure protection for nuclear power plants
    Xie, Chuangshu
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2014, 38 (06): : 123 - 127
  • [5] Probability Based Worn Circuit Breaker Modeling and Risk Evaluation on Potential Power Grid Failures
    Tian, Weisong
    Lei, Chengwei
    Jia, Ruting
    Winter, Robb M.
    2017 IEEE 7TH ANNUAL INTERNATIONAL CONFERENCE ON CYBER TECHNOLOGY IN AUTOMATION, CONTROL, AND INTELLIGENT SYSTEMS (CYBER), 2017, : 1431 - 1436
  • [6] Analysis of Capacitor Cells Failure Due to Circuit Breaker Pole Discrepancy in RRVPNL Power Grid
    Mahela, Om Prakash
    Gupta, Neeraj
    Ola, Sheesh Ram
    2014 IEEE STUDENTS' CONFERENCE ON ELECTRICAL, ELECTRONICS AND COMPUTER SCIENCE (SCEECS), 2014,
  • [7] Simulation and analysis of a gas insulated switchgear explosion accident caused by a failure of high-voltage circuit breaker in a thermal power plant
    Zhang, Xun
    Dai, Kai
    Niu, Wei
    Xie, Rongbin
    Zeng, Huarong
    Wen, Yi
    Ma, Xiaohong
    JOURNAL OF ENGINEERING-JOE, 2019, 2019 (04): : 3418 - 3424
  • [8] The reliability evaluation of configuration of bus arrangement in substations by the variable failure rate of power circuit breaker under time-based maintenance
    Lipirodjanapong, Sumate
    Suwanasri, Cattareeya
    Suwanasri, Thanapong
    2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 705 - 708
  • [9] A Highly Linear and Efficient CMOS RF Power Amplifier With a 2-D Circuit Synthesis Technique
    Ding, Miaofu
    Gard, Kevin G.
    Steer, Michael B.
    IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, 2012, 60 (09) : 2851 - 2862
  • [10] Sensorless control of a PMSM drive post an open circuit failure based on 3D-SVPWM technique
    Saleh, Kamel
    Sumner, Mark
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2022, 17 (07) : 1072 - 1082