Improving energy and water consumption of a data center via air free-cooling economization: The effect weather on its performance

被引:21
|
作者
Silva-Llanca, Luis [1 ,2 ]
Ponce, Carolina [2 ]
Bermudez, Elizabeth [2 ]
Martinez, Diego [2 ]
Diaz, Andres J. [3 ]
Aguirre, Fabian [1 ,2 ]
机构
[1] Univ La Serena, Inst Multidisciplinario Invest & Postgrad, Raul Bitran 1305, La Serena, Coquimbo, Chile
[2] Univ La Serena, Dept Ingn Mecan, Benavente 980, La Serena, Coquimbo, Chile
[3] Univ Diego Portales, Escuela Ingn Ind, Fac Ingn & Ciencias, Ctr Energia & Desarrollo Sustentable, Ave Ejercito 441, Santiago, Metropolitana, Chile
关键词
Air-free cooling; Data centers; Thermal management; SIDE ECONOMIZERS; SYSTEM; SIMULATION; EFFICIENCY; OPERATION;
D O I
10.1016/j.enconman.2023.117344
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the past two decades, data centers have significantly grown in size and number around the globe, leading to substantial energy and water stress wherever they operate. Thermal management typically represents half of the total energy consumption in traditional data centers. This work studies the energy and water savings that air -side free-cooling yields under diverse weather conditions. We modeled a free-cooling system and a conventional data center using MATLAB. The hourly weather data was obtained from a publicly available online repository for the Chilean territory. Using air-side free-cooling for data center thermal management is feasible in various weather conditions. Locations with colder temperatures (< 20 degrees C) and higher humidity (> 60%) are more favorable as they require minimal use of the chiller and/or humidifier. These conditions are present in BSk'(s) Cold Semi-arid climate with dry summer and oceanic influence, as well as Csb' Mediterranean climate (warm summer) with oceanic influence. However, locations with drier air (< 50%) and warmer temperatures (> 20 degrees C), such as those found in ET(w) Tundra climate with dry winter, BWk(w) Cold Desert climate with dry winter, or BSk(s) Cold Semi-arid climate with dry summer, are less suitable for air free cooling. Even under suboptimal energy and water savings, the air-side economizer still performed considerably better than a conventional data center cooling method (using CRAH units).
引用
收藏
页数:19
相关论文
共 26 条
  • [21] Chilled water temperature set-point reset based on outdoor air temperature and its cooling energy performance in an office building
    Young Jun Lee
    Sung Hyup Hong
    Jong Man Lee
    Yeo Beom Yoon
    Jong Min Choi
    Kwang Ho Lee
    Journal of Mechanical Science and Technology, 2022, 36 : 1557 - 1568
  • [22] Effect of air temperature non-uniformity on water-air heat exchanger thermal performance - Toward innovative control approach for energy consumption reduction
    Ramadan, M.
    Khaled, M.
    El Hage, H.
    Harambat, F.
    Peerhossaini, H.
    APPLIED ENERGY, 2016, 173 : 481 - 493
  • [23] Energy differential-based optimal outdoor air ventilation strategy for high-tech cleanrooms concerning free cooling and its performance evaluation
    Zhao, Wenxuan
    Li, Hangxin
    Wang, Shengwei
    BUILDING AND ENVIRONMENT, 2023, 231
  • [24] A novel data center free radiating system driven by waste heat and wind energy system (DCFRWWs) and its operation performance analysis
    Zou, Zetai
    Yang, Chao
    Hu, Licui
    Zhang, Qiang
    ENERGY AND BUILDINGS, 2024, 310
  • [25] Thermal Performance and Energy Saving Analysis of Indoor Air-Water Heat Exchanger Based on Micro Heat Pipe Array for Data Center
    Jing, Heran
    Quan, Zhenhua
    Zhao, Yaohua
    Wang, Lincheng
    Ren, Ruyang
    Liu, Zichu
    ENERGIES, 2020, 13 (02)
  • [26] Performance improvement of cogeneration plants in hot arid regions via sustainable turbine inlet air cooling technologies: An energy-water nexus comparative case study
    Abdulrahim, Ali H.
    Chung, Jacob N.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2021, 45 (07) : 10765 - 10793