Simulation analysis on energy consumption and economy of CPU cooling system based on loop heat pipe for data center

被引:11
|
作者
Du, Sheng [1 ,3 ]
Zhang, Quan [1 ]
Zou, Sikai [2 ]
Meng, Fanxi [1 ]
Liu, Lijun [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Hunan, Peoples R China
[2] East China Jiaotong Univ, Sch Civil Engn & Architecture, Nanchang 330013, Peoples R China
[3] CRRC Zhuzhou Inst Co Ltd, Zhuzhou 412001, Peoples R China
基金
中国国家自然科学基金;
关键词
Data center; CPU cooling; Loop heat pipe; System energy model; Economic analysis; THERMAL MANAGEMENT; PRESSURE-DROP; CONDENSATION; TEMPERATURE; PERFORMANCE; EVAPORATOR; CAPACITY; POWER; FLOW;
D O I
10.1016/j.tsep.2023.102115
中图分类号
O414.1 [热力学];
学科分类号
摘要
The existing computer room air conditioner (CRAC) system hardly satisfies the rapidly increasing cooling demand of the server's CPU with high heat flux, and it has ultra-high refrigerating energy consumption. As a solution, a water-cooled loop heat pipe (LHP) system can be adapted to cool the CPU in the data center and decrease refrigerating energy consumption. In this study, a Hybrid cooling system combining a water-cooled LHP system and a water-cooled CRAC system is proposed, and the system energy model is developed to analyze its annual energy consumption and economy. Based on a case data center using a lake water source, the effects of system setting points on energy consumption are investigated. The results show the Hybrid system has a considerable energy saving rate of 34.9%-52.4% than the conventional CRAC system. Meanwhile, the annual energy consumption of the Hybrid system declines substantially with increasing CPU power ratio, while it drops slightly with increasing CPU safety temperature. Additionally, the economic analysis illustrates that although the initial investment of Hybrid cooling system is 44.13%-77.74% higher than CRAC system, the dynamic payback periods are 2.48-6.64 years for system retrofit under different operating stages, and the life cycle cost savings are 22.06%-36.45%.
引用
收藏
页数:15
相关论文
共 50 条
  • [21] Static analysis on energy consumption of water loop heat pump system
    Ma, Zuiliang
    Cao, Yuan
    Harbin Jianzhu Daxue Xuebao/Journal of Harbin University of Civil Engineering and Architecture, 30 (06): : 68 - 74
  • [22] ENERGY-SAVING AND EMISSION REDUCTION SYSTEM OF DATA CENTER HEAT PIPE BASED ON LATENT HEAT OF WATER EVAPORATION
    Zhao, Jinhui
    Wang, Panle
    Li, Jingshun
    Gu, Tianwei
    Lu, Jiaxu
    THERMAL SCIENCE, 2022, 26 (05): : 4475 - 4487
  • [23] Experimental Investigation of Heat Transfer and Flow Characteristics of Split Natural Cooling System for Data Center Based on Micro Heat Pipe Array
    Jing, Heran
    Quan, Zhenhua
    Zhao, Yaohua
    Wang, Lincheng
    Ren, Ruyang
    Dong, Ruixue
    Wu, Yuting
    ENERGIES, 2022, 15 (12)
  • [24] Operating characteristics analysis and optimization of loop heat pipe radiation cooling system in space reactor
    Xia, Genglei
    Zhou, Tao
    Zhang, Yuandong
    Dai, Shoubao
    Jiao, Guanghui
    NUCLEAR ENGINEERING AND DESIGN, 2024, 420
  • [25] Experimental analysis and FEM simulation of loop heat pipe charged with diamond nanofluid for desktop PC cooling
    Gunnasegaran, P.
    Abdullah, M. Z.
    Yusoff, M. Z.
    7TH INTERNATIONAL CONFERENCE ON COOLING & HEATING TECHNOLOGIES (ICCHT 2014), 2015, 88
  • [26] Numerical simulation of flattened heat pipe with double heat sources for CPU and GPU cooling application in laptop computers
    Sanhan, Wisoot
    Vafai, Kambiz
    Kammuang-Lue, Niti
    Terdtoon, Pradit
    Sakulchangsatjatai, Phrut
    JOURNAL OF COMPUTATIONAL DESIGN AND ENGINEERING, 2021, 8 (02) : 524 - 535
  • [27] Experimental research and energy saving analysis of an integrated data center cooling and waste heat recovery system
    Chen, Xiaoxuan
    Wang, Xinyi
    Ding, Tao
    Li, Zhen
    APPLIED ENERGY, 2023, 352
  • [28] Design and key technology of the energy consumption management system for the liquid cooling data center
    Lai, Yibo
    Fang, Xiang
    Han, Rongjie
    Xuan, Yi
    Huang, Jiabin
    ENERGY SCIENCE & ENGINEERING, 2023, 11 (03) : 1284 - 1293
  • [29] Impacts of Local Cooling Technologies on Air Cooled Data Center Server Performance: Test Data Analysis of Heatsink, Direct Liquid Cooling and Passive 2-Phase Enhanced Air Cooling Based on Loop Heat Pipe
    Vuckovic, Maxime
    Depret, Nicolas
    2016 32ND THERMAL MEASUREMENT, MODELING & MANAGEMENT SYMPOSIUM (SEMI-THERM), 2016, : 71 - 80
  • [30] Analysis on energy efficiency of an integrated heat pipe system in data centers
    Wang, Zhenying
    Zhang, Xiaotong
    Li, Zhen
    Luo, Ming
    APPLIED THERMAL ENGINEERING, 2015, 90 : 937 - 944