Impact of HVAC Operation and Air Distribution Schemes on Thermal Comfort and Energy Consumption in Intermittent High-Occupancy Buildings: A Case of Mosques

被引:4
|
作者
Samiuddin, Syed [1 ]
Budaiwi, Ismail M. [2 ]
Mohammed, Mohammed Alhaji [2 ]
机构
[1] King Fahd Univ Petr & Minerals, Dept Prep Engn Technol, Dhahran 31261, Saudi Arabia
[2] King Fahd Univ Petr & Minerals, Dept Architectural Engn, Dhahran 31261, Saudi Arabia
关键词
Energy consumption; Thermal comfort; Heating; ventilating; and air-conditioning operation; Intermittent operation; Mosque; COMPUTATIONAL FLUID-DYNAMICS; DISTRIBUTION-SYSTEMS; VENTILATION SYSTEM; LECTURE THEATER; PERFORMANCE; SIMULATION; QUALITY; EFFICIENCY; ROOM; STRATEGIES;
D O I
10.1061/JAEIED.AEENG-1451
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In high-occupancy intermittent buildings, such as mosques and theaters, it is challenging to design proper air distribution systems and HVAC (heating, ventilating, and air-conditioning) operation strategies to maintain thermal comfort at reduced energy consumption. This study investigates the thermal and energy performance of a high-occupancy intermittently operated mosque in Saudi Arabia. DesignBuilder software (version v4.7) was used for the coupled energy and computational fluid dynamics simulations. The continuous HVAC operation results indicate an annual cooling energy consumption of 181 kW center dot h/m(2), with only two under-floor air distribution system models [through-wall supply with eight diffusers at 3 m height and ceiling return (M5) and through-wall supply with 10 diffusers at 3 m height and wall return at 3 m from the ground (M6)] achieving thermal comfort with only a few cold spots in the throw areas. The intermittent operation saved 30% of the total annual energy consumption, reducing it from 181 to 127 kW center dot h/m(2), in turn, saving 35% of the total cooling energy consumption. Intermittent HVAC operation cases achieved thermal comfort, except for the four-way ceiling supply and wall return (M1). Therefore, implementing intermittent HVAC operation strategies in high-occupancy buildings significantly reduces energy consumption, while achieving thermal comfort when appropriate air distribution strategies are employed. These results provide critical guidelines for the design and operation of proper HVAC systems.
引用
收藏
页数:15
相关论文
共 39 条
  • [1] Assessment of thermal comfort in high-occupancy spaces with relevance to air distribution schemes: A case study of mosques
    Samiuddin, S.
    Budaiwi, Ismail M.
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2018, 39 (05): : 572 - 589
  • [2] Acceptable indoor air quality at reduced energy consumption for high-occupancy buildings with intermittent operation
    Budaiwi, Ismail Mohammed
    Mohammed, Mohammed Alhaji
    ARCHITECTURAL SCIENCE REVIEW, 2023, 66 (03) : 242 - 258
  • [3] HVAC system operational strategies for reduced energy consumption in buildings with intermittent occupancy: The case of mosques
    Budaiwi, I.
    Abdou, A.
    ENERGY CONVERSION AND MANAGEMENT, 2013, 73 : 37 - 50
  • [4] Post Energy Audit of Two Mosques as a Case Study of Intermittent Occupancy Buildings: Toward more Sustainable Mosques
    El Fouih, Younness
    Allouhi, Amine
    Abdelmajid, Jamil
    Kousksou, Tarik
    Mourad, Youssef
    SUSTAINABILITY, 2020, 12 (23) : 1 - 22
  • [5] Energy consumption, thermal comfort, and indoor air quality in mosques: Impact of Covid-19 measures
    Yuksel, Ahmet
    Arici, Muslum
    Krajcik, Michal
    Civan, Mihriban
    Karabay, Hasan
    JOURNAL OF CLEANER PRODUCTION, 2022, 354
  • [6] Urban climate - Impact on energy consumption and thermal comfort of buildings
    Remund, Jan
    Grossenbacher, Urs
    PROCEEDINGS OF THE ISES EUROSUN 2018 CONFERENCE - 12TH INTERNATIONAL CONFERENCE ON SOLAR ENERGY FOR BUILDINGS AND INDUSTRY, 2018, : 1614 - 1623
  • [7] AN ANALYSIS OF ENERGY-CONSUMPTION AND THERMAL COMFORT IN BUILDINGS IN DAILY INTERMITTENT HEATING
    NANNEI, E
    TANDA, G
    BRICK AND BLOCK MASONRY, VOLS 1-3, 1988, : 1248 - 1259
  • [8] Prediction of thermal comfort, IAQ, and energy consumption in a dense occupancy environment with the under floor air distribution system
    Fathollahzadeh, Mohammad Hassan
    Heidarinejad, Ghassem
    Pasdarshahri, Hadi
    BUILDING AND ENVIRONMENT, 2015, 90 : 96 - 104
  • [9] Urban and future climate - Impact on energy consumption and thermal comfort of buildings
    Remund, Jan
    Grossenbacher, Urs
    PROCEEDINGS OF BUILDING SIMULATION 2019: 16TH CONFERENCE OF IBPSA, 2020, : 4738 - 4745
  • [10] Effects of Partition on Thermal Comfort, Indoor Air Quality, Energy Consumption, and Perception in Air-Conditioned Buildings
    Aryal, Pradip
    Leephakpreeda, Thananchai
    JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2016, 138 (05):