A fast computational method for internal temperature field in Oil-Immersed power transformers

被引:12
|
作者
Liu, Gang [1 ]
Hu, Wanjun [1 ]
Hao, Shiyuan [1 ]
Gao, Chenglong [1 ]
Liu, Yunpeng [1 ]
Wu, Weige [2 ]
Li, Lin [3 ]
机构
[1] North China Elect Power Univ, Hebei Prov Key Lab Power Transmiss Equipment Secur, Baoding, Peoples R China
[2] Hebei Prov Key Lab Electromagnet & Struct Performa, Baoding, Peoples R China
[3] North China Elect Power Univ Renewable Energy Sour, State Key Lab Alternate Elect Power Syst, Beijing, Peoples R China
关键词
Oil -immersed transformer; Proper orthogonal decomposition; Radial basis function response surface method; Reduced Order Model; OPTIMIZATION;
D O I
10.1016/j.applthermaleng.2023.121558
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to improve the computational efficiency of the steady-state temperature rise of oil-immersed power transformer windings, this paper proposes a temperature field reduced order model(ROM) based on proper orthogonal decomposition (POD) and response surface method(RSM). The method takes the operating conditions of the transformer as input and uses the POD method as a carrier, and establishes a fast calculation model of the steady-state temperature field through RSM, thus achieving fast calculation from transformer operating data to the entire temperature field. The paper first analyzes the reduction characteristics of the POD method, and then introduces the RSM to establish the correlation between the POD modal coefficients and the transformer conditions. Compared with traditional surrogate models, this method can obtain high-precision surrogate relationships with a small number of sample points, and the time cost of establishing is relatively low. The method aims to quickly obtain the POD modal coefficients through the winding conditions, thereby skipping the complex nonlinear calculation and efficiently reconstructing the winding temperature field with the reduced modal. The related examples show that the method has good computational accuracy and efficiency. In a 2D forced oil circulation cooling model, out of 100 test conditions, the error is not more than 2.0 K compared with the fullorder calculation, and the total calculation time is only 3.13 s. Finally, based on a 35 kV natural oil circulation cooling transformer, a temperature rise test platform is constructed to verify the effectiveness of the method. The experimental results show that the calculated error of the ROM is not more than 5 K compared with the experimental results, and the single-step calculation time is only 0.73 s, which has greatly improved the computational efficiency compared with full-order calculation of the same scale. The proposed method in this study achieves a second-level calculation efficiency for the transformer winding temperature, providing a feasible solution for digital online monitoring of transformer temperatures.
引用
收藏
页数:15
相关论文
共 50 条
  • [41] 3D modeling of winding hot spot temperature in oil-immersed transformers
    Reza Kebriti
    S. M. Hassan Hossieni
    Electrical Engineering, 2022, 104 : 3325 - 3338
  • [42] Study on Electrothermal Characteristics of Oil-immersed Power Transformers in Early Stage of Interturn Faults
    Zhang L.
    Sheng G.
    Ni Z.
    Jiang X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (15): : 6124 - 6135
  • [43] New perspectives to overloading with accurate modeling of thermal transients in oil-immersed power transformers
    Van der Veken, W
    Declercq, J
    Baelmans, M
    Van Mileghem, S
    2001 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION, VOLS 1 AND 2: DEVELOPING NEW PERSPECTIVES, 2001, : 147 - 152
  • [44] Evolution of graphical methods for the identification of insulation faults in oil-immersed power transformers: A review
    Bustamante, Sergio
    Manana, Mario
    Arroyo, Alberto
    Laso, Alberto
    Martinez, Raquel
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2024, 199
  • [45] Fault Diagnosis of Oil-Immersed Power Transformers Using SVM and Logarithmic Arctangent Transform
    Hu, Qin
    Mo, Jiaqing
    Ruan, Saisai
    Zhang, Xin
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2022, 17 (11) : 1562 - 1569
  • [46] 3D modeling of winding hot spot temperature in oil-immersed transformers
    Kebriti, Reza
    Hossieni, S. M. Hassan
    ELECTRICAL ENGINEERING, 2022, 104 (05) : 3325 - 3338
  • [47] Novel Hotspot Temperature Prediction of Oil-Immersed Distribution Transformers: An Experimental Case Study
    Abdali, Ali
    Abedi, Ali
    Mazlumi, Kazem
    Rabiee, Abbas
    Guerrero, Josep M.
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2023, 70 (07) : 7310 - 7322
  • [48] A Novel Anti-maloperation Gas Relay for Internal Fault Protection of Oil-immersed Transformers
    Xue, Bing
    Yi, Wanshuang
    Li, Yongbo
    Liu, Chengxiang
    Tian, Siyu
    Ma, Jinyang
    Zhang, Tengbo
    Wan, Shuting
    ADVANCES IN ELECTRICAL AND COMPUTER ENGINEERING, 2025, 25 (01) : 21 - 28
  • [49] A Multivariable Sensing System for Condition Monitoring of Oil-Immersed Transformers
    Wani, Shufali Ashraf
    Sarathi, Ramanujam
    Subramanian, Venkatachalam
    IEEE SENSORS JOURNAL, 2025, 25 (06) : 9708 - 9717
  • [50] DEVELOPMENT OF AN OIL-IMMERSED SURGE ARRESTER FOR DISTRIBUTION TRANSFORMERS.
    McMillen, C.J.
    Comber, M.G.
    Hopkinson, R.H.
    Schoendube, C.W.
    IEEE transactions on power apparatus and systems, 1985, PAS-104 (09): : 2482 - 2491