A fast computational method for internal temperature field in Oil-Immersed power transformers

被引:12
|
作者
Liu, Gang [1 ]
Hu, Wanjun [1 ]
Hao, Shiyuan [1 ]
Gao, Chenglong [1 ]
Liu, Yunpeng [1 ]
Wu, Weige [2 ]
Li, Lin [3 ]
机构
[1] North China Elect Power Univ, Hebei Prov Key Lab Power Transmiss Equipment Secur, Baoding, Peoples R China
[2] Hebei Prov Key Lab Electromagnet & Struct Performa, Baoding, Peoples R China
[3] North China Elect Power Univ Renewable Energy Sour, State Key Lab Alternate Elect Power Syst, Beijing, Peoples R China
关键词
Oil -immersed transformer; Proper orthogonal decomposition; Radial basis function response surface method; Reduced Order Model; OPTIMIZATION;
D O I
10.1016/j.applthermaleng.2023.121558
中图分类号
O414.1 [热力学];
学科分类号
摘要
In order to improve the computational efficiency of the steady-state temperature rise of oil-immersed power transformer windings, this paper proposes a temperature field reduced order model(ROM) based on proper orthogonal decomposition (POD) and response surface method(RSM). The method takes the operating conditions of the transformer as input and uses the POD method as a carrier, and establishes a fast calculation model of the steady-state temperature field through RSM, thus achieving fast calculation from transformer operating data to the entire temperature field. The paper first analyzes the reduction characteristics of the POD method, and then introduces the RSM to establish the correlation between the POD modal coefficients and the transformer conditions. Compared with traditional surrogate models, this method can obtain high-precision surrogate relationships with a small number of sample points, and the time cost of establishing is relatively low. The method aims to quickly obtain the POD modal coefficients through the winding conditions, thereby skipping the complex nonlinear calculation and efficiently reconstructing the winding temperature field with the reduced modal. The related examples show that the method has good computational accuracy and efficiency. In a 2D forced oil circulation cooling model, out of 100 test conditions, the error is not more than 2.0 K compared with the fullorder calculation, and the total calculation time is only 3.13 s. Finally, based on a 35 kV natural oil circulation cooling transformer, a temperature rise test platform is constructed to verify the effectiveness of the method. The experimental results show that the calculated error of the ROM is not more than 5 K compared with the experimental results, and the single-step calculation time is only 0.73 s, which has greatly improved the computational efficiency compared with full-order calculation of the same scale. The proposed method in this study achieves a second-level calculation efficiency for the transformer winding temperature, providing a feasible solution for digital online monitoring of transformer temperatures.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] A review of temperature prediction methods for oil-immersed transformers
    Guo, Yi
    Chang, Yuan
    Lu, Bing
    MEASUREMENT, 2025, 239
  • [2] Electrical insulation diagnostic method and maintenance criteria for oil-immersed power transformers
    Okubo, H.
    Kobayashi, S.
    Aoshima, Y.
    Takagi, H.
    Mori, E.
    Ikeda, M.
    Kishi, A.
    IEEE International Conference on Conduction and Breakdown in Dielectric Liquids, ICDL, 1999, : 372 - 377
  • [3] Internal streaming simulation of oil-immersed transformers and on-line fault prediction method
    Tu, Wei-Min
    Cui, Guo-Min
    Li, Yu
    Hu, Xiang-Bai
    Dianwang Jishu/Power System Technology, 2010, 34 (05): : 195 - 200
  • [4] Numerical Simulation and Fast Calculation of Temperature Field of Oil-immersed Transformer
    Yao, Zhoufei
    Liu, Haotong
    Ding, Min
    PROCEEDINGS OF THE 4TH INTERNATIONAL SYMPOSIUM ON NEW ENERGY AND ELECTRICAL TECHNOLOGY, ISNEET 2023, 2024, 1255 : 68 - 83
  • [5] Recent diagnostic technology on oil-immersed power transformers in Japan
    Tsuchie, M
    IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXHIBITION 2002: ASIA PACIFIC, VOLS 1-3, CONFERENCE PROCEEDINGS: NEW WAVE OF T&D TECHNOLOGY FROM ASIA PACIFIC, 2002, : 1496 - 1499
  • [6] On the estimation.of elapsed life of oil-immersed power transformers
    Pradhan, MK
    Ramu, TS
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) : 1962 - 1969
  • [7] Review of Studies on the Hot Spot Temperature of Oil-Immersed Transformers
    Lin, Lin
    Qiang, Chengdan
    Zhang, Hui
    Chen, Qingguo
    An, Zhen
    Xu, Weijie
    ENERGIES, 2025, 18 (01)
  • [8] Recent diagnostic technology on oil-immersed power transformers in Japan
    1600, IEEE Power Engineering Society, IEEE Japan (Institute of Electrical and Electronics Engineers Inc.):
  • [9] An Empirical Study on Assessment Method for Aging Medium & Large Oil-immersed Power Transformers
    Chang, Jeong-Ho
    Oh, Seung-Chan
    Lee, Heung-Ho
    PROCEEDINGS OF THE 2012 IEEE INTERNATIONAL POWER MODULATOR AND HIGH VOLTAGE CONFERENCE, 2012, : 731 - 735
  • [10] Ensemble Anomaly Data Detection Method for Oil-immersed Transformers
    Kari, Tusongjiang
    Abudukerimu, Munawaer
    Jia, Jing
    Ma, Xiaojing
    2024 6TH ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM, AEEES 2024, 2024, : 463 - 468