Performance assessment of heat exchanger coated with encapsulated ultra-high salt content desiccant

被引:4
|
作者
Pan, Q. W. [1 ,2 ]
Ruan, Y. L. [3 ]
Li, X. Y. [1 ]
Zhao, Q. Y. [1 ]
Wang, B. [1 ,2 ]
Gan, Z. H. [1 ,4 ]
机构
[1] Hangzhou City Univ, Cryogen Ctr, Hangzhou 310015, Peoples R China
[2] Key Lab Safe Construct & Intelligent Maintenance U, Hangzhou 310015, Peoples R China
[3] Nanjing Inst Technol, Sch Energy & Power Engn, Nanjing 211169, Peoples R China
[4] Zhejiang Univ, Key Lab Refrigerat & Cryogen Technol Zhejiang Prov, Hangzhou 310027, Peoples R China
基金
中国国家自然科学基金;
关键词
Ultra-high salt content; Composite desiccant; Porous membrane; Desiccant coated heat exchanger; SILICA-GEL; COMPOSITE DESICCANTS; ADSORPTION;
D O I
10.1016/j.applthermaleng.2023.120974
中图分类号
O414.1 [热力学];
学科分类号
摘要
Desiccant coated heat exchanger (DCHE) provides an effective way to decouple the sensible and latent heat loads and improves the energy efficiency by raising the evaporation temperature of air conditioning system. In this paper, a new encapsulation of porous membrane is adopted to fabricate the ultra-high salt content composite desiccant, AFLi30@P, whose salt content can reach over 85w %. Its adsorption capacity can be as high as 3.8 g g-1 at 27 & DEG;C and 70 % humidity. And then, DCHE based on AFLi30@P is developed. Experiments on both desiccant and DCHE levels are conducted to investigate the effects of temperature and humidity conditions on the dehumidification performance. The results reveal that, different from air temperature and dehumidification temperature, air humidity and regeneration temperature has positive effects on the DCHE dehumidification performance. Comparison between vertical and horizontal placements presents that horizontal placement of AFLi30@P on DCHE can avoid the effect of gravity to realize more uniform adsorption and heat transfer capacity. Dehumidification capacity of AFLi30@P DCHE can reach 1.08 g g-1 under the conditions of 27 & DEG;C air temper-ature, 70 % air humidity, 30 & DEG;C dehumidification temperature and 60 & DEG;C regeneration temperature.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Numerical Assessment of Ultra-high Performance Concrete Material
    Yin, Hor
    Shirai, Kazutaka
    Teo, Wee
    5TH ASIA CONFERENCE ON MECHANICAL AND MATERIALS ENGINEERING (ACMME 2017), 2017, 241
  • [32] Comparison of performance characteristics of desiccant coated air-water heat exchanger with conventional air-water heat exchanger - Experimental and analytical investigation
    Sun, X. Y.
    Dai, Y. J.
    Ge, T. S.
    Zhao, Y.
    Wang, R. Z.
    ENERGY, 2017, 137 : 399 - 411
  • [33] Performance Assessment of Ultra-High Durability Concrete Produced From Recycled Ultra-High Durability Concrete
    Borg, Ruben Paul
    Cuenca, Estefania
    Garofalo, Roberto
    Schillani, Fabrizio
    Nasner, Milena Lozano
    Ferrara, Liberato
    FRONTIERS IN BUILT ENVIRONMENT, 2021, 7
  • [34] Simulation investigation on solar powered desiccant coated heat exchanger cooling system
    Ge, T. S.
    Dai, Y. J.
    Li, Y.
    Wang, R. Z.
    APPLIED ENERGY, 2012, 93 : 532 - 540
  • [35] Energy effectiveness analysis of desiccant coated heat exchanger based on numerical method
    Liu, M. Z.
    Vivekh, P.
    Chen, W. D.
    Chua, K. J.
    APPLIED THERMAL ENGINEERING, 2023, 220
  • [36] Performance of an internally cooled and heated desiccant-coated heat and mass exchanger: Effectiveness criteria and design methodology
    Jagirdar, Mrinal
    Lee, Poh Seng
    Padding, Johan T.
    APPLIED THERMAL ENGINEERING, 2021, 188
  • [37] Design and performance prediction of desiccant coated heat exchanger using ANFIS-AI tool and dynamic model
    Priyadarshi, Gaurav
    Baruah, Dipankar
    Naik, B. Kiran
    APPLIED THERMAL ENGINEERING, 2022, 217
  • [38] Performance study of SAPO-34 and FAPO-34 desiccants for desiccant coated heat exchanger systems
    Zheng, X.
    Wang, R. Z.
    Ge, T. S.
    Hu, L. M.
    ENERGY, 2015, 93 : 88 - 94
  • [39] Feasible study of a self-cooled solid desiccant cooling system based on desiccant coated heat exchanger
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    Li, Y.
    APPLIED THERMAL ENGINEERING, 2013, 58 (1-2) : 281 - 290
  • [40] Investigation on activated carbon-sodium polyacrylate coated aluminum sheets for desiccant coated heat exchanger
    Chen, K.
    Zheng, X.
    Wang, S. N.
    ENERGY, 2022, 245